Plan Review Details - Permit 19051286
Plan Review Stops For Permit 19051286
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-07-30 Cont ID  
Sent By pvalenti Date 2019-07-30 Time 15:24 Rev Time 0.00
Received By shill Date 2019-07-30 Time 15:24 Sent To  
Notes
2019-07-30 15:25:06PROVISO: DOOR PRODUCT APPROVAL TO BE SUBMITTED,
 REVIEWED AND ISSUED PRIOR TO INSTALLATION
 PANIC BARS REQUIRED
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-07-22 Cont ID  
Sent By shill Date 2019-07-22 Time 12:06 Rev Time 0.00
Received By shill Date 2019-07-22 Time 12:06 Sent To  
Notes
2019-07-22 12:07:02****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 COMMENT FROM PREVIOUS LIST:
  
 3. THE DOOR PRODUCT APPROVAL WAS PROVIDED, BUT I WAS
 UNABLE TO LOCATE AN OPTION FOR A PANIC BAR/FIRE EXIT
 HARDWARE IN THE PRODUCT APPROVAL. EITHER CIRCLE ON THE
 PRODUCT APPROVAL OR PROVIDE A NEW ONE WHICH INCLUDES
 THIS OPTION.
  
 FBC 107, PRODUCT APPROVAL IS TO BE REVIEWED BY DESIGNER
 OF RECORD.
  
 OWNER WAS EMAILED; UPON REQUEST THIS CAN BE A DEFERRED
 SUBMITTAL.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-07-03 Cont ID  
Sent By shill Date 2019-07-03 Time 16:55 Rev Time 0.00
Received By shill Date 2019-07-03 Time 16:55 Sent To  
Notes
2019-07-03 17:01:11****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC B 1609, SEE PREVIOUS LIST, I WAS UNABLE TO
 LOCATE WIND DESIGN CRITERIA (WIND SPEED, EXPOSURE,
 DESIGN PRESSURES).
  
 2. OK
  
 3. THE DOOR PRODUCT APPROVAL WAS PROVIDED, BUT I WAS
 UNABLE TO LOCATE AN OPTION FOR A PANIC BAR/FIRE EXIT
 HARDWARE IN THE PRODUCT APPROVAL. EITHER CIRCLE ON THE
 PRODUCT APPROVAL OR PROVIDE A NEW ONE WHICH INCLUDES
 THIS OPTION.
  
 FBC 107, PRODUCT APPROVAL IS TO BE REVIEWED BY DESIGNER
 OF RECORD.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-05 Cont ID  
Sent By shill Date 2019-06-05 Time 17:25 Rev Time 0.00
Received By shill Date 2019-06-05 Time 17:25 Sent To  
Notes
2019-06-05 17:26:08****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC B 1609, SHEETS M503, PROVIDE A STRUCTURAL DETAIL
 FOR THE NEW DOOR OPENING. IF SHEET M503 IS ELIMINATED
 AND THE STRUCTURAL PAGE IS REVISED TO INCLUDE THE DOOR
 DETAIL, PLEASE SPECIFY PANIC BAR AS SHOWN ON M503.
  
 THE DETAIL PROVIDED LACKS WIND DESIGN CRITERIA, LINTEL
 SPEC (ONLY STATES "PAINTED STEEL LINTEL"), LINTEL
 INSTALLATION SPECIFICS, DOES NOT SHOW FILLED CELLS ON
 EITHER SIDE OF THE NEW DOOR, ETC.
  
 2. FBC 107, REVISE PLAN TO SHOW LOCATION OF NEW DOOR.
  
 3. FBC B 1609, PROVIDE DOOR PRODUCT APPROVAL REVIEWED
 BY DESIGNER OF RECORD.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-07-22 Cont ID  
Sent By jleahy Date 2019-07-22 Time 08:29 Rev Time 0.00
Received By jleahy Date 2019-07-19 Time 13:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-07-03 Cont ID  
Sent By jleahy Date 2019-07-03 Time 15:55 Rev Time 0.00
Received By jleahy Date 2019-07-03 Time 15:55 Sent To  
Notes
2019-07-03 16:15:40FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE FOR THE WORK SHOWN IS TOO LOW.
  
 1A) PLEASE INDICATE ALL EQUIPMENT AND VALUE THAT IS
 SUPPLIED BY THE OWNER
 UPS, BATTERY, AC, BUSS DUCT ECT. ECT.
 VALUES SENT IN EMAIL NOT REALISTIC FOR EQUIPMENT SHOWN
  
 1B) PLEASE INDICATE VALUE FOR EACH PCS. OF EQUIPMENT
 SUPPLIED BY OWNER AND CUT SHEETS TO GO WITH EQUIPMENT
 SO WE CAN UNDERSTAND WHAT IS WHAT.
  
 2) NEED TO SUBMIT CUT SHEETS AND INDICATE WHICH MODEL