Plan Review Details - Permit 19051525
Plan Review Stops For Permit 19051525
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2020-04-14 Cont ID  
Sent By cpuell Date 2020-04-14 Time 15:40 Rev Time 0.00
Received By cpuell Date 2020-04-14 Time 15:40 Sent To  
Notes
2020-04-14 15:41:05ADDRESS TO REMAIN THE SAME SINCE NO DEMO.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-02-10 Cont ID  
Sent By cpuell Date 2020-02-10 Time 14:55 Rev Time 0.00
Received By cpuell Date 2020-02-10 Time 14:55 Sent To  
Notes
2020-02-10 14:56:53PLEASE CONTACT [email protected] TO DISCUSS THE ADDRESS
 FOR THIS PROPERTY. I WILL ALSO BE REACHING OUT TO
 APPLICANT TO DISCUSS. CP

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2020-01-06 Cont ID  
Sent By jwitmer Date 2020-01-06 Time 13:03 Rev Time 0.00
Received By jwitmer Date 2020-01-06 Time 13:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2022-06-28 Cont ID  
Sent By jwitmer Date 2022-06-28 Time 10:47 Rev Time 0.00
Received By jwitmer Date 2022-06-28 Time 10:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2022-04-12 Cont ID  
Sent By jwitmer Date 2022-04-12 Time 08:44 Rev Time 0.00
Received By jwitmer Date 2022-04-12 Time 08:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2021-12-15 Cont ID  
Sent By jwitmer Date 2021-12-15 Time 07:35 Rev Time 0.00
Received By jwitmer Date 2021-12-15 Time 07:13 Sent To  
Notes
2021-12-15 07:25:292017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19051525
 ADD: 719 N. SAPODILLA AVE.
 CONT: TBD/ TO BE DETERMINED
 TEL: NONE
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 4TH REVIEW
  
 DATE: WED. DEC.15TH/ 2020
 ACTION: BUILDING PROVISOS:
  
 1) PROVISO: THIS PROJECT HAS BOLTED STEEL CONNECTIONS
 AS WELL AS WELDED STEEL CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION. IN ACCORDANCE WITH THE AMERICAN WELDING
 SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS IN REGARDS TO THESE
 REQUIREMENTS PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
 2) PROVISO/ DEFERRED SUBMITTALS. 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, EFIS
 SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 3A) PROVISO/ DEFERRED SUBMITTALS. W. P. B. 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 3B) PROVISO/ DEFERRED SUBMITTALS. DELEGATED
 ENGINEERING. 61G15-30.003 ENGINEERING DOCUMENT
 CLASSIFICATION. FL 61G-15-30.006 (3) THE DELEGATED
 ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING
 DOCUMENTS TO THE ENGINEER OF RECORD FOR REVIEW.
  
 3C)PROVISO: 107.3.4.2 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
  
 3D) PROVISO/ DEFERRED SUBMITTALS. PLEASE IDENTIFY ON
 THE PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 3E) PROVISO/ DEFERRED SUBMITTALS. ROOFING PRODUCT
 APPROVALS: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL
 ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR
 ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS,
 IF ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 3F) PROVISO/ DEFERRED SUBMITTALS. 107.2.1.2 FOR ROOF
 ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION
 DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE
 TYPE OF ROOFING SYSTEM, MATERIALS, VENTING, FASTENING
 REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE
 RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT
 EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE
 WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-07-02 Cont ID  
Sent By jwitmer Date 2020-07-02 Time 09:43 Rev Time 0.00
Received By jwitmer Date 2020-07-02 Time 09:01 Sent To  
Notes
2020-07-02 09:43:412017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19051525
 ADD: 719 N. SAPODILLA AVE.
 CONT: TBD/ TO BE DETERMINED
 TEL: NONE
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 4TH REVIEW
  
 DATE: THUR. JULY 02ND/ 2020
 ACTION: BUILDING PROVISOS:
  
 1) PROVISO: THIS PROJECT HAS BOLTED STEEL CONNECTIONS
 AS WELL AS WELDED STEEL CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION. IN ACCORDANCE WITH THE AMERICAN WELDING
 SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS IN REGARDS TO THESE
 REQUIREMENTS PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
 2) PROVISO/ DEFERRED SUBMITTALS. 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, EFIS
 SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 3A) PROVISO/ DEFERRED SUBMITTALS. W. P. B. 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 3B) PROVISO/ DEFERRED SUBMITTALS. DELEGATED
 ENGINEERING. 61G15-30.003 ENGINEERING DOCUMENT
 CLASSIFICATION. FL 61G-15-30.006 (3) THE DELEGATED
 ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING
 DOCUMENTS TO THE ENGINEER OF RECORD FOR REVIEW.
  
 3C)PROVISO: 107.3.4.2 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
  
 3D) PROVISO/ DEFERRED SUBMITTALS. PLEASE IDENTIFY ON
 THE PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 3E) PROVISO/ DEFERRED SUBMITTALS. ROOFING PRODUCT
 APPROVALS: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL
 ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR
 ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS,
 IF ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 3F) PROVISO/ DEFERRED SUBMITTALS. 107.2.1.2 FOR ROOF
 ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION
 DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE
 TYPE OF ROOFING SYSTEM, MATERIALS, VENTING, FASTENING
 REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE
 RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT
 EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE
 WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-03-02 Cont ID  
Sent By pvalenti Date 2020-03-02 Time 17:41 Rev Time 0.00
Received By pvalenti Date 2020-03-02 Time 13:44 Sent To  
Notes
2020-03-02 18:05:40***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 THIRD BUILDING REVIEW DENIED:
  
 APPROVAL IS PENDING THE CORRECTION OF THE FOLLOWING
 ITEMS FROM THE LAST REVIEW:
  
 1A)(2) PROVIDE ALL SET BACKS FROM PROPERTY LINE
 INCLUDING EDGE OF PROPOSED WORK ON SURVEY.
  
 1B) PROVIDE THE UNITY OF TITLE. THE UNITY OF TITLE IS
 REQUIRED PRIOR TO ISSUANCE OF PERMIT.
  
 2A) ON PAGE 307 LS PLEASE CORRECT THE BASED ON SEATS
 LAYOUT TOTAL OCCUPANT LOAD FROM 150 TO 138.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-01-06 Cont ID  
Sent By jwitmer Date 2020-01-06 Time 13:28 Rev Time 0.00
Received By jwitmer Date 2020-01-06 Time 08:22 Sent To  
Notes
2020-01-06 13:28:012017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19051525
 ADD: 719 N. SAPODILLA AVE.
 CONT: TBD/ TO BE DETERMINED
 TEL: NONE
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY JAN.6TH/2020
 ACTION: DENIED
  
 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B)
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 1) SHEET G DRAWING INDEX & PROJECT INFO:
  
 1A)(1) PLEASE CORRECT THE SHEET G THE DRAWING INDEX
 WITH SURVEY SHEET LISTED 005G AS SHOWN IN THE INDEX OR
 REMOVE THE SHEET NUMBER WITH A REVISION.
 1ST ROUND OF COMMENTS. PLEASE NOTE THE DRAWING INDEX
 THERE SHOULD BE A SURVEY SHEET 005G BETWEEN SHEET 004 G
 STANDARD ABBREVIATIONS & SYMBOLS SHEET AND CIVIL COVER
 SHEET 100C. MISSING DOCUMENT. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 1A)(2) NEW COMMENT. A SURVEY IS REQUIRED TO DETERMINE
 THE EXISTING BUILDING AND LOCATION OF LOT LINES, ALL
 LOT LINES, NOT JUST THE ADJOINING LOT 713. THERE ARE
 MANY REQUIREMENTS THAT WILL NEED TO SEE HOW FAR THE
 BUILDING IS FROM THE PROPERTY LINE. EXTERIOR FIRE
 RATING OF WALLS, REAR EGRESS FROM THE BUILDING AND
 CANOPY, EGRESS COURT REQUIREMENTS, THESE AND OTHER
 REQUIREMENTS CANNOT BE DETERMINED UNTIL A SURVEY IS
 SUBMITTED SHOWING THE DISTANCE FROM THE BUILDING TO THE
 PROPERTY LINE IN ALL DIRECTIONS. PLEASE NOTE THE SURVEY
 SUBMITTED SHEET 103 ENGINEERING PLAN IS FOR
 TOPOGRAPHICAL USE AND SANITARY USE ONLY. NOTE THIS
 SURVEY ALSO INDICATES THE PROPERTY AS ONE LARGE LOT NOT
 2 ADJOINING LOTS WHICH IS INCORRECT. THE SURVEY BY ENG
 ENUITY GROUP INC. HAS AN ELECTRONIC SIGNATURE AND SEAL
 12/11/2019 BY ADAM SWANEY. APPARENTLY THE SHEET WAS
 PRINTED ON A PAPER COPY WAS UPLOADED, THERE IS NO
 ELECTRONIC SIGNATURE NOR SEAL ON THIS SHEET
 OR THERE WAS NEVER A ELECTRONIC SIGNATURE & SEAL.
  
