Plan Review Details - Permit 19051536
Plan Review Stops For Permit 19051536
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-09-30 Cont ID  
Sent By jwitmer Date 2019-09-30 Time 12:31 Rev Time 0.00
Received By jwitmer Date 2019-09-30 Time 11:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-08-20 Cont ID  
Sent By jwitmer Date 2019-08-20 Time 08:09 Rev Time 0.00
Received By jwitmer Date 2019-08-20 Time 06:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-18 Cont ID  
Sent By jwitmer Date 2019-06-18 Time 11:38 Rev Time 0.00
Received By jwitmer Date 2019-06-17 Time 13:09 Sent To  
Notes
2019-06-18 11:38:332017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19051536
 ADD: 201 ARKONA CT.
 CONT: MIAMI SYSTEMS INC.
 TEL: 561-394-5450
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JUNE 17, 2019
 ACTION: DENIED
 1) PLEASE NOTE THE STATED VALUE FOR THIS PERMIT IS LOW
 THE COST BREAKDOWN DOES NOT INCLUDE THE PROVISIONS FOR
 THE SIDELIGHT GLASS OR SINGLE FRENCH DOOR (SHEET LS 1
 SHOWS DOUBLE DOORS AT THE FRONT ENTRY) NOR DOES THE
 COST BREAK DOWN INCLUDE 22 NEW IMPACT WINDOWS OR THE
 FEES FOR THE ARCHITECTURAL FIRM AND THE M-E-P ENGINEERS
 OR THE STRUCTURAL ENGINEER. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE A REVISED ITEMIZED LIST AND SUBTRACT
 THESE LINE ITEMS AND THEIR VALUE FROM THE OVERALL
 BUILDING VALUE STATED ON THE PERMIT APPLICATION FOR
 THIS PROJECT. THE REMAINING BALANCE WILL BE AFFECTIVELY
 THE VALUE OF THE BUILDING YOU WILL BE PAYING FOR THIS
 PERMIT. THE BUILDING DEPARTMENT DOES NOT WANT TO
 COLLECT TWICE FOR THE VALUE OF THESE SUB-PERMITS NOT
 COVERED UNDER THE PRIME OR MASTER PERMIT.
 2A) THE STATED VALUE FOR THE PROJECT CURRENTLY IS
 $336,000.00 DOLLARS IN VALUE, THIS WILL INCREASE.
 PLEASE ALSO PROVIDE ON EITHER THE ARCHITECT?S OR
 CONTRACTOR?S LETTER HEAD WHERE UP TO 0.20% OF THE
 STATED VALUE OF THE PROJECT WILL BE SPENT ON MAKING
 ACCESSIBLE UPGRADES TO THE BUILDING AND COMPLIANCE WITH
 EITHER 202.4.1 DISPROPORTIONATE COST OR 202.4.2.
 ACCESSIBLE FEATURES IN THE EVENT OF DISPROPORTIONATE
 COST.
 PLEASE LIST IN ORDER WHERE THE FUNDS WERE SPENT IN
 ORDER TO MAKE THE PATH OF TRAVEL SHALL BE MADE
 ACCESSIBLE THE PRIMARY FUNCTION AREA. 2017
 FBC-ACCESSIBILITY CODE.
  
 2017 FBC-ACCESS. CODE 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 3) SHEET X1 UNDER THE HEADING OF DESCRIPTION LIST
 BOTTLED WATER IN LIEU OF HI-LO WALL MOUNT ADA DRINKING
 FOUNTAINS. PLEASE REVIEW THE 2017 FBC-PLUMBING CODE
 SECTION 410.2 DRINKING FOUNTAINS ARE NOT REQUIRED WHEN
 THERE IS AN OCCUPANT LOAD OF 15 OR FEWER. WHEN THEY ARE
 REQUIRED THEN COMPLIANCE WITH THE FBC-ACCESSIBILITY
 CODE (2017) SECTION 211.2 IS REQUIRED.
  
 2017 ACCESS. CODE 211.2 MINIMUM NUMBER. NO FEWER THAN
 TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH 602.7.
  
 4) SHEET X1 UNDER THE HEADING OF PROJECT PLAN REVIEW
 DATA MISSING INFORMATION NOT GIVEN IS THE BUILDING AND
 OCCUPANT LOAD FACTOR (TABLE 1004.1.2. OF THE FBC-B) OR
 OCCUPANT LOAD.
  
 5A) THE LIFE SAFETY SHEET IN THE BOTTOM LEFT CORNER OF
 THE PAGE INDICATES THE PLANS ARE DRAWN TO 1/8 INCH
 SCALE, WHEREAS WHEN YOU SCALE THE PLAN, IT APPEARS TO
 BE DRAWN TO ? INCH SCALE. TYPO, PLEASE CORRECT
 THE DISCREPANCY. 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED. APPEARS TO BE A TYPO.
  
 5B) SHEET LS 1 INDICATES THE MAXIMUM ALLOWED TRAVEL
 DISTANCE IS 100 FT. THIS IS ONLY TRUE WHEN THE TOTAL
 OCCUPANT LOAD FOR THE BUILDING IS 100 FEET, AN OCCUPANT
 LOAD OF 30 OR LESS THEN ONLY ONE EXIT IS REQUIRED.
 THE OCCUPANT LOAD GIVEN IS 36 AND THE COMMON PATH OF
 TRAVEL FROM THE OFFICE 104 ONE FOOT FROM THE WALL LINE
 TO THE FRONT DOOR IS 82 FEET REQUIRING 2 MEANS OF
 EGRESS FOR THIS BUILDING. SEE TABLE 1006.2.1 (FBC-B)
 SPACES WITH ONE EXIT ACCESS DOORWAY.
  
