Plan Review Details - Permit 19051495
Plan Review Stops For Permit 19051495
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-08-21 Cont ID  
Sent By cthroop Date 2019-08-21 Time 10:07 Rev Time 0.00
Received By cthroop Date 2019-08-21 Time 10:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-25 Cont ID  
Sent By cthroop Date 2019-06-25 Time 13:16 Rev Time 0.00
Received By cthroop Date 2019-06-24 Time 15:51 Sent To  
Notes
2019-06-25 13:43:46BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE FRAMING DETAIL FOR WINDOW IN-FILL.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. ONE PLAN SHOWS THE WINDOW LOCATED NEXT TO THE CLOSET
 AS 37X38. A SECOND PLAN PAGE SHOWS THIS WINDOW AS
 37X49. PLEASE CLARIFY.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. IDENTIFY EGRESS FROM NEW BEDROOM.
 107.2.3 MEANS OF EGRESS. THE CONSTRUCTION DOCUMENTS
 SHALL SHOW IN SUFFICIENT DETAIL THE LOCATION,
 CONSTRUCTION, SIZE AND CHARACTER OF ALL PORTIONS OF THE
 MEANS OF EGRESS IN COMPLIANCE WITH THE PROVISIONS OF
 THIS CODE.
  
 4. DETAIL #2 PLAN PAGE REQUIRES CONTRACTORS SIGNATURE.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5) AND F.S. 481.229.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-08-21 Cont ID  
Sent By cthroop Date 2019-08-21 Time 10:08 Rev Time 0.00
Received By cthroop Date 2019-08-21 Time 10:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-06-25 Cont ID  
Sent By cthroop Date 2019-06-25 Time 13:56 Rev Time 0.00
Received By cthroop Date 2019-06-24 Time 15:51 Sent To  
Notes
2019-06-25 14:20:41ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PANEL SCHEDULE. INCLUDE ANY NEW CIRCUTS.
 PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902.
  
 2. PANEL SHALL BE LABELED.
 E3401.4 ADDITIONS AND ALTERATIONS.
 ANY ADDITION OR ALTERATION TO AN EXISTING ELECTRICAL
 SYSTEM SHALL BE MADE IN CONFORMITY TO THE PROVISIONS OF
 CHAPTERS 34 THROUGH 43.
  
 3. OUTLET SPACING SHALL COMPLY WITH E3901.2.1.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET.
 PROVIDE CORRECTION. NEC 210.52; FBC RE E3901.2.1.
  
 4. PLAN INDICATES MAIN BREAKER PANEL IS 125 AMPS.
 PUBLIC RECORDS INDICATE EXISTING PANEL TO BE 150 AMPS.
 PLEASE CLARIFY.
  
 5. LOAD CALCULATION PAGE REQUIRES ORIGINAL SIGNATURE OF
 CONTRACTOR.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5) AND F.S. 481.229.
  
 6. SMOKE ALARMS SHALL COMPLY WITH R314.
  
 R314.2.2 ALTERATIONS, REPAIRS AND ADDITIONS.
  
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
 EXCEPTIONS:
 1.WORK INVOLVING THE EXTERIOR SURFACES OF DWELLINGS,
 SUCH AS THE REPLACEMENT OF ROOFING OR SIDING, THE
 ADDITION OR REPLACEMENT OF WINDOWS OR DOORS, OR THE
 ADDITION OF A PORCH OR DECK, ARE EXEMPT FROM THE
 REQUIREMENTS OF THIS SECTION.
 2.INSTALLATION, ALTERATION OR REPAIRS OF PLUMBING OR
 MECHANICAL SYSTEMS ARE EXEMPT FROM THE REQUIREMENTS OF
 THIS SECTION.
  