 1B) THIS REVIEW WILL NEED TO BE FAILED SINCE THERE IS
 NO UNITY OF TITLE FILED WITH THE CLERK OF THE COURTS
 OFFICE. THE REQUEST TO HAVE THE UNITY OF TITLE AFTER
 THE PERMIT IS ISSUED WILL NEED TO BE DECIDED ON BY THE
 BUILDING OFFICIAL ROBERT BROWN AND THE DIRECTOR OF THE
 CRA, STIPULATIONS WILL ALSO NEED TO BE AGREED UPON AND
 BEFORE THE ISSUANCE OF A CERTIFICATE OF COMPLETION
 SINCE THIS PERMIT IS FOR A SHELL ONLY.
  
 1ST ROUND OF COMMENTS. WHEN VIEWING THIS PROJECT IN THE
 PALM BEACH COUNTY PROPERTY APPRAISERS WEBSITE THE
 PROJECT COMPRISES OF 2 LOTS 719 AND 713 N. SAPODILLA
 AVE. PLEASE NOTE WITHOUT A UNITY OF TITLE THE CANOPY
 CANNOT BE BUILT SINCE IT PASSES OVER PROPERTY LINES OF
 2 ADJOINING LOTS.
 CREATION OR EXTENSION OF NONCONFORMITY. 2017 EXISTING
 BUILDING CODE LEVEL II 701.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING. CREATION OR EXTENSION OF
 NONCONFORMITY. ALL NEW WORK, RE-CONFIGURATION SHALL NOT
 CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING
 BUILDING TO WHICH THE RE-CONFIGURATION OF SPACE IS
 BEING MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL
 STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY
 OF MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS.
  
 UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE'
 SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT
 APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
 OR
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 1C) COMPLIED. NO HISTORIC EXEMPTIONS ARE BEING TAKEN.
  
 1D) 2ND ROUND OF COMMENTS. USING THE SHEET 103C
 ENGINEERING PLAN THE DESIGNER OF RECORD DOES SHOW UNDER
 THE PROPOSED OUTDOOR COVERED PATIO THE 2 REQUIRED
 EXITS. THERE IS ONLY 1 EXIT WHICH IS AN ACCESSIBLE
 EXIT. AS NOTED IN THE 1ST REVIEW IF 2 EXITS ARE
 REQUIRED, THEN 2 ACCESSIBLE EXITS TO THE PUBLIC WAY
 WOULD BE REQUIRED. THE 2ND MEANS OF EGRESS DROPS YOU
 OFF BEHIND THE COVERED PATIO INTO A GRASSED AREA. THIS
 MEANS OF EGRESS NEEDS TO BE EXTENDED TO THE PUBLIC WAY.
 THE 2ND ISSUE WITH THIS MEANS OF EGRESS, A SURVEY WITH
 MEASUREMENTS FROM THE BUILDING ARE NOT SHOWN. IS THERE
 AN ALLEY BEHIND THIS LOT OR ANOTHER LOT? IT CANNOT BE
 DETERMINED IF THE EXIT DISCHARGE FROM UNDER THE COVERED
 OUTDOOR PATIO TO THE PROPERTY LINE FOR THE EGRESS COURT
 WILL REQUIRE 1 HOUR RATED WALLS AT THE PROPERTY LINE,
 SEE 2017 FBC-B SECTION 1028.4.2.
  
 1ST ROUND OF COMMENTS. PLEASE NOTE THE TABLE SHOWING
 THE OCCUPANT LOAD FOR THE BUILDING AS A TOTAL 145
 OCCUPANTS. PLEASE NOTE THAT THE COVERED OUTDOOR PATIO
 IS ALREADY OUTSIDE OF THE BUILDING AND A SEPARATE COUNT
 SHOULD BE TAKEN FOR THIS OUTDOOR SEATING. A SEPARATE
 PERMIT SHOULD BE APPLIED FOR THE CANOPY. PLEASE ALSO
 NOTE THE OCCUPANT LOAD UNDER THE OUTDOOR CANOPY IS
 STATED AT 77 REQUIRING 2 EXITS.
 PLEASE NOTE THE CURRENT EXIT FROM THE PATIO EXITS ONTO
 THE GRASS, NOT AN ACCESSIBLE EXIT. 2017
 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF EGRESS
 SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
  
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
  
 1E) COMPLIED.
  
 2) LIFE SAFETY SHEET LS1:
  
 2A)(1) SEMI-COMPLIED SEE COMMENT (1D), REQUIRES 2
 ACCESSIBLE MEANS OF EGRESS TO THE PUBLIC WAY.
 1ST ROUND OF COMMENTS. WITHIN THE BUILDING THE PLANS
 SHOW 2 REQUIRED EXITS. UNDER THE COVERED OUTDOOR PATIO
 THE WITH AN OCCUPANT LOAD OF 77 BUT ONLY ONE MEANS OF
 EGRESS, YOU CAN?T REENTER THE BUILDING FOR THE 2ND
 MEANS OF EGRESS, PLEASE SHOW COMPLIANCE WITH THE 2017
 FBC-B TABLE 1006.2.1 MAXIMUM OCCUPANT LOAD WITH ONE
 EXIT.
  
 2A)(2) NEW COMMENT. SHEET 002 PROJECT INFO STATES THERE
 IS 90 SEATS ON THE EXTERIOR PATIO, THE LIFE SAFETY
 SHEET 1ST FLOOR INDICATES 100 SEATS WHEN YOU COUNT THE
 SEATS 110 SEATS ON THE PATIO. WHERE THE 2 PATIO EXITS
 ARE IN A GREY BOX AND STATING FUTURE ASSEMBLY
 CONCENTRATED, THIS AREA IS PART OF THE EGRESS PATH AND
 NOT HAVE OCCUPANTS BLOCKING THE EGRESS PATH. PLEASE
 REVIEW: WHERE PERSONS ARE ADMITTED TO THE BUILDING AT
 TIMES WHEN SEATS ARE NOT AVAILABLE, SUCH PERSONS SHALL
 BE ALLOWED TO WAIT IN A LOBBY OR SIMILAR SPACE,
 PROVIDED SUCH LOBBY OR SIMILAR SPACE SHALL NOT ENCROACH
 UPON THE MINIMUM WIDTH OR REQUIRED CAPACITY OF THE
 MEANS OF EGRESS. 2017 FBC-B 1029.4.
  
 2B) 2ND REQUEST. THE RESPONSE SHEET INDICATES THE
 OUTDOOR CANOPY IS TO BE UNDER SEPARATE PERMIT BUT ON
 SHEETS 315A, 320A & 321A NOTE # 10 MENTIONS THE OUTDOOR
 CANOPY NEW FIXED FABRIC SHED AWNING AND SHOP DRAWINGS
 TO BE SIGNED AND SEALED BY A FLORIDA REGISTERED
 ENGINEER. NOWHERE DOES THE STATEMENT ON ANY OF THE
 PLANS INDICATE UNDER SEPARATE PERMIT.
 1ST ROUND OF COMMENTS. IS THE COVERED OUTDOOR PERMIT
 SUPPOSED TO BE PART OF THIS PERMIT PACKAGE OR UNDER A
 SEPARATE PACKAGE. THERE IS NO DESIGN INFORMATION FOR
 THIS PORTION OF WORK. IS THE SAME CONTRACTOR FOR THE
 BUILDING AS THE COVERED OUTDOOR DINING AREA. 107.2.1.2.
 ADDITIONAL INFORMATION REQUIRED.
  
 2C) 2ND REQUEST. THE RESPONSE SHEET INDICATES THE
 OUTDOOR CANOPY IS TO BE UNDER SEPARATE PERMIT BUT ON
 SHEETS 320A & 321A NOTE # 10 MENTIONS THE OUTDOOR
 CANOPY NEW FIXED FABRIC SHED AWNING AND SHOP DRAWINGS
 TO BE SIGNED AND SEALED BY A FLORIDA REGISTERED
 ENGINEER. NOWHERE DOES THE STATEMENT ON ANY OF THE
 PLANS INDICATE UNDER SEPARATE PERMIT.
 1ST ROUND OF COMMENTS. THE COVERED OUTDOOR DINING AREA.
 THERE IS NO INFORMATION FOR THIS AREA OF WORK. WILL
 THERE BE PLASTIC WIND BREAKS ADDED TO THE CANOPY FOR
 RAIN AND HEAT IN THE WINTER? 107.2.1.2. ADDITIONAL
 INFORMATION REQUIRED.
  