 5C) PEASE ALSO REVIEW SECTIONS: 2017 FBC-ACCESSIBILITY
 CODE SECTION 207.1 MEANS OF EGRESS SHALL COMPLY WITH
 SECTION 1003.2.13 OF THE INTERNATIONAL BUILDING CODE
 (2000 EDITION AND 2001 SUPPLEMENT) OR SECTION 1007 OF
 THE INTERNATIONAL BUILDING CODE (2003 EDITION).
  
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
 PLEASE SHOW HOW BOTH THE FRONT AND REAR EXITS (EXIT
 DISCHARGE) ARE GOING TO ALLOW THE OCCUPANTS TO TRAVEL
 TO THE PUBLIC WAY. 2017 FBC-B 1028.5. PLEASE NOTE THIS
 IS THE 1ST AREAS WHERE FUNDS ARE TO BE SPENT (I) COSTS
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA.
  
 5D) THE LS1 SHEET IN THE BOTTOM LEFT CORNER OF THE
 SHEET STATES THE GC IS TO PROVIDE PRICING FOR A 1 HOUR
 FIRE BARRIER AT THE IT/ ELECTRIC PANEL ROOM 112,
 CURRENTLY NOT SHOWN ON THE LS SHEET. PLEASE NOTE THERE
 CANNOT BE ALTERNATES, THE PLANS HAVE TO BE SPECIFIC.
  
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.3: W.P.B.
 ADMINISTRATIVE CODE. 2017 DRAWINGS & SPECIFICATIONS
 SHALL CONTAIN INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC TO THE
 TECHNICAL CODES. CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 5E) THE LIFE SAFETY SHEET INDICATES SEE SHEET E2 FOR
 EMERGENCY LIGHTING. SHEET E2 IS MISSING BOTH EMERGENCY
 LIGHTING IN THE OFFICE 114 AND A DIRECTIONAL SIGN, THE
 ADA RESTROOM 113 HAS AN EMERGENCY LIGHT BUT THE ADA
 BATHROOM 105 DOES NOT HAVE EMERGENCY LIGHTING, SHOW
 COMPLIANCE WITH THE 2017 FBC-B SECTION 1013.1. SHEET
 A2.0 SHOWS A FUTURE WALL SPLITTING OFFICE 114 INTO 2
 OFFICES ADDITIONAL DIRECTIONAL AND EMERGENCY LIGHTS
 WILL ALSO BE NEEDED AT THAT TIME.
  
 6) SHEET A1.0 DEMOLITION:
 6A) OLD OFFICE 107 NEW OFFICE 104 INDICATES NEW SAFE
 ROOM, PROVIDE PRICE TO CUT FOOTER AND NEW BLOCK WALL,
 IS THIS INCLUDED IN THE CONTRACT VALUE GIVEN? 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 6B) OLD OFFICE 107 NEW OFFICE 104 INDICATES NEW SAFE
 ROOM SHEET A2.0 INDICATES WALL TYPE A WITH ADDED LAYERS
 OF DRYWALL TO BE DETERMINED DURING CONSTRUCTION. NO
 ALTERNATES ALLOWED, PLANS ARE TO BE SPECIFIC TO THE
 TYPE OF CONSTRUCTION. ADMINISTRATION 107.2.1.3: W.P.B.
 ADMINISTRATIVE CODE. 2017 DRAWINGS & SPECIFICATIONS
 SHALL CONTAIN INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC TO THE
 TECHNICAL CODES.
  
 6C) SHEET A1.0 & SHEET A2.0. SHEET A2.0 THE FRONT ENTRY
 SHOWS AN ALTERNATE TO CLEAN EXISTING PAVERS OR PRICE
 FOR NEW PORCELAIN TILE. 2017 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1.3: W.P.B. ADMINISTRATIVE CODE. 2017 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES. CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 7) SHEET A2.0:
 7A) THE CONFERENCE ROOM (101) HAS 2 2 DOORWAYS WITH
 SLIDING DOORS 101 & 106. THIS ROOM IS CONSIDERED A
 SMALL ASSEMBLY SPACE AND MEETS THE REQUIREMENTS OF
 FBC-B 303.1.2. THE ROOM IS 243 SQ. FT. / 15 = 17
 OCCUPANTS. THE 2017 FBC-B DOES NOT ALLOW FOR HORIZONTAL
 SLIDING DOORS BE PART OF A MEANS OF EGRESS WHEN THERE
 IS AN OCCUPANT LOAD MORE THAN 10 OCCUPANTS. SEE 2017
 FBC-B SECTION 1010.1.2 EXC. 9.
  
 7B) PLEAS PROVIDE THE DIMENSIONS FOR THE NEW BENCH WITH
 STORAGE BENEATH AND COMPLIANCE WITH THE 2017
 FBC-ACCESSIBILITY CODE SECTION 903.5 HEIGHT. THE TOP OF
 THE BENCH SEAT SURFACE SHALL BE 17 INCHES (430 MM)
 MINIMUM AND 19 INCHES (485 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND
  
 7C)(1) SHEET IT ROOM ALTERNATE PRICING AGAIN STATED.
 107.2.1.3: W.P.B. ADMINISTRATIVE CODE. 2017 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES.
  
 7C)(2) THE PLAN STATES THE WALL TO BE 1 HOUR RATED.
 SHEET A8.0 DETAIL 2 DOES DESIGNATE AN 1 HOUR FIRE RATED
 ASSEMBLY, BUT DOES NOT PROVIDE THE REQUIRED COMPONENTS
 FOR THE RATED ASSEMBLY. THE FIELD INSPECTOR WILL NEED
 THESE FIRE RATED WALL ASSEMBLY COMPONENTS ON THE PLANS
 TO COMPLETE THE FIELD INSPECTION. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 7C)(3) IN THIS SAME DETAIL THE PLANS STATE THE
 REQUIREMENT FOR THE 2003 IBC, 2004 & 2007 FBC-B PLEASE
 UPDATE THE CODES AND CODE REFERENCES. THIS SAME DETAIL
 ALSO REFERENCES THE REQUIREMENT FOR FIRE RESISTANT
 JOINT SYSTEMS AROUND THE BAR JOIST AND ROOF DECK FLUTED
 DECK SYSTEM, PLEASE PROVIDE COMPLIANCE WITH 2017 FBC-B
 SECTION 715.1.
  
