Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-06-20 Cont ID  
Sent By pleduc Date 2019-06-20 Time   Rev Time 0.00
Received By pleduc Date 2019-06-20 Time 15:53 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-06-05 Cont ID  
Sent By bwoods Date 2019-06-05 Time   Rev Time 0.00
Received By pleduc Date 2019-06-05 Time 10:04 Sent To I
Notes
2019-06-05 10:13:206/5/19
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET 3 OF 7 - THE REVISED HEAD LOCATION COULD NOT
 BE IDENTIFIED PER THE APPLICATION LOCATION OR ANY OTHER
 PLAN SHEET.
  
 PER NFPA 1
  
 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION
 DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND
 SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE
 CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD
 CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS.
  
 PLEASE CLEARLY CLOUD OR OTHERWISE CLEARLY INDCIATE THE
 LOCATION.
  
  
 2) SHEET 3 OF 7 - THE SPRINKLER LEGEND DOES NOT
 INDICATE THE ADDITION OF 2 NEW HEADS PER THE
 APPLICATION.
  
 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION
 DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND
 SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE
 CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD
 CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS.
  
 PLEASE CLEARLY CLOUD OR OTHERWISE CLEARLY INDCIATE THE
 THE ADDITION OF TWO HEAD ON ALL APPLICABLE SHEETS.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-20 Cont ID  
Sent By cpuell Date 2019-06-20 Time 16:45 Rev Time 0.00
Received By cpuell Date 2019-06-18 Time 09:26 Sent To  
Notes
2019-06-20 09:26:36RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-05 Cont ID  
Sent By cpuell Date 2019-06-05 Time 15:50 Rev Time 0.00
Received By cpuell Date 2019-05-31 Time 15:12 Sent To  
Notes
2019-06-03 15:12:25REVISION ROUTED TO FIRE INBOX