 2D) COMPLIED. MEZZANINE LEVEL IS 1/3RD THE FLOOR AREA
 ALLOWED BY SECTION 505.2.1
  
 2E) 2ND REQUEST. THE PLANS LIFE SAFETY 1ST FLOOR AND
 MEZZANINE LEVEL STATE YES FIRE EXTINGUISHERS ON THE
 PLAN BUT DO NOT PLACE THEM IN THE BUILDING SHOWING CODE
 COMPLIANCE.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1. W.P.B.
 ADMINISTRATIVE CODE/2017. CONSTRUCTION DOCUMENTS SHALL
 BE SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
 1ST ROUND OF COMMENTS. THE PLANS UNDER THE HEADING OF
 FIRE PROTECTION SYSTEMS ALSO INDICATES PORTABLE FIRE
 EXTINGUISHERS BUT NONE ARE SHOWN ON THE FLOOR PLAN OR
 COMPLIANCE WITH 2017 FBC-B 906.1.
  
 2F) NEW COMMENT. THE 1ST FLOOR LIFE SAFETY PLAN SHOWS 1
 ACCESSIBLE SEAT AT WHAT APPEARS TO BE THE BAR, PLEASE
 SHOW COMPLIANCE WITH THE 2017 FBC-ACCESSIBLITY CODE
 SECTION. 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2G) NEW COMMENT. THE 1ST FLOOR PLAN HAS A TOTAL OF 153
 SEATS ON THE 1ST FLOOR. 153 XO.O5= 7.65 OR 8 ACCESSIBLE
 SEATS REQUIRED. THE PLAN ONLY SHOWS 6 PLEASE UPDATE THE
 PLANS. 2017 ACCESSIBILITY CODE 226.1 WHERE DINING
 SURFACES ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR
 DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES AND
 STANDING SPACES AT THE DINING SURFACES SHALL COMPLY
 WITH 902.
  
 3) SHEET LS 2 THE MEZZANINE PLAN.
  
 3A-B) COMPLIED.
  
 4) COMPLIED. ROOF HATCH 16 SQ. FT. OF OPENING.
  
 5-7) COMPLIED.
  
 8) 2ND REQUEST. PERMIT 19051529 IF THIS PERMIT IS FOR
 THE SCREENING PROPERTY LINE WALL OR IS IT FOR SCREENING
 WALL ON THE ROOF TOP FOR THE A/C UNITS. THE RESPONSE
 COMMENTS SOUND AS IF IT IS FOR THE ROOF TOP SCREENING
 OF THE A/C EQUIPMENT WHICH WOULD BE PART OF THE MAIN
 BUILDING PERMIT? A SEPARATE PERMIT IS REQUIRED FOR PLAN
 SHEET A326 TRASH ENCLOSURE AND PRECAST CONCRETE WALL
 SYSTEM. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 9) PROVISO: SHEET 328 A ROOF DETAILS, DETAIL 3. 2017
 FBC-B TABLE 1510.10. BOTTOM OF HORIZONTAL FRAMING
 MEMBER ALLOWS FOR THE WIDTH OF THE A/C UNIT TO BE 24
 -36 INCHES WIDE.
  
 10) COMPLIED.
  
 11) COMPLIED, ASCE 7-10.
  
 12) 2ND REQUEST. SHEET 400S. S1 UNDER THE HEADING OF
 SHALLOW FOUNDATION MENTIONS A SOILS REPORT BY
 GEOTECHNICAL MATERIAL TESTING INSPECTION SERVICES DATED
 01/18/2018, PLEASE SUBMIT THE REPORT FOR ITS FINDINGS.
 2017 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
 PLEASE SUBMIT EITHER IF IN PAPER AN ORIGINAL SIGNED AND
 SEALED REPORT. IF ELECTRONICALLY THE REPORT WILL NEED
 TO BE SIGNED AND SEALED ELECTRONICALLY.
  
 13) PROVISO: THIS PROJECT HAS BOLTED STEEL CONNECTIONS
 AS WELL AS WELDED STEEL CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION. IN ACCORDANCE WITH THE AMERICAN WELDING
 SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS IN REGARDS TO THESE
 REQUIREMENTS PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
 14) PROVISO/ DEFERRED SUBMITTALS. 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, EFIS
 SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 15A) PROVISO/ DEFERRED SUBMITTALS. W. P. B. 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 15B) PROVISO/ DEFERRED SUBMITTALS. DELEGATED
 ENGINEERING. 61G15-30.003 ENGINEERING DOCUMENT
 CLASSIFICATION. FL 61G-15-30.006 (3) THE DELEGATED
 ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING
 DOCUMENTS TO THE ENGINEER OF RECORD FOR REVIEW.
  
 15C)PROVISO: 107.3.4.2 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 16) PROVISO/ DEFERRED SUBMITTALS. PLEASE IDENTIFY ON
 THE PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 17A) PROVISO/ DEFERRED SUBMITTALS. ROOFING PRODUCT
 APPROVALS: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL
 ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR
 ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS,
 IF ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 17B) PROVISO/ DEFERRED SUBMITTALS. 107.2.1.2 FOR ROOF
 ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION
 DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE
 TYPE OF ROOFING SYSTEM, MATERIALS, VENTING, FASTENING
 REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE
 RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT
 EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE
 WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE.
  
 18) IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
 19) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-23 Cont ID  
Sent By jwitmer Date 2019-07-23 Time 07:50 Rev Time 0.00
Received By jwitmer Date 2019-07-22 Time 07:58 Sent To  
Notes
2019-07-23 07:49:552017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19051525
 ADD: 719 N. SAPODILLA AVE.
 CONT: TBD/ TO BE DETERMINED
 TEL: NONE
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY JULY 22/2019
 ACTION: DENIED
  
 1) SHEET G DRAWING INDEX & PROJECT INFO:
  
 1A) PLEASE NOTE THE DRAWING INDEX THERE SHOULD BE A
 SURVEY SHEET 005G BETWEEN SHEET 004 G STANDARD
 ABBREVIATIONS & SYMBOLS SHEET AND CIVIL COVER SHEET
 100C. MISSING DOCUMENT. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 1B) WHEN VIEWING THIS PROJECT IN THE PALM BEACH COUNTY
 PROPERTY APPRAISERS WEBSITE THE PROJECT COMPRISES OF 2
 LOTS 719 AND 713 N. SAPODILLA AVE. PLEASE NOTE WITHOUT
 A UNITY OF TITLE THE CANOPY CANNOT BE BUILT SINCE IT
 PASSES OVER PROPERTY LINES OF 2 ADJOINING LOTS.
 CREATION OR EXTENSION OF NONCONFORMITY. 2017 EXISTING
 BUILDING CODE LEVEL II 701.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING. CREATION OR EXTENSION OF
 NONCONFORMITY. ALL NEW WORK, RE-CONFIGURATION SHALL NOT
 CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING
 BUILDING TO WHICH THE RE-CONFIGURATION OF SPACE IS
 BEING MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL
 STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY
 OF MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS.
  