 7D) RECEPTION AREA DESK PASS THROUGH INDICATES FINAL
 HEIGHT TO BE DETERMINED IN INTERIOR DESIGN DRAWINGS.
 MUST COMPLY WITH THE 2017 FBC-ACCESS. CODE SECTIONS:
  
 904.3.3 CHECK WRITING SURFACES. WHERE PROVIDED, CHECK
 WRITING SURFACES SHALL COMPLY WITH 902.3.
  
 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS AND
 SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2.
 THE ACCESSIBLE PORTION OF THE COUNTER TOP SHALL EXTEND
 THE SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP.
  
 7E) OFFICE 104 SHOWS AN EGRESS WINDOW, WILL THIS OFFICE
 BE USED AS A SLEEPING ROOM REQUIRING AN EGRESS WINDOW?
 IF SO PLEASE PROVIDE THE STYLE OF WINDOW, SIZE OF
 WINDOW, THE WINDOW SCHEDULE ON SHEET A9.0 JUST STATES
 MATCH EXISTING. PROVIDE COMPLIANCE WITH ALL SECTIONS OF
 1030.2 & 1020.3 OF THE 2017 FBC-B.
  
 7F) OFFICES 102 & 103 ALTERNATE PRICING FOR GLAZING.
 107.2.1.3: W.P.B. ADMINISTRATIVE CODE. 2017 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES.
  
 7G) THE BREAK ROOM 108 REFERENCES THE INSTALLATION OF A
 MICROWAVE OVER THE OVEN PLEASE NOTE THERE IS NO
 ELEVATIONS FOR THE PLACEMENT OF THE MICROWAVE BUT WILL
 NEED TO SHOW COMPLIANCE WITH THE 2017 ACCESS. CODE
 SECTIONS:
 308 REACH RANGES
 308.2 FORWARD REACH. / 308.2.1 UNOBSTRUCTED/ 308.2.2
 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 309 OPERABLE PARTS
 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE
 OR MORE OF THE REACH RANGES SPECIFIED IN 308.
 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH
 ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 MAXIMUM.
  
 8) SHEET A4.0:
 8A) THE ADA BATHROOM # 105 SHOWS THE WATERCLOSET?S
 CLEAR FLOOR SPACE BEING INTERFERED WITH THE LAVATORY
 VANITY WITHIN THE REQUIRED 60 INCH CLEAR FLOOR SPACE
 REQUIRED FOR THE WATERCLOSET. SEE THE 2017 FBC-ACCESS.
 CODE 604.3.1 & 604.3.2.
  
 8B) DETAILS 2, 3 & 4 BOTH SHOW THE GRAB BARS AT A
 HEIGHT OF 3 FEET TO THE CENTER OF THE GRAB BAR. PLEASE
 NOTE A CODE CHANGE AS HOW YOU MEASURE THE HEIGHT, TO
 THE TOP OF THE GRASPING SURFACE, NOT CENTER LINED. SEE
  
 2017 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF
 GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 8C) THE PLUMBING SCHEDULE DOES INDICATE THE
 INSTALLATION OF ADA MIRRORS BUT NONE OF THE DETAILS
 SHOW THE ACTUAL HEIGHT THE MIRRORS ARE TO BE INSTALLED.
 PLEASE SHOW COMPLIANCE WITH THE 2017 ACCESS. CODE 603.3
 MIRRORS. MIRRORS LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 8D) PLEASE REVIEW DETAIL # 2 IN REGARDS TO THE TOP OF
 THE VANITY WHERE THE UNDER MOUNT LAVATORY IS INSTALLED,
 THE HEIGHT OF THE VANITY IS NOT GIVEN. SHOW COMPLIANCE
 WITH THE 2017 ACCESS. CODE SECTION 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 8E) THE DETAILS DO NOT PROVIDE THE LOCATION OF THE
 TOILET PAPER DISPENSER LOCATION. SHOW COMPLIANCE WITH
 2017 ACCESS. CODE 604.7 DISPENSERS. TOILET PAPER
 DISPENSERS SHALL COMPLY WITH 309.4 AND SHALL BE 7
 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS.
 DISPENSERS SHALL NOT BE OF A TYPE THAT CONTROLS
 DELIVERY OR THAT DOES NOT ALLOW CONTINUOUS PAPER FLOW.
  
 9) SHEET S1.0:
 9A) UNDER THE HEADING OF WIND LOADS (J) THE PLANS
 INDICATE THE BUILDING IS LOCATED WITHIN THE HIGH
 VELOCITY HURRICANE ZONE AND THE WINDS SHOWN ALSO
 REFLECT AS SUCH. IF THE DESIGNER OF RECORD WISHES TO
 DESIGN TO THE HIGHER WIND ZONE YOU MAY BUT PLEASE
 REMOVE THE WORDING HIGH VELOCITY HURRICANE ZONE, THAT
 IS FOR BROWARD AND MIAMI-DADE COUNTIES ONLY.
  