 R314.4 INTERCONNECTION.
 WHERE MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE
 INSTALLED WITHIN AN INDIVIDUAL DWELLING UNIT IN
 ACCORDANCE WITH SECTION R314.3, THE ALARM DEVICES SHALL
 BE INTERCONNECTED IN SUCH A MANNER THAT THE ACTUATION
 OF ONE ALARM WILL ACTIVATE ALL OF THE ALARMS IN THE
 INDIVIDUAL DWELLING UNIT. PHYSICAL INTERCONNECTION OF
 SMOKE ALARMS SHALL NOT BE REQUIRED WHERE LISTED
 WIRELESS ALARMS ARE INSTALLED AND ALL ALARMS SOUND UPON
 ACTIVATION OF ONE ALARM.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-06-12 Cont ID  
Sent By fmittner Date 2019-06-12 Time 11:37 Rev Time 0.00
Received By fmittner Date 2019-06-12 Time 11:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-21 Cont ID  
Sent By cthroop Date 2019-08-21 Time 10:08 Rev Time 0.00
Received By cthroop Date 2019-08-21 Time 10:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-25 Cont ID  
Sent By cthroop Date 2019-06-25 Time 14:20 Rev Time 0.00
Received By cthroop Date 2019-05-30 Time 14:27 Sent To  
Notes
2019-05-31 14:27:16R04

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-08-26 Cont ID  
Sent By cthroop Date 2019-08-26 Time 10:07 Rev Time 0.00
Received By cthroop Date 2019-08-26 Time 10:07 Sent To  
Notes
2019-08-26 10:08:29MU-2019-26613-0000. CT

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-08-21 Cont ID  
Sent By cthroop Date 2019-06-25 Time 13:15 Rev Time 0.00
Received By cthroop Date 2019-06-24 Time 15:51 Sent To  
Notes
2019-06-25 13:15:55PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-08-21 Cont ID  
Sent By cthroop Date 2019-08-21 Time 10:08 Rev Time 0.00
Received By cthroop Date 2019-08-21 Time 10:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-06-25 Cont ID  
Sent By cthroop Date 2019-06-25 Time 13:43 Rev Time 0.00
Received By cthroop Date 2019-06-24 Time 15:51 Sent To  
Notes
2019-06-25 13:56:10MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THERE IS NO RECORD OF THE 10X12 A/C VENT BEING
 PERMITTED. SHOW AS PROPOSED AND INCLUDE IN ENERGY
 CALCULATIONS FOR SYSTEM SIZING.
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES.
  
 2. PROVIDE MECHANICAL RISER DIAGRAHM. INCLUDE THE
 PROPOSED 10X12 VENT AND REQUIRED RETURN AIR VENT.
 FBC E R403.7.1EQUIPMENT SIZING.
 HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN
 ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR
 OTHER APPROVED HEATING AND COOLING CALCULATION
 METHODOLOGIES, BASED ON BUILDING LOADS FOR THE
 DIRECTIONAL ORIENTATION OF THE BUILDING. THE
 MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR
 UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH
 THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN
 CONDITIONS DESCRIBED IN SECTION R302.1
  
 3. NOTE ON PLAN STATES SYSTEM IS A 4 TON UNIT. PROVIDE
 MAKE AND MODEL NUMBER OF AHU & CU.
 M1202.1ADDITIONS, ALTERATIONS OR REPAIRS.
 ADDITIONS, ALTERATIONS, RENOVATIONS OR REPAIRS TO A
 MECHANICAL SYSTEM SHALL CONFORM TO THE REQUIREMENTS FOR
 A NEW MECHANICAL SYSTEM WITHOUT REQUIRING THE EXISTING
 MECHANICAL SYSTEM TO COMPLY WITH ALL OF THE
 REQUIREMENTS OF THIS CODE. ADDITIONS, ALTERATIONS OR
 REPAIRS SHALL NOT CAUSE AN EXISTING MECHANICAL SYSTEM
 TO BECOME UNSAFE, HAZARDOUS OR OVERLOADED. MINOR
 ADDITIONS, ALTERATIONS OR REPAIRS TO EXISTING
 MECHANICAL SYSTEMS SHALL MEET THE PROVISIONS FOR NEW
 CONSTRUCTION, UNLESS SUCH WORK IS DONE IN THE SAME
 MANNER AND ARRANGEMENT AS WAS IN THE EXISTING SYSTEM,
 IS NOT HAZARDOUS, AND IS APPROVED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2019-06-12 Cont ID  
Sent By awooten Date 2019-06-12 Time 11:37 Rev Time 0.00
Received By fmittner Date 2019-06-12 Time 11:37 Sent To  
Notes
***NONE***