 UNITY OF TITLE. / UNITY OF CONTROL (2) DIFFERENT
 OWNERS/ QUICK CLAIM DEED
 THE PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL
 BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'. A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT
 APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
 OR
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 1C) UNDER THE SCOPE OF WORK THE PLANS STATE THAT THIS
 PROJECT IS THE RECONSTRUCTION OF A HISTORIC BUILDING,
 BUT THERE IS NO EXPLANATION AS TO WHAT EXEMPTIONS YOU
 ARE TAKING FOR A HISTORIC BUILDING. 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 1D) PLEASE NOTE THE TABLE SHOWING THE OCCUPANT LOAD FOR
 THE BUILDING AS A TOTAL 145 OCCUPANTS. PLEASE NOTE THAT
 THE COVERED OUTDOOR PATIO IS ALREADY OUTSIDE OF THE
 BUILDING AND A SEPARATE COUNT SHOULD BE TAKEN FOR THIS
 OUTDOOR SEATING. A SEPARATE PERMIT SHOULD BE APPLIED
 FOR THE CANOPY. PLEASE ALSO NOTE THE OCCUPANT LOAD
 UNDER THE OUTDOOR CANOPY IS STATED AT 77 REQUIRING 2
 EXITS.
 PLEASE NOTE THE CURRENT EXIT FROM THE PATIO EXITS ONTO
 THE GRASS, NOT AN ACCESSIBLE EXIT. 2017
 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF EGRESS
 SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
  
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
 1E) SHEET 002 G THE DRAWING INDEX & PROJECT INFO SHEET
 UNDER THE HEADING OF FIRE PROTECTION THE PLAN INDICATES
 NO FIRE SPRINKLERS FOR THIS PROJECT WHEREAS ON SHEET
 404S-S2.2 THE ROOF FRAMING PLAN ROOF NOTE 2 INDICATES
 THE JOIST DELEGATE ENGINEER SHALL COORDINATE W/ FIRE
 SPRINKLER PLAN FOR THE SPRINKLER LOCATIONS AND LOADS TO
 BE SUPPORTED BY THE JOIST. DISCREPANCY IN PLANS.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) LIFE SAFETY SHEET LS1:
 2A) WITHIN THE BUILDING THE PLANS SHOW 2 REQUIRED
 EXITS. UNDER THE COVERED OUTDOOR PATIO THE WITH AN
 OCCUPANT LOAD OF 77 BUT ONLY ONE MEANS OF EGRESS, YOU
 CAN?T REENTER THE BUILDING FOR THE 2ND MEANS OF EGRESS,
 PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B TABLE
 1006.2.1 MAXIMUM OCCUPANT LOAD WITH ONE EXIT.
  
 2B) IS THE COVERED OUTDOOR PERMIT SUPPOSED TO BE PART
 OF THIS PERMIT PACKAGE OR UNDER A SEPARATE PACKAGE.
 THERE IS NO DESIGN INFORMATION FOR THIS PORTION OF
 WORK. IS THE SAME CONTRACTOR FOR THE BUILDING AS THE
 COVERED OUTDOOR DINING AREA. 107.2.1.2. ADDITIONAL
 INFORMATION REQUIRED.
  
 2C) THE COVERED OUTDOOR DINING AREA. THERE IS NO
 INFORMATION FOR THIS AREA OF WORK. WILL THERE BE
 PLASTIC WIND BREAKS ADDED TO THE CANOPY FOR RAIN AND
 HEAT IN THE WINTER? 107.2.1.2. ADDITIONAL INFORMATION
 REQUIRED.
  
 2D) FIRST FLOOR COMMERCIAL KITCHEN AND LEASE SPACE
 INSIDE WALL LINE IS APPROXIMATELY 1,328.5 SQ. FT. IT
 APPEARS THE MEZZANINE LEVEL IS OVER THE ALLOWABLE 1/3RD
 THE FLOOR AREA ALLOWED BY SECTION 505.2.1 AREA
 LIMITATION OF THE 2017 FBC-B. THE AGGREGATE AREA OF A
 MEZZANINE OR MEZZANINES WITHIN A ROOM SHALL BE NOT
 GREATER THAN ONE-THIRD OF THE FLOOR AREA OF THAT ROOM
 OR SPACE IN WHICH THEY ARE LOCATED. THE ENCLOSED
 PORTION OF A ROOM SHALL NOT BE INCLUDED IN A
 DETERMINATION OF THE FLOOR AREA OF THE ROOM IN WHICH
 THE MEZZANINE IS LOCATED.
 THE 1,362.5 SQ. FT. AREA OF THE 1ST FLOOR MINUS 118 SQ.
 FT. (RESTROOMS) OR 1,244.5/ 3 = 414.66 ALLOWABLE AREA
 FOR THE MEZZANINE. THE AREA OF THE MEZZANINE WALLS
 INCLUDED IS APPROX. 492 SQ. FT. OR 78 SQ. FT. OVER THE
 ALLOWABLE AREA. THERE IS ALSO AN AREA OF CONCERN WHAT
 APPEARS TO BE JANITORS CLOSET THAT WAS NOT INCLUDED IN
 THE REDUCTION FACTOR.
  
 2E) THE PLANS UNDER THE HEADING OF FIRE PROTECTION
 SYSTEMS ALSO INDICATES PORTABLE FIRE EXTINGUISHERS BUT
 NONE ARE SHOWN ON THE FLOOR PLAN OR COMPLIANCE WITH
 2017 FBC-B 906.1.
  
 3) SHEET LS 2 THE 2ND FLOOR (MEZZANINE) PLAN.
  
 3A) THIS PLAN SHOWS AN ASSEMBLY OCCUPANCY WITH AN
 OCCUPANT LOAD OF 30 OCCUPANTS. PLEASE PROVIDE
 COMPLIANCE WITH THE 2017 EXISTING BUILDING CODE SECTION
 1006.1. ACCESSIBILITY IN PORTIONS OF THE BUILDING
 UNDERGOING A CHANGE OF OCCUPANCY CLASSIFICATION SHALL
 COMPLY WITH THE PROVISIONS OF THE:
 FBC- ACCESSIBILITY CODE 201.1.1 VERTICAL ACCESSIBILITY.
 SECTIONS 553.501-553.513, F.S., AND THE ADA STANDARDS
 FOR ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY
 BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE
 SECTIONS FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE
 OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE
 STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH
 BUILDING, STRUCTURE OR FACILITY.
 FLORIDA VERTICAL ACCESSIBILITY REQUIRES ALL LEVELS IN
 ALL NEW BUILDINGS, STRUCTURES AND FACILITIES AND ALL
 ALTERED AREAS OF EXISTING BUILDINGS, STRUCTURES AND
 FACILITIES TO BE ACCESSIBLE TO PERSONS WITH
 DISABILITIES. ALL NEW AND ALTERED AREAS MUST COMPLY
 WITH THE ADA STANDARDS FOR ACCESSIBLE DESIGN INCLUDING
 REQUIREMENTS FOR ACCESSIBLE ROUTES. WHERE THE ADA
 STANDARDS DO NOT REQUIRE AN ACCESSIBLE ROUTE TO EACH
 AND EVERY LEVEL, THE FLORIDA REQUIREMENT MAY BE WAIVED
 DOWN TO THE REQUIREMENT OF THE ADA STANDARDS.
  
 SEE ACCESSIBILITY CODE SECTION 408.1.
 LIMITED-USE/LIMITED-APPLICATION ELEVATORS SHALL COMPLY
 WITH 408 AND WITH ASME A17. THEY SHALL BE PASSENGER
 ELEVATORS AS CLASSIFIED BY ASME A17.1. ELEVATOR
 OPERATION SHALL BE AUTOMATIC.
  
 3B)HANDRAIL/ GUARDRAIL COMPLIED SHEET 327 A DETAIL
 SHEET.
  
 4) BOTH SHEETS A 2ND FLOOR REFLECTED CEILING PLAN & A
 PROPOSED ROOF PLAN AND SHEET 329 ROOF DETAILS, DETAIL 2
 SHOW ROOF TOP ACCESS WITH A ROOF HATCH. PLEASE REVIEW
 ROOF TOP HATCH SIZE REQUIREMENTS UNDER 2017 FBC-B
 1011.12.2 ROOF ACCESS.
 EXCEPTION: IN BUILDINGS WITHOUT AN OCCUPIED ROOF,
 ACCESS TO THE ROOF SHALL BE PERMITTED TO BE A ROOF
 HATCH OR TRAP DOOR NOT LESS THAN 16 SQUARE FEET IN AREA
 AND HAVING A MINIMUM DIMENSION OF 2 FEET.
  
 5) THE 2ND FLOOR PLAN DOES NOT SHOW ANY OF THE PROPOSED
 CHASES FOR THE FUTURE KITCHEN EQUIPMENT ON THE
 ARCHITECTURAL SHEET THAT ARE SHOWN ON THE M1.02 2ND
 FLOOR PLAN. PLEASE ALSO NOTE THE S2.1 ALSO IS MISSING
 THE BLOCK OUTS IN THE NEW 2ND FLOOR SLAB. 107.2.1.2
 ADDITIONAL INFORMATION REQUIRED ON THE A & S SHEETS.
  
 6) STRUCTURAL SHEETS INDICATE THE STAIRS TO THE 2ND
 FLOOR ARE TO BE DESIGNED BY A SPECIALTY ENGINEER.
 DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 7) THE ARCHITECTURAL SHEET A STAIR PLAN DOES NOT
 PROVIDE A VERTICAL SECTION OF THE STAIRS. IT IS NOT
 CLEAR IF THE UNDER THE STAIR WAY WHAT OCCURS, NO
 STORAGE. FBC-B 1011.7.3. ENCLOSURES UNDER INTERIOR
 STAIRWAYS. ALSO LOOK AT THE ACCESS. CODE 307.4 VERTICAL
 CLEARANCES AND FIGURE 307.4.
  