 9B) WALL PRESSURE CHART/ COMPONENTS AND CLADDING CHART.
 THE CHART DOES NOT PROVIDE IF THE GIVEN PRESSURES ARE
 IN VASD OR VULT. IT WOULD APPEAR THE PRESSURES ARE IN
 VASD PLEASE INDICATE AS SUCH. NOTE ALL PRODUCT
 APPROVALS ARE IN VASD WHICH HELPS IN CHECKING
 PRESSURES. 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 9C) NO ROOF PRESSURES ARE GIVEN, THE DEMOLITION SHEET
 AND A2.1 INDICATES THERE WILL BE ROOF REPAIRS NEEDED
 AND SO THE PRESSURES FOR ROOF ZONES 1, 2 & 3 WILL BE
 REQUIRE. 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 9D) COMPONENTS & CLADDING. 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, & MULLIONS.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: WALL LOUVERS
 (D) ROOFING PRODUCTS AND ASSEMBLIES,
  
 9E) IDENTIFY GLAZING/ MULLIONS.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 9F) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 9G) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 9H) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-08-21 Cont ID  
Sent By jpearson Date 2019-08-21 Time 15:25 Rev Time 0.00
Received By jpearson Date 2019-08-21 Time 15:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-03 Cont ID  
Sent By jleahy Date 2019-07-03 Time 10:27 Rev Time 0.00
Received By jleahy Date 2019-07-03 Time 10:20 Sent To  
Notes
2019-07-03 10:32:23FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 1) PLEASE SHOW DETAIL OF OUTLET AND LIGHTING CONTROL
 PER FBC ENERGY CODE
  
 2) ALL 120 VOLT 15 AND 20 AMPERE OUTLETS IN THE KITCHEN
 TO BE GFCI PROTECTED
  
 210.8(B) OTHER THAN DWELLING UNITS. ALL 125-VOLT,
 SINGLE-PHASE,
 15- AND 20-AMPERE RECEPTACLES INSTA LLED IN THE
 LOCATIONS SPECIFIED
 IN 210.8(B)(1) THROUGH (8) SHALL HAVE GROUND-FAULT
 CIRCUITINTERRUPTER
 PROTECTION FOR PERSONNEL. (2) KITCHENS

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2019-09-20 Cont ID  
Sent By pleduc Date 2019-09-20 Time   Rev Time 0.00
Received By pleduc Date 2019-09-20 Time 11:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-08-08 Cont ID  
Sent By pleduc Date 2019-08-08 Time   Rev Time 0.00
Received By pleduc Date 2019-08-08 Time 15:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2019-06-20 Cont ID  
Sent By pleduc Date 2019-06-20 Time   Rev Time 0.00
Received By pleduc Date 2019-06-20 Time 14:55 Sent To  
Notes
2019-06-20 15:00:526/20/19
  
 THERE ARE NO INDICATIONS, NARRATIVE, NUMBERED
 RESPONSES, OR CLOUDED AREAS OF REVISION THAT ADDRESSED
 THE PREVIOUS FIRE COMMENTS.
  
 THE PREVIOUS FIRE COMMENTS ARE RESTATED BELOW.
  
 PLEASE ADDRESS THEM BY NARRATIVE, NUMBERED RESPONSE OR
 CLOUDED AREAS OF REVISION.
  
 *******************************************************
 *******************************************************
 ***********************************************
  
 1) SHEET A 2.0 - THERE IS AN INDICATION OF A GAS RANGE
 AND OVEN. WHERE FOOD IS PROCESSED THE INSTALLATION
 SHALL BE PROTECTION PER NFPA 101 AND OTHER APPLICABLE
 CODES.
  
 PER NFPA 101 CH 38 AND/OR 39 NEW & EXISTING BUSINESS
 OCCUOANCIES
  
 38.3.2.3* COMMERCIAL COOKING OPERATIONS. COMMERCIAL
 COOKING
 OPERATIONS SHALL BE PROTECTED IN ACCORDANCE WITH 9.2.3,
 UNLESS THE
 COOKING EQUIPMENT IS ONE OF THE FOLLOWING TYPES:
 (1) OUTDOOR EQUIPMENT
 (2) EQUIPMENT USED ONLY FOR FOOD WARMING
  
 39.3.2.3* COMMERCIAL COOKING OPERATIONS. COMMERCIAL
 COOKING OPERATIONS SHALL BE PROTECTED IN ACCORDANCE
 WITH 9.2.3,
 UNLESS THE COOKING EQUIPMENT IS ONE OF THE FOLLOWING
 TYPES:
 (1) OUTDOOR EQUIPMENT
 (2) EQUIPMENT USED ONLY FOR FOOD WARMING
  
  
 9.2.3 COMMERCIAL COOKING OPERATIONS. WHERE REQUIRED BY
 ANOTHER
 SECTION OF THIS CODE, COMMERCIAL COOKING OPERATIONS
 SHALL BE PROTECTED
 IN ACCORDANCE WITH NFPA 96, STANDARD FOR VENTILATION
 CONTROL AND
 FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS,
 UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE
 PERMITTED TO BE CONTINUED IN SERVICE.
  
 ANY PROPOSED INSTALLTION THAT INCLUDES A RANGE/STOVE
 TOP IN A COMMERCIAL/BUSINESS SETTING HAS THE POTENTIAL
 TO PRODUCE GREASE LADEN VAPORS AND SHALL BE PROTECTED
 FOR SUCH IN ACCORDNCE WITH NFPA 96 AND WITH A FIRE
 SUPPRESSION SYSTEM.
  
 EQUIPMENT DESIGN FOR WARMING; MICROWAVE, CONVECTION
 OVEN, TOASTER OVEN, ETC, WOULD NOT REQUIRE SUCH A
 SYSTEM.
  
 A HOOD AND FIRE SUPPRESSION SYSTEM SHALL BE INSTALLED
 UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT OR REMOVE THE GAS RANGE TOP.
  
  
  
 2) SHEET A 2.0 - THERE ARE HORIZONTAL SLIDING DOORS
 INDICATED IN THE MEAND OF EGRESS FROM THE CONFERNECE
 ROOM.
  