 8) THE SUBMITTED PLAN A DETAILS SHOW A TRASH ENCLOSURE
 AND PRECAST CONCRETE WALL SYSTEM. THESE ITEMS WILL
 REQUIRE A SEPARATE PERMIT, NOT PART OF THIS REVIEW VOID
 DETAILS. DETAILS INDICATE SCREEN WALL DESIGN INDICATE
 THE DEPTH AND DIAMETER OF FOUNDATION TO BE DETERMINED.
  
 9) SHEET 328 A ROOF DETAILS, DETAIL 3 WILL NEED TO
 COMPLY WITH THE HEIGHT REQUIREMENTS FOR ROOF TOP
 EQUIPMENT SEE THE 2017 FBC-B TABLE 15.10 CLEARANCE
 BELOW RAISED ROOF MOUNTED MECHANICAL UNITS.
  
 10) SHEET 317A PROPOSED ROOF PLAN NOTE # 12 DOES NOT
 MATCH THE DETAIL SHEET 329A ROOF DETAILS. SHEET 317A
 NOTE # 12 INDICATES A PROPOSED 4 FOOT HIGH LOUVERED
 ROOF TOP EQUIPMENT SCREEN: WILLARD SHUTTER CO.
 ECONOSPAN 45 DEGREES PITCHED LOUVER. G. C. TO PROVIDE
 SHOP DRAWINGS. DISCREPANCY IN NOTE 12 VERSUS THE
 DETAILS ON SHEET A317. 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED, DISCREPANCY IN PLANS.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 11) SHEET 401SS1.1. THE WALL PRESSURE CHART IN VASD AND
 KD= 0.85, MEAN ROOF HEIGHT OF 21 FEET(USING 20 FOOT
 MEAN ROOF HEIGHT FROM CHARTS), NO 3 FOOT PARAPET, THE
 OPENING PRESSURES ARE BETWEEN 2.8 TO 3 PSF LOWER THAN
 THE ASCE CHARTS AND ENGINEER FRANK BONNARD?S CHARTS.
 YOUR RANGE OF OPENING SIZES ALSO DOES NOT LINE UP TO
 THE ASCE CHARTS EITHER. YOU START AT 0-19 SQ. FT. OF
 TRIBUTARY OR EFFECTIVE WIND AREA DEPENDING ON IF YOU
 ARE USING THE ASCE OR CHART IN 1609 OF THE FBC-B CODE
 BOOK WHERE THESE CHARTS ARE STARTING AT 10 FEET. PLEASE
 PROVIDE WHY YOUR PRESSURES ARE LOWER? ROOF PRESSURES ON
 SHEET 400 S.S1 PRESSURES ARE GOOD.
  
 12) SHEET 400S. S1 UNDER THE HEADING OF SHALLOW
 FOUNDATION MENTIONS A SOILS REPORT BY GEOTECHNICAL
 MATERIAL TESTING INSPECTION SERVICES DATED 01/18/2018,
 PLEASE SUBMIT THE REPORT FOR ITS FINDINGS.
 2017 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
 PLEASE SUBMIT EITHER IF IN PAPER AN ORIGINAL SIGNED AND
 SEALED REPORT. IF ELECTRONICALLY THE REPORT WILL NEED
 TO BE SIGNED AND SEALED ELECTRONICALLY.
  
 13) THIS PROJECT HAS BOLTED STEEL CONNECTIONS AS WELL
 AS WELDED STEEL CONNECTIONS. THE CONTRACTOR IS REQUIRED
 TO PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER
 OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION. IN ACCORDANCE WITH THE AMERICAN WELDING
 SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS IN REGARDS TO THESE
 REQUIREMENTS PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
 14) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, EFIS
 SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 15A) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 15B) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 15C) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 16) PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 17A) ROOFING PRODUCT APPROVALS: FOR ALL ROOFING
 PRODUCTS PLEASE IDENTIFY ALL ROOFING SUB-SYSTEMS AND
 THEIR ASSOCIATED PRESSURES FOR ROOF ZONE # 1. REVIEW
 THE PRODUCT APPROVAL LIMITATIONS, IF ENHANCED FASTENING
 IS ALLOWED FOR ROOF ZONES 2 & 3. FASTENER DENSITIES
 SHALL BE INCREASED FOR BOTH INSULATION & THE BASE SHEET
 AS CALCULATED IN COMPLIANCE WITH ROOFING APPLICATION
 STANDARDS RAS 117. CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 17B) 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE
 CODE, THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE,
 DESCRIBE AND DELINEATE THE TYPE OF ROOFING SYSTEM,
 MATERIALS, VENTING, FASTENING REQUIREMENTS, FLASHING
 REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE
 REQUIRED TO BE INSTALLED. PRODUCT EVALUATION AND
 INSTALLATION SHALL INDICATE COMPLIANCE WITH THE WIND
 CRITERIA REQUIRED FOR THE SPECIFIC SITE.
  
 18) IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
 19) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2022-04-27 Cont ID  
Sent By mpeterso Date 2022-04-27 Time 13:49 Rev Time 0.00
Received By mpeterso Date 2022-04-27 Time 13:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-01-10 Cont ID  
Sent By jleahy Date 2022-01-10 Time 14:28 Rev Time 0.00
Received By jleahy Date 2022-01-10 Time 14:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-12-26 Cont ID  
Sent By jpearson Date 2019-12-26 Time 09:11 Rev Time 0.00
Received By jpearson Date 2019-12-26 Time 09:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-07-23 Cont ID  
Sent By jleahy Date 2019-07-23 Time 14:38 Rev Time 0.00
Received By jleahy Date 2019-07-23 Time 14:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2022-04-11 Cont ID  
Sent By cwalker Date 2022-04-11 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2021-12-15 Cont ID  
Sent By cwalker Date 2021-12-15 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-03-02 Cont ID  
Sent By pleduc Date 2020-03-02 Time   Rev Time 0.00
Received By pleduc Date 2020-03-02 Time 13:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-12-16 Cont ID  
Sent By pleduc Date 2019-12-16 Time   Rev Time 0.00
Received By pleduc Date 2019-12-16 Time 12:50 Sent To  
Notes
2019-12-16 13:20:55THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE RECONSTURCTION OF THE ROOF SYSTEM INDICATES
 LIGHT-FRAMET TRUSS TYPE.
  
  
 PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR
 STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION.
 ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT
 RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES
 HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A
 MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND
 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR.
 THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO
 THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-07-05 Cont ID  
Sent By pleduc Date 2019-07-05 Time   Rev Time 0.00
Received By pleduc Date 2019-07-05 Time 13:29 Sent To  
Notes
2019-07-05 14:55:12THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE RECONSTURCTION OF THE ROOF SYSTEM INDICATES
 LIGHT-FRAMET TRUSS TYPE.
  
  
 PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR
 STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION.
 ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT
 RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES
 HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A
 MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND
 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR.
 THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO
 THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2022-06-13 Cont ID  
Sent By ccole Date 2022-06-13 Time 13:42 Rev Time 0.00
Received By ccole Date 2022-06-13 Time 12:23 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2022-04-19 Cont ID  
Sent By ccole Date 2022-04-19 Time 14:03 Rev Time 0.00
Received By ccole Date 2022-04-19 Time 11:16 Sent To  
Notes
2022-04-19 14:04:122ND REVIEW FBC-2020 FUEL GAS
 PERMIT-19051525
 4/19/22
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENT #2 FROM THE 1ST
 REVIEW PRINTED BELOW WAS NOT ADDRESSED. PLEASE PROVIDE
 THE SUBMITTALS OR INDICATE THEY WILL BE DEFERRED PER
 SEC 107.4.1 WPB.
  
 2) P301: SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 COOKING APPLIANCES MARKED OR HIGHLIGHTED TO SHOW THE
 BTU LOADS AND THE INPUT PRESSURES- SEC. 623.1 FBC FG.
 PLEASE NOTE THAT REGULATORS MAY BE REQUIRED AT EACH
 APPLIANCE BASED ON INPUT PRESSURE RATINGS- SECTION
 410.2 FBC FG. PLEASE REVIEW THE SPECS AND SHOW
 REGULATORS AND INPUT/OUTPUT PRESSURES WHERE REQUIRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-12-17 Cont ID  
Sent By ccole Date 2021-12-17 Time 11:17 Rev Time 0.00
Received By ccole Date 2021-12-16 Time 16:48 Sent To  
Notes
2021-12-17 11:18:091ST REVIEW FBC-2020 FUEL GAS
 PERMIT-19051525
 12/16/21
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P301: PROVIDE COMBUSTION AIR CALCULATIONS FOR
 THE COOKING APPLIANCES AND INDICATE HOW THE AIR WILL BE
 PROVIDED- SECTION 304.1 FBC FG.
  
 2) P301: SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 COOKING APPLIANCES MARKED OR HIGHLIGHTED TO SHOW THE
 BTU LOADS AND THE INPUT PRESSURES- SEC. 623.1 FBC FG.
 PLEASE NOTE THAT REGULATORS MAY BE REQUIRED AT EACH
 APPLIANCE BASED ON INPUT PRESSURE RATINGS- SECTION
 410.2 FBC FG. PLEASE REVIEW THE SPECS AND SHOW
 REGULATORS AND INPUT/OUTPUT PRESSURES WHERE REQUIRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 5 Status P Date 2022-05-04 Cont ID  
Sent By amhamilt Date 2022-05-04 Time 11:54 Rev Time 0.00
Received By amhamilt Date 2022-05-04 Time 11:54 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 4 Status P Date 2020-07-06 Cont ID  
Sent By fmittner Date 2020-07-06 Time 15:55 Rev Time 0.00
Received By fmittner Date 2020-07-06 Time 15:55 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2020-03-12 Cont ID  
Sent By fmittner Date 2020-03-12 Time 13:35 Rev Time 0.00
Received By fmittner Date 2020-03-12 Time 13:35 Sent To  
Notes
2020-03-12 13:35:21DMP TO DO ZONING REVIEW.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-12-23 Cont ID  
Sent By fmittner Date 2019-12-23 Time 12:33 Rev Time 0.00
Received By fmittner Date 2019-12-23 Time 12:33 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-07-15 Cont ID  
Sent By fmittner Date 2019-07-15 Time 14:55 Rev Time 0.00
Received By fmittner Date 2019-07-15 Time 14:55 Sent To Z
Notes
2019-07-15 14:55:28DMP TO COMPLETE ZONING REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date   Cont ID  
Sent By   Date 2022-06-28 Time   Rev Time 0.00
Received By lmarchan Date 2022-06-08 Time 13:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2022-06-08 Cont ID  
Sent By lmarchan Date 2022-06-08 Time 11:13 Rev Time 0.00
Received By lmarchan Date 2022-04-10 Time 09:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-01-11 Cont ID  
Sent By lmarchan Date 2022-01-11 Time 09:19 Rev Time 0.00
Received By lmarchan Date 2021-12-09 Time 10:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-07-09 Cont ID  
Sent By lmarchan Date 2020-07-09 Time 11:26 Rev Time 0.00
Received By lmarchan Date 2020-07-01 Time 16:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-03-26 Cont ID  
Sent By cpuell Date 2020-03-26 Time 09:28 Rev Time 0.00
Received By cpuell Date 2020-02-28 Time 13:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-01-13 Cont ID  
Sent By lmarchan Date 2020-01-13 Time 10:16 Rev Time 0.00
Received By lmarchan Date 2019-12-12 Time 07:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-08-01 Cont ID  
Sent By shill Date 2019-08-01 Time 15:10 Rev Time 0.00
Received By shill Date 2019-07-01 Time 11:43 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-05-10 Cont ID  
Sent By lmarchan Date 2022-05-10 Time 12:18 Rev Time 0.00
Received By lmarchan Date 2020-07-09 Time 11:26 Sent To  
Notes
2022-05-09 17:02:09RECEIPT MU-2020-029346 - $20,176.53 PAID
2022-01-10 14:33:15IMPACT OFFICE WILL NEED TO BE NOTIFIED TO RE-REVIEW FOR
 IMPACT FEES DUE TO CHANGES ON PLANS. LEM
2020-07-09 11:26:427/9/20 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-07-23 Cont ID  
Sent By jwitmer Date 2019-07-23 Time 07:47 Rev Time 0.00
Received By jwitmer Date 2019-07-22 Time 07:58 Sent To  
Notes
2019-07-23 07:47:43IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2022-04-26 Cont ID  
Sent By medwards Date 2022-04-26 Time 07:03 Rev Time 0.00
Received By medwards Date 2022-04-26 Time 07:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2021-12-16 Cont ID  
Sent By medwards Date 2021-12-16 Time 15:43 Rev Time 0.00
Received By medwards Date 2021-12-16 Time 15:43 Sent To  
Notes
2021-12-16 15:43:571ST REVIEW FBC-2020 MECHANICAL
 PERMIT-19051525
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS NEW SCOPE OF WORK HAS INCREASED THE VALUE OF
 THE ORIGINAL PROJECT. PLEASE SUBMIT A NEW PLAN REVIEW
 REQUEST FORM SHOWING THE NEW REVISED VALUE OF THIS
 PROJECT. FBC 107.2.1
  
 2) NOTHING ABOUT THE HOOD OR THE REFRIGERATION WILL BE
 REVIEWED UNDER THIS PERMIT. A SEPARATE PERMIT FOR EACH
 WILL BE REQUIRED.
  
 3) SHEET M1.03: THE MEASUREMENT FROM THE HOOD EXHAUST
 TERMINATION TO THE MUA INTAKE IS SHOWING A MEASUREMENT
 OF 8 FT 7 INCHES, PLEASE SHOW THIS CLEARANCE MEETS THE
 10 FEET MINIMUM. FBC M 401.4
  
 4) PLEASE SHOW THE RETURN AIR PATH FROM THE KITCHEN TO
 AHU-3. FBC M 601.6
  
 5) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THE MECHANICAL SYSTEMS. FBC EC
 C403.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-03-17 Cont ID  
Sent By ccole Date 2020-03-17 Time 08:12 Rev Time 0.00
Received By ccole Date 2020-03-16 Time 17:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-12-30 Cont ID  
Sent By ccole Date 2019-12-30 Time 08:29 Rev Time 0.00
Received By ccole Date 2019-12-27 Time 15:48 Sent To  
Notes
2019-12-30 08:30:262ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19051525
 12/30/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS 317A & M1.03: BASED ON THE DRAWINGS IT
 APPEARS THE NEW SCREENING ON THE ROOF WILL ALSO
 FUNCTION AS THE REQUIRED GUARD AT THE ROOF EDGES, AND
 SHALL BE IN COMPLIANCE WITH SECTION 1607.8.1 FBC B
 HANDRAILS AND GUARDS.
  
 HANDRAILS AND GUARDS SHALL BE DESIGNED TO RESIST A
 LINEAR LOAD OF 50 POUNDS PER LINEAR FOOT (PLF) (0.73
 KN/M) IN ACCORDANCE WITH SECTION 4.5.1 OF ASCE 7. GLASS
 HANDRAIL ASSEMBLIES AND GUARDS SHALL ALSO COMPLY WITH
 SECTION 2407.
  
 PLEASE VERIFY THE SCREENING WILL BE IN COMPLIANCE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-08-01 Cont ID  
Sent By shill Date 2019-08-01 Time 14:58 Rev Time 0.00
Received By shill Date 2019-08-01 Time 14:58 Sent To  
Notes
2019-08-01 14:59:251ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19051525
 8/1/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS 308LS & M1.01: THE GREASE EXHAUST DUCT SHALL
 BE ENCLOSED FROM THE POINT OF PENETRATION AT THE
 FLOOR/CEILING ASSEMBLY TO THE OUTLET TERMINAL.
 PLEASE CLARIFY WHICH ENCLOSURE METHOD WILL BE USED- A
 CONSTRUCTED FIRE-RATED SHAFT,
 A LISTED AND LABELED FIELD APPLIED GREASE DUCT WRAP, OR
 UL 2221 FACTORY-BUILT GREASE DUCT ASSEMBLY-
 SECTIONS 506.3.11, 506.3.11.1, & 506.3.11.3 FBC M.
  
 2) M1.03: VERIFY THAT THERE IS AN EXISTING PARAPET
 EXTENDING A MINIMUM OF 42" FROM THE ROOF SURFACE, OR
 PROVIDE MINIMUM 42" HIGH GUARDS AT THE ROOF EDGES WHERE
 SERVICEABLE EQUIPMENT IS LOCATED WITHIN 10' OF THE ROOF
 EDGES- SECTION 304.11 FBC M.
  