 PER NFPA 101
  
 38.2.2.2.7 HORIZONTAL OR VERTICAL SECURITY GRILLES OR
 DOORS
 COMPLYING WITH 7.2.1.4.1(3) SHALL BE PERMITTED TO BE
 USED AS PART
 OF THE REQUIRED MEANS OF EGRESS FROM A TENANT SPACE
  
 7.2.1.4 SWING AND FORCE TO OPEN.
 7.2.1.4.1* SWINGING-TYPE DOOR ASSEMBLY REQUIREMENT. ANY
 DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL BE OF THE
 SIDE-HINGED OR
 PIVOTED-SWINGING TYPE, AND SHALL BE INSTALLED TO BE
 CAPABLE OF
 SWINGING FROM ANY POSITION TO THE FULL REQUIRED WIDTH
 OF THE
 OPENING IN WHICH IT IS INSTALLED, UNLESS OTHERWISE
 SPECIFIED AS
 FOLLOWS:
 (3) WHERE PERMITTED IN CHAPTERS 11 THROUGH 43,
 HORIZONTALSLIDING
 OR VERTICAL-ROLLING SECURITY GRILLES OR DOOR ASSEMBLIES
 THAT ARE PART OF THE REQUIRED MEANS OF EGRESS SHALL BE
 PERMITTED, PROVIDED THAT ALL OF THE FOLLOWING CRITERIA
 ARE MET:
 (A) SUCH GRILLES OR DOOR ASSEMBLIES SHALL REMAIN
 SECURED IN
 THE FULLY OPEN POSITION DURING THE PERIOD OF OCCUPANCY
 BY THE GENERAL PUBLIC.
 (B) ON OR ADJACENT TO THE GRILLE OR DOOR OPENING, THERE
 SHALL
 BE A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN
 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT
 READS AS FOLLOWS: THIS DOOR TO REMAIN OPEN
 WHEN THE SPACE IS OCCUPIED.
 (C) DOOR LEAVES OR GRILLES SHALL NOT BE BROUGHT TO THE
 CLOSED
 POSITION WHEN THE SPACE IS OCCUPIED.
 (D) DOOR LEAVES OR GRILLES SHALL BE OPERABLE FROM
 WITHIN THE
 SPACE WITHOUT THE USE OF ANY SPECIAL KNOWLEDGE OR
 EFFORT.
 (E) WHERE TWO OR MORE MEANS OF EGRESS ARE REQUIRED, NOT
 MORE THAN HALF OF THE MEANS OF EGRESS SHALL BE EQUIPPED
 WITH HORIZONTAL-SLIDING OR VERTICAL-ROLLING GRILLES OR
 DOOR
 ASSEMBLIES.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT OR CORRECT.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-06-13 Cont ID  
Sent By pleduc Date 2019-06-13 Time   Rev Time 0.00
Received By pleduc Date 2019-06-13 Time 11:34 Sent To  
Notes
2019-06-13 11:56:31THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A 2.0 - THERE IS AN INDICATION OF A GAS RANGE
 AND OVEN. WHERE FOOD IS PROCESSED THE INSTALLATION
 SHALL BE PROTECTION PER NFPA 101 AND OTHER APPLICABLE
 CODES.
  
 PER NFPA 101 CH 38 AND/OR 39 NEW & EXISTING BUSINESS
 OCCUOANCIES
  
 38.3.2.3* COMMERCIAL COOKING OPERATIONS. COMMERCIAL
 COOKING
 OPERATIONS SHALL BE PROTECTED IN ACCORDANCE WITH 9.2.3,
 UNLESS THE
 COOKING EQUIPMENT IS ONE OF THE FOLLOWING TYPES:
 (1) OUTDOOR EQUIPMENT
 (2) EQUIPMENT USED ONLY FOR FOOD WARMING
  
 39.3.2.3* COMMERCIAL COOKING OPERATIONS. COMMERCIAL
 COOKING OPERATIONS SHALL BE PROTECTED IN ACCORDANCE
 WITH 9.2.3,
 UNLESS THE COOKING EQUIPMENT IS ONE OF THE FOLLOWING
 TYPES:
 (1) OUTDOOR EQUIPMENT
 (2) EQUIPMENT USED ONLY FOR FOOD WARMING
  
  
 9.2.3 COMMERCIAL COOKING OPERATIONS. WHERE REQUIRED BY
 ANOTHER
 SECTION OF THIS CODE, COMMERCIAL COOKING OPERATIONS
 SHALL BE PROTECTED
 IN ACCORDANCE WITH NFPA 96, STANDARD FOR VENTILATION
 CONTROL AND
 FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS,
 UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE
 PERMITTED TO BE CONTINUED IN SERVICE.
  
 ANY PROPOSED INSTALLTION THAT INCLUDES A RANGE/STOVE
 TOP IN A COMMERCIAL/BUSINESS SETTING HAS THE POTENTIAL
 TO PRODUCE GREASE LADEN VAPORS AND SHALL BE PROTECTED
 FOR SUCH IN ACCORDNCE WITH NFPA 96 AND WITH A FIRE
 SUPPRESSION SYSTEM.
  
 EQUIPMENT DESIGN FOR WARMING; MICROWAVE, CONVECTION
 OVEN, TOASTER OVEN, ETC, WOULD NOT REQUIRE SUCH A
 SYSTEM.
  
 A HOOD AND FIRE SUPPRESSION SYSTEM SHALL BE INSTALLED
 UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT OR REMOVE THE GAS RANGE TOP.
  
  
  
 2) SHEET A 2.0 - THERE ARE HORIZONTAL SLIDING DOORS
 INDICATED IN THE MEAND OF EGRESS FROM THE CONFERNECE
 ROOM.
  
 PER NFPA 101
  
 38.2.2.2.7 HORIZONTAL OR VERTICAL SECURITY GRILLES OR
 DOORS
 COMPLYING WITH 7.2.1.4.1(3) SHALL BE PERMITTED TO BE
 USED AS PART
 OF THE REQUIRED MEANS OF EGRESS FROM A TENANT SPACE
  
 7.2.1.4 SWING AND FORCE TO OPEN.
 7.2.1.4.1* SWINGING-TYPE DOOR ASSEMBLY REQUIREMENT. ANY
 DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL BE OF THE
 SIDE-HINGED OR
 PIVOTED-SWINGING TYPE, AND SHALL BE INSTALLED TO BE
 CAPABLE OF
 SWINGING FROM ANY POSITION TO THE FULL REQUIRED WIDTH
 OF THE
 OPENING IN WHICH IT IS INSTALLED, UNLESS OTHERWISE
 SPECIFIED AS
 FOLLOWS:
 (3) WHERE PERMITTED IN CHAPTERS 11 THROUGH 43,
 HORIZONTALSLIDING
 OR VERTICAL-ROLLING SECURITY GRILLES OR DOOR ASSEMBLIES
 THAT ARE PART OF THE REQUIRED MEANS OF EGRESS SHALL BE
 PERMITTED, PROVIDED THAT ALL OF THE FOLLOWING CRITERIA
 ARE MET:
 (A) SUCH GRILLES OR DOOR ASSEMBLIES SHALL REMAIN
 SECURED IN
 THE FULLY OPEN POSITION DURING THE PERIOD OF OCCUPANCY
 BY THE GENERAL PUBLIC.
 (B) ON OR ADJACENT TO THE GRILLE OR DOOR OPENING, THERE
 SHALL
 BE A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN
 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT
 READS AS FOLLOWS: THIS DOOR TO REMAIN OPEN
 WHEN THE SPACE IS OCCUPIED.
 (C) DOOR LEAVES OR GRILLES SHALL NOT BE BROUGHT TO THE
 CLOSED
 POSITION WHEN THE SPACE IS OCCUPIED.
 (D) DOOR LEAVES OR GRILLES SHALL BE OPERABLE FROM
 WITHIN THE
 SPACE WITHOUT THE USE OF ANY SPECIAL KNOWLEDGE OR
 EFFORT.
 (E) WHERE TWO OR MORE MEANS OF EGRESS ARE REQUIRED, NOT
 MORE THAN HALF OF THE MEANS OF EGRESS SHALL BE EQUIPPED
 WITH HORIZONTAL-SLIDING OR VERTICAL-ROLLING GRILLES OR
 DOOR
 ASSEMBLIES.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT OR CORRECT.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2019-08-22 Cont ID  
Sent By jesmith Date 2019-08-22 Time 15:53 Rev Time 0.00
Received By jesmith Date 2019-08-22 Time 15:53 Sent To  
Notes
2019-08-22 15:54:32THERE IS NO GAS IN THE SCOPE OF WORK.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-06-20 Cont ID  
Sent By thunt Date 2019-06-20 Time 09:44 Rev Time 0.00
Received By thunt Date 2019-06-20 Time 09:44 Sent To  
Notes
2019-06-20 09:45:56GAS 1ST REVIEW**DENIED**
  
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT IS REQUIRED FOR A
 CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE
 COMPLETE PLANS THAT REFLECT THE ENTIRE SCOPE OF GAS
 WORK TO BE DONE. WPB AMEND. TO FBC SEC.107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-09-30 Time   Rev Time 0.00
Received By lmarchan Date 2019-09-18 Time 14:36 Sent To  
Notes
2019-09-19 14:36:50B24

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-10 Cont ID  
Sent By hmoser Date 2019-09-10 Time 10:05 Rev Time 0.00
Received By hmoser Date 2019-08-06 Time 14:37 Sent To  
Notes
2019-08-07 14:37:45B29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-10 Cont ID  
Sent By cpuell Date 2019-07-10 Time 15:26 Rev Time 0.00
Received By cpuell Date 2019-06-10 Time 14:20 Sent To  
Notes
2019-06-11 14:21:01B08

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-06-18 Cont ID  
Sent By jwitmer Date 2019-06-18 Time 11:38 Rev Time 0.00
Received By jwitmer Date 2019-06-17 Time 13:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-09-10 Cont ID  
Sent By hmoser Date 2019-09-10 Time 10:05 Rev Time 0.00
Received By hmoser Date 2019-09-10 Time 09:28 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-06-28 Cont ID  
Sent By ccole Date 2019-06-28 Time 15:21 Rev Time 0.00
Received By ccole Date 2019-06-28 Time 14:27 Sent To  
Notes
2019-06-28 15:33:461ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19051536
 6/28/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 809.2 FBC EX AND PROVIDE MINIMUM
 VENTILATION CALCULATIONS FOR ALL ROOMS AND SPACES PER
 TABLE 403.3.1.1 FBC-17 MECHANICAL. PROVIDE A SCHEDULE
 THAT INDICATES THE REQUIRED AND PROVIDED CFMS OF
 OUTDOOR AIR.
  
 2) REFER TO SECTION 508.1.2 FBC EC AND PROVIDE AIR
 BALANCE CALCULATIONS.
  