 3) M1.03: REFER TO SECTIONS 501.3.1 AND 506.3.13.1 FBC
 M AND INDICATE REQUIRED CLEARANCES FOR THE GREASE
 EXHAUST TERMINATION OUTLET.
  
 4) PLACE NOTES ON THE PLAN TO INDICATE SEPARATE PERMITS
 ARE REQUIRED FOR THE RESTAURANT BUILD-OUT,
 THE KITCHEN HOOD, THE FIRE SUPPRESSION SYSTEM, AND
 WALK-IN COOLERS AND FREEZERS- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2022-06-13 Cont ID  
Sent By ccole Date 2022-06-13 Time 13:42 Rev Time 0.00
Received By ccole Date 2022-06-13 Time 12:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2022-04-19 Cont ID  
Sent By ccole Date 2022-04-19 Time 13:25 Rev Time 0.00
Received By ccole Date 2022-04-19 Time 11:16 Sent To  
Notes
2022-04-19 13:25:492ND REVIEW FBC-2020 PLUMBING
 PERMIT- 19051525
 4/19/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 PREVIOUS REVIEW ARE LISTED BELOW TITH ADDITIONAL NOTES
 FOR CLARIFICATION.
  
 4) FAILED. P101 & P301: SHOW THE HWR LINE ON THE
 PLUMBING FLOOR PLAN AND IN THE ISOMETRIC DRAWING-
 SECTION 607.2 FBC P, AND C404.5.1 FBC EC. THE 1/2-INCH
 HW WATER LINES TO THE LAVATORIES ARE EXCEEDING THE
 MAXIMUM LENGTHS OF 2 FT FROM THE HOT WATER SOURCE TO
 THE FIXTURE- REFER TO SECS. C404.5.1 & C404.5.2 FBC EC.
  
 6C) FAILED. P102: PROVIDE PRIMARY AND EMERGENCY SCUPPER
 AND DOWN SPOUT SIZES- TABLE 1106.3 & SECS.1106.5,
 1108.1 FBC P. PLEASE INCLUDE CONSTRUCTION DETAILS OR
 INSTALLATION DETAILS FOR MANUFACTURED PRODUCTS- SEC.
 107.2.1 WPB. SCUPPPER DETAILS NOT PROVIDED. PLEASE SEE
 SECS. 1503.4.2 & 1503.4.2.1 FBC B.
  
 NEW COMMENT.
  
 1) INDICATE HOW TEMPERED WATER WILL BE DELIVERED FROM
 THE LAVATORIES- SEC. 419.5 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2021-12-17 Cont ID  
Sent By ccole Date 2021-12-17 Time 10:35 Rev Time 0.00
Received By ccole Date 2021-12-16 Time 15:28 Sent To  
Notes
2021-12-17 10:37:171ST REVIEW FBC-2020 PLUMBING
 PERMIT- 19051525
 12/17/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P101: THE SUBMITTED INCREASED SCOPE OF WORK
 INDICATES THE KITCHEN WILL BE INSTALLED. PLEASE REMOVE
 THE "FUTURE" LABELS FOR THE PLUMBING FIXTURES AND
 APPLIANCES- SECTION 107.2.1 WPB.
  
 2) P101, 338 A: THE HAND SINKS (B04) (K10), AND
 DRAINAGE FROM THE ICE MACHINE (B02) AND THE ICE BIN
 (B08) SHALL NOT DISCHARGE INTO THE GREASE WASTE LINE
 AND GREASE INTERCEPTOR- SECTION 1003.3.1 FBC P. GREASE
 INTERCEPTORS SHALL RECEIVE WASTE ONLY FROM FIXTURES AND
 EQUIPMENT THAT ALLOW FATS, OIL OR GREASE TO BE
 DISCHARGED.
  
 3) P101: PROVIDE A PLUMBING FIXTURE SCHEDULE FOR THE
 RESTROOMS- SECTION 107.2.1 WPB. THE ARCHITECTURAL PLANS
 APPEAR TO SHOW WATER CLOSETS WITH FLUSH VALVES WHICH
 REQUIRE 1-INCH SUPPLY PIPES. THE PLUMBING PLAN AND
 ISOMETRIC DRAWING ARE INDICATING 3/4-INCH PIPES- SEE
 TABLE 604.5 FBC P.
  
 4) P101 & P301: SHOW THE HWR LINE ON THE PLUMBING FLOOR
 PLAN AND IN THE ISOMETRIC DRAWING- SECTION 607.2 FBC P,
 AND C404.5.1 FBC EC.
  
 5) P101 & P201: PROVIDE TRAFFIC RATED LIDS FOR THE
 GREASE INTERCEPTOR ACCESS OPENINGS, AND THE SAMPLING
 PORT- SECTION 305.6 FBC P. PLEASE NOTE THAT SPECS FOR
 THE LIDS AND FOR THE GREASE INTERCEPTORS SHALL BE
 SUBMITTED UNDER THE REQUIRED SEPARATE GREASE
 INTERCEPTOR PERMIT- SECS.105.1 & 107.2.1 WPB.
  
 6) P102- ROOF AND STORM DRAINAGE PLANS ARE INCOMPLETE.
 A) INDICATE THE RAINFALL RATE PER SEC. 1106.1 AND
 PROVIDE ROOF DRAINAGE CALCULATIONS BASED ON THE RATE-
 SECS. 1106.1- 1106.4 FBC P.
 B) VERIFY THE ROOF AND DRAINAGE SYSTEM HAS BEEN
 DESIGNED IN COMPLIANCE WITH SECTION 1101.7 FOR MAXIMUM
 DEPTH OF PONDING WATER AND DEFLECTED STRUCTURAL
 ELEMENTS.
 C) PROVIDE PRIMARY AND EMERGENCY SCUPPER AND DOWN SPOUT
 SIZES- TABLE 1106.3 & SECS.1106.5, 1108.1 FBC P. PLEASE
 INCLUDE CONSTRUCTION DETAILS OR INSTALLATION DETAILS
 FOR MANUFACTURED PRODUCTS- SEC. 107.2.1 WPB.
 D) SHOW THE DOWNSPOUT DISCHARGE LOCATIONS. CLARIFY IF
 THE DOWNSPOUTS WILL CONNECT TO AN UNDERGROUND STORM
 DRAIN SYSTEM OR BE DISCHARGED TO GRADE. PLEASE PROVIDE
 CIVIL DRAWINGS SHOWING STORM DRAINAGE POINTS OF
 CONNECTIONS (IF APPLICABLE), OR REFER TO SEC. 1503.7
 FBC B AND INDICATE THE DOWNSPOUTS WILL DISCHARGE AT
 LEAST 1 FOOT AWAY FROM THE BUILDING SIDE WALL TO
 APPROVED LOCATIONS OF DISPOSAL- SEC.1101.2 FBC P.
  
 7) SHEETS 340A-A, 341A-A- FBC ACC COMPLIANCES:
 A) SHOW THE CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS
 FOR THE WATER CLOSETS- SEC. 604.3.
 B) SHOW THE CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS
 FOR THE LAVATORIES- 606.2.
 C) SHOW THE TURNING SPACE DIAMETERS- 304.3.
 D) THE DOORS SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACES REQUIRED FOR THE WATER CLOSETS- 603.2.3
 E) SHOW THE HEIGHTS OF THE WATER CLOSET SEATS FROM THE
 FINISHED FLOORS- SECTION 604.4.
 F) SHOW THE KNEE AND TOE CLEARANCES FOR THE LAVATORIES-
 606.2, AND FIGURES 306.2 & 306.3.
  
 8) SHEETS 315A, 340A-A, 341A-A: PROVIDE THE TYPE OF
 FINISH MATERIALS TO BE INSTALLED AT THE WALL SURROUNDS
 FOR THE WATER CLOSETS, URINALS, AND SERVICE SINK.
 PLEASE NOTE THAT THE MATERIAL SURFACES SHALL BE SMOOTH,
 HARD AND NONABSORBENT IN COMPLIANCE WITH SEC. 310.3 FBC
 P, AND 1210.2.2 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-12-31 Cont ID  
Sent By gjohnson Date 2019-12-31 Time 16:11 Rev Time 0.00
Received By gjohnson Date 2019-12-30 Time 17:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-07-24 Cont ID  
Sent By gjohnson Date 2019-07-24 Time 14:58 Rev Time 0.00
Received By gjohnson Date 2019-07-23 Time 08:19 Sent To  
Notes
2019-07-24 14:58:321ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE WATER ISOMETRIC DOES NOT MATCH THE SITE PLAN IT
 IS MISSING THE HOSE BIB IN THE TRASH ENCLOSURE PLEASE
 CORRECT ISOMETRIC. PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 2. STORM WATER SHALL NOT DISCHARGE TO THE SANITARY THE
 FLOOR DRAIN IN THE TRASH ENCLOSURE SHALL NOT RECEIVE
 STORM WATER. WEST PALM BEACH, FLORIDA - CODE OF
 ORDINANCES SEC. 90-126(5)
  
 3. THE FLOOR DRAIN IN TRASH ENCLOSURE IS MISSING ON THE
 SANITARY ISOMETRIC AND ALSO REQUIRES A TRAP PRIMER. PER
 FBC PL 1002.4.1
  
 THE GREASE WASTE SHOULD NOT DISCHARGE THROUGH THE SAND
 OIL SEPARATOR UNLESS APPROVED BY SCHIER. PER WPB AMEND
 TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 8 Status P Date 2022-06-28 Cont ID  
Sent By jwitmer Date 2022-06-28 Time 10:36 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 7 Status P Date 2022-06-08 Cont ID  
Sent By shill Date 2022-06-08 Time 09:04 Rev Time 0.00
Received By shill Date 2022-06-08 Time 09:04 Sent To  
Notes
2022-04-26 07:04:58MECHANICAL DIGITAL SIGNATURES APPROVED. ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2021-12-15 Cont ID  
Sent By jwitmer Date 2021-12-15 Time 07:13 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2020-07-02 Cont ID  
Sent By jwitmer Date 2020-07-02 Time 09:44 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-04-03 Cont ID  
Sent By pvalenti Date 2020-04-03 Time 11:41 Rev Time 0.00
Received By pvalenti Date 2020-04-03 Time 11:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-04-03 Cont ID  
Sent By pvalenti Date 2020-03-03 Time 11:39 Rev Time 0.00
Received By pvalenti Date 2020-03-03 Time 06:05 Sent To  
Notes
2020-03-03 06:06:47***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 3RD SIGNATURE REVIEW DENIED:
  
 FBC B 107/FS 471/FAC 61G15-23.004, ALL PLANS AND
 ODCUMENTS SUBMITTED DIGITALLY NEED TO BE DIGITALLY
 SIGNED/SEALED AND INCLUDE THIRD PARTY VERIFICATION.
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-01-13 Cont ID  
Sent By lmarchan Date 2020-01-13 Time 10:16 Rev Time 0.00
Received By lmarchan Date 2020-01-13 Time 10:16 Sent To  
Notes
2019-12-26 09:11:08ELECTRICAL SHEETS: PER THE WPB AMENDMENTS TO THE FBC,
 EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL
 PLAN REQUIRES A DIGITAL SIGNATURE WITH THE PROPER THIRD
 PARTY VERIFICATION. SHEET E1.03 IS NOT DIGITALLY
 SIGNED. PROVIDE CORRECTION. WPB FBC 107.1; FS 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-08-01 Cont ID  
Sent By shill Date 2019-08-01 Time 15:10 Rev Time 0.00
Received By shill Date 2019-08-01 Time 15:00 Sent To  
Notes
2019-08-01 15:05:51SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SHEET 002G IS NOT DIGITALLY SIGNED (ARCHITECT);
 PAGES ARE SPOT CHECKED, PLEASE VERIFY ALL.
  
 2. DIGITAL SIGNATURE FOR ADAM SWANEY, PE (CIVIL) IS
 SELF CERTIFIED; 3RD PARTY REQUIRED PER FAC61G15-23.004.
 PLEASE OBTAIN; THIS ISSUE WILL NOT DELAY PERMIT
 ISSUANCE.
  
 3. STRUCTURAL PAGES ARE NOT DIGITALLY SIGNED, FS471,
 DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS.
  
 4. MEP PAGES SIGNATURE OK.
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 6 Status P Date 2022-06-10 Cont ID  
Sent By ckimmerl Date 2022-06-10 Time 14:48 Rev Time 0.00
Received By ckimmerl Date 2022-06-10 Time 14:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status P Date 2022-06-08 Cont ID  
Sent By ckimmerl Date 2022-06-08 Time 09:21 Rev Time 0.00
Received By ajones Date 2022-06-08 Time 09:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2020-07-06 Cont ID  
Sent By aaponte Date 2020-07-06 Time 16:55 Rev Time 0.00
Received By aaponte Date 2020-07-06 Time 16:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2020-03-23 Cont ID  
Sent By aaponte Date 2020-03-23 Time 16:35 Rev Time 0.00
Received By aaponte Date 2020-03-23 Time 16:27 Sent To  
Notes
2020-03-23 16:31:341. LANDSCAPE BUFFER WAS REDUCED FROM THE REQUIRED 5'
 MINIMUM INDICATED IN A PREVIOUS VERSION TO 3'-3".
 PLEASE ADJUST AGAIN TO PROVIDE MINIMUM REQUIREMENT.
 2. REPEAT COMMENT- CURB CUT SHALL BE REDUCED TO A
 MAXIMUM 25' AT THE CURB. THE FLARE IS COUNTED AS PART
 OF THE CURB. IF THE WIDTH OF THE DRIVEWAY AT THE
 SIDEWALK IS REDUCED TO 20 FEET , THE ERSULTING CURB CUT
 AT THE CURB LINE WOULD BE THE MAXIMUM 24' ALLOWED.
 3. LANDSCAPE AREAS SHALL BE PROTECTED FROM VEHICULAR
 ENCROACHMENT.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 2 Status F Date 2020-01-13 Cont ID  
Sent By aaponte Date 2020-01-13 Time 08:38 Rev Time 0.00
Received By aaponte Date 2020-01-13 Time 08:38 Sent To  
Notes
2020-01-13 08:40:121. CURB CUT SHALL BE REDUCED TO MAXIMUM 25 FEET AT THE
 CURB LINE. THIS COMMENT WAS INCLUDED IN PREVIOUS
 REVIEW.
 2. LANDSCAPE DRAWINGS INCLUDED FOR REFERENCE DOES NOT
 MATCH THE SITE PLAN WITH PROPOSED CHANGES AROUND
 DUMPSTER AREA. PLEASE UPDATE AND INCLUDE A NOTE ON THIS
 PLAN STATING THAT THE LANDSCAPE IS FOR REFERENCE ONLY.
 PLEASE SUBMIT A RESPONSE LETTER TO ALL COMMENTS FROM
 THIS REVIEW AND LAST REVIEW.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 1 Status F Date 2019-07-31 Cont ID  
Sent By aaponte Date 2019-07-31 Time 15:19 Rev Time 0.00
Received By aaponte Date 2019-07-31 Time 15:19 Sent To  
Notes
2019-07-31 16:41:211. PROPERTY SHALL BE UNIFIED.
 2. CURB CUT SHALL BE NO MORE THAN 25 FEET AT THE CURB
 LINE, ACCESS DRIVE AT THE SIDEWALK CAN BE AS SMALL AS
 20 FEET. BACK UP SPACE SHALL BE MAINTAINED AT 24 FEET.
 3. DUMPSTER SHALL BE SCREENED WITH A HEDGE. PEDESTRIAN
 GATE CAN BE MOVED TOWARDS THE EAST AND CONCRETE PATH
 CAN BE SHORTENED TO ALLOW FOR HEDGE ON NORTH SIDE.
 4. PLEASE CONFIRM THAT THE CURRENT DUMPSTER LOCATION
 HAS BEEN APPROVED BY PUBLIC WORKS. CONTACT JOSH
 MCDERMONT (822-2044).
 5. PERIMETER WALL SHALL BE REDUCED TO 4 FEET WHEN
 LOCATED WITHIN THE FRONT SETBACK (ALIGNED WITH EXISTING
 FRONT PORCH OF HOUSE ON WEST SIDE ON 7TH STREET, AND
 12.5 FEET ALONG SAPODILLA AVE).
 6. PLEASE REMOVE SHEET 200L FROM THIS PERMIT AS
 LANDSCAPE IS APPROVED UNDER A SEPARATE PERMIT.
 7. PLEASE INDICATE THE SPECS OF NEW LIGHT FIXTURE AND
 POLE TO BE LOCATED ALONG SAPODILLA AVENUE.
 8. PLANTING AREAS SHALL BE PROTECTED FROM VEHICULAR
 ENCROACHMENT (PLANTING ADJACENT TO CURB CUT SHALL BE
 PROTECTED)
 FOR ADDITINAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.