 3) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR THE
 KITCHEN HOOD EXHAUST SYSTEM, AND FIRE SUPPRESSION
 SYSTEM. PLEASE NOTE THAT THE TEMPERATURE DIFFERENITAL
 BETWEEN MAKEUP AIR FOR THE HOOD AND AIR IN THE
 CONDITIONED SPACE SHALL NOT EXCEED 10 DEGREES F. THIS
 REQUIREMENT MAY AFFECT THE DESIGN OF THE MAIN HVAC
 SYSTEMS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-09-27 Cont ID  
Sent By tklarge Date 2019-09-27 Time 08:23 Rev Time 0.00
Received By tklarge Date 2019-09-26 Time 04:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-08-22 Cont ID  
Sent By jesmith Date 2019-08-22 Time 16:32 Rev Time 0.00
Received By jesmith Date 2019-08-22 Time 15:55 Sent To  
Notes
2019-08-22 16:01:55CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 PLUMBING COMMEMTS: DENIED
 1. SECOND REQUEST: SHOW OR PROVIDE NOTE THAT BOTH
 TOILET ROOM SINKS ARE TEMPERED 110F MAX BY AN ASSE 1070
 DEVICE. FBC P 607.1.2; NOTE THAT AFTER REVIEWING
 RESPONSE COMMENTS AND THE REVISED PLANS, I COULD NOT
 FIND EVIDENCE OF COMPLIANCE. PLEASE PROVIDE NOTE AND
 CLOUD AS A REVISION.
 2. FBC ACC 606.3 LAVATORIES AND SINKS SHALL BE
 INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. DIMENSION ON COUNTER DETAIL
 SHALL BE TO THE FIXTURE RIM WHICH IS THE HIGHER OF THE
 TWO ITEMS.
 3. FOR A CLARIFICATION AND TO ALLOW FOR THE USE OF AN
 AIR ADMITTANCE VALVE FOR THE KITCHEN SINK AS OPPOSED TO
 PROVIDING A VENT THROUGH THE ROOF, PER WPB FBC 107.2.1,
 INDICATE ON THE PLAN VIEW THAT THE UPSTREAM SIDE OF THE
 BRANCH CONNECTION TO THE EXTERIOR DRAIN AS WELL AS 5
 FEET PLUS OR MINUS DOWNSTREAM OF THE BRANCH CONNECTION
 IS THE "SANITARY BUILDING DRAIN". PROVIDE AND SHOW A
 FULL SIZE TWO-WAY CLEANOUT TO GRADE AND DESIGNATE
 SANITARY BUILDING SEWER DOWNSTREAM OF THE CLEANOUT.
 ADDITIONALLY, INDICATE ON NOTE 1 ON P-1 "EXISTING
 BUILDING DRAIN" AS OPPOSED TO "EXISTING". ON THE
 SANITARY RISER DIAGRAMS ON P-2, TIE IN NOTES SHOULD SAY
 "EXISTING BUILDING DRAIN" AS OPPOSED TO "EXISTING".
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19051536 201 ARKONA CT
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-06-20 Cont ID  
Sent By thunt Date 2019-06-20 Time 12:10 Rev Time 0.00
Received By thunt Date 2019-06-20 Time 12:10 Sent To  
Notes
2019-06-20 12:14:22PLUMBING 1ST REVIEW**DENIED** I WOULD ADVISE THE DESIGN
 TEAM COMING IN FOR A MEETING DUE TO THE LARGE AMOUNT OF
 COMMENTS SO ALL CAN BE ADDRESSED ON THE 2ND REVIEW.
  
 1) PROVIDE OCCUPANT LOAD ON SHT.SP1. FBC 107.3.5
  
 2) SHT.X1 NOTES ADVISES BOTTLE WATER WILL BE PROVIDE
 LIEU OF LOW OF A HI-LOW DRINKING FOUNTAIN. FBC P403.1
 REQUIRES UNDER YOUR BUSINESS CLASSIFICATION A DRINKING
 FOUNTAIN SHALL BE SUPPLIED UNDER FBC P410.3. WITH YOUR
 OCCUPANT LOAD.
  
 3) PROVIDE CLEAR FLOOR SPACE AS REQUIRED BY FBC-ACC 606
 AND 608.
 (A) THE BAR SINK IN THE CONFERENCE ROOM
 (B) THE BREAK ROOM SINK
 (C) BATHROOM SHOWER
  
 4) A GREASE INTERCEPTOR IS REQUIRED ANY TIME COOKING OR
 THE HEATING OF FOOD (GAS STOVE) IS PROVIDED WHICH WOULD
 CAUSE THE DISCHARGE OF GREASER TO ENTER THE SEWAGE
 SYSTEM. PROVIDE LOCATION, TYPE, SIZE AND HOW YOU CAME
 TO SIZE OF THE INTERCEPTOR. FBC P1003.1, 1003.2,
 1003.3.4
  
 5) BREAKROOM SINK IS NOT PERMITTED TO BE USED AS THE
 SERVICE SINK. PROVIDE LOCATION AND ADD TO WATER AND
 SANITARY ISOMETRIC DRAWING. FBC 403.1, 107.3.5
  
 6) PROVIDE SHOWER DIMENSION ON SHT A4 SHOWER THE
 FINISHED SHOWER WILL BE 36" X 36". FBC-ACC 104.1
  
 7) TOILET ROOMS SHALL BE LISTED AS MEN?S AND WOMEN?S.
 PLEASE SUPPLY A SHOWER TO THE OTHER TOILET ROOM AS TO
 PROVIDE A SHOWER TO THE OPPOSITE SEX TO MEET EQUIVALENT
 FACILITATION. FBC-ACC 103
  
 8) TOILET ROOM 105 SHOWS THE LAVATORY ENCROACHING INTO
 THE CLEAR FLOOR SPACE OF THE TOILET. OTHER FIXTURES ARE
 NOT PERMITTED TO BE IN THE CLEAR FLOOR.FBC-ACC 604.3.2
  
 9) PLAN CALLS OUT FOR A GAS RANGE. A SEPARATE GAS PLAN
 AND PERMIT IS REQUIRED. SEE GAS REVIEW COMMENTS. FBC
 105.1
  
 10) SHT. A4.0 SHOW ALL GRAD BAR MOUNTING TO BE 36? TO
 THE CENTER. GRAB BARS SHALL BE MOUNTED 33-36? TO THE
 TOP OF THE GRIPPING SURFACE. FBC-ACC 609.4
  
 11) SHT A4.0 DETAIL # 2 AND SHT. A6.0 SHOWS ADA SINKS
 TO HAVE A KNEE CLEARANCE OF 2? 6? (30) AND A CABINET
 WITH DOORS. THE MIN KNEE CLEARANCE PERMITTED IS 27? PER
 FBC-ACC AND HAVE A FRONT APPROACH WHICH DOES NOT ALLOW
 FOR A CABINET WITH DOORS. FBC-ACC 606.2, FBC-ACC 306.3
  
 12) PROVIDE MIRROR DETAIL SHOWING MOUNTING MAX 40? TO
 THE REFLECTIVE SURFACE. FBC-ACC 603.3 AND THE TOILET
 PAPER DISPENSER 7?-9? FROM THE FRONT OF THE BOWL.
 FBC-ACC 604.7
  
 13) PROVIDE INSTALLATION MANUAL FOR THE SHOWER PAN
 MATERIAL CALLED OUT ON SHT. A8.0 (NOBELSEAL) FBC
 107.2.1
  
 14) PROVIDE KITCHEN CABINET AND COUNTER TOP DETAIL. MAX
 HEIGHT PERMITTED IS 34? AND SHOW THAT YOU MEET ALL
 REACH RANGES. FBC-ACC 606.3, FBC-ACC 308
  
 15) SHOW OR PROVIDE NOTE THAT BOTH TOILET ROOM SINKS
 ARE TEMPERED 110F MAX BY AN ASSE 1070 DEVICE. FBC P
 607.1.2
  
 16) SHT. P1.0 CALLS OUT OF FOR TANKLESS TO BE 3.5 KW.
 PROVIDE HEAT RISE CHART SHOWING HEATER IS CAPABLE OF
 PRODUCING 2.2 GPM OF HOT WATER MIN 110F. FBC P 607.1
  
 17) SHT. P-2 SHOWS KITCHEN AS BEING VENTED BY AAV. SHT
 P1 CALLS FOR THIS TO BE A NEW BUILDING DRAIN. THIS LINE
 MUST ALSO CONNECT INTO A GREASE INTERCEPTOR WHICH BOTH
 REQUIRED A VENT EXTEND TO THE OUTDOORS. FBC P904.1, AND
 THE INSTALLATION MANUAL OF THE INTERCEPTOR. FBC P
 1003.3.4
  
 18) SHT P2 BATHROOM GROUP 105 SHOWS THE BAR SINK
 DISCHARGING INTO THE BATHROOM GROUP WET VENT. ONLY
 THOSE FIXTURES LOCATED IN THE BATROOM OR 1 OTHER
 BATHROOM GROUP ARE PERMITTED TO DISCHARGE INTO THE
 BATHROOM GROUP WET VENT. ALL OTHERS SHALL DISCHARGE
 DOWN STREAM OF THE BATHROOM GROUP. FBC P 912.1
  
 19) PROVIDE SHOWER VALVES INSTALLATION MANUAL OR NOTE
 ON PLAN SHALL BE PRESSURE BALANCED/ THERMO ASSE 1016
 APPROVED WITH INTEGRAL SHUT OFF VALVES. FBC P 434.3.
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  

Review Stop Z ZONING
Rev No 4 Status P Date 2019-09-27 Cont ID  
Sent By llouie Date 2019-09-27 Time   Rev Time 0.00
Received By llouie Date 2019-09-27 Time   Sent To  
Notes
2019-09-27 09:16:12ZONING APPROVED WITH THE FOLLOWING NOTES:
  
 1.) INTERIOR MODIFICATIONS ONLY.
  
 2.) SEPARATE PERMIT AND REVIEW REQUIRED FOR PARKING LOT
 IMPROVEMENTS.

Review Stop Z ZONING
Rev No 3 Status P Date 2019-08-14 Cont ID  
Sent By llouie Date 2019-08-14 Time   Rev Time 0.00
Received By llouie Date 2019-08-14 Time   Sent To  
Notes
2019-08-14 12:19:43SEPARATE PERMIT REQUIRED FOR PARKING LOT STRIPING.

Review Stop Z ZONING
Rev No 2 Status F Date 2019-07-10 Cont ID  
Sent By llouie Date 2019-07-10 Time 11:17 Rev Time 0.00
Received By llouie Date 2019-07-10 Time 11:17 Sent To  
Notes
2019-07-10 11:09:23** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE VALUE OF THE CONSTRUCTION ($336,000) EXCEEDS
 50% OF THE STRUCTURE'S VALUE ($129,462) ACCORDING TO
 THE P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE,
 PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY. [6/14/19 REPEAT
 COMMENT]
  
  
 NOTES:
  
 * INTERIOR MODIFICATIONS ONLY.
  
 * SEPARATE PERMITS REQUIRED FOR: LANDSCAPE, PARKING
 AREA STRIPING.
  
 * REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * EXISTING PROFESSIONAL OFFICE BUILDING IN A
 RESIDENTIAL ZONE
  
 * ZONE: MF32
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-06-14 Cont ID  
Sent By llouie Date 2019-06-14 Time   Rev Time  
Received By llouie Date 2019-06-14 Time   Sent To  
Notes
2019-06-14 16:24:16** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) BUILDING ELEVATIONS (EXISTING AND PROPOSED)
 REQUIRED. ALSO, SHOW DIRECTIONS (I.E. NORTH, SOUTH,
 EAST AND WEST).
  
 2.) THE VALUE OF THE CONSTRUCTION ($336,000) EXCEEDS
 50% OF THE STRUCTURE'S VALUE ($129,462) ACCORDING TO
 THE P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE,
 PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY.
  
  
 NOTES:
  
 * INTERIOR MODIFICATIONS ONLY.
  
 * SEPARATE PERMITS REQUIRED FOR: LANDSCAPE, PARKING
 AREA STRIPING.
  
 * REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * EXISTING PROFESSIONAL OFFICE BUILDING IN A
 RESIDENTIAL ZONE
  
 * ZONE: MF32
  


Account Summary | Usage Policy | Privacy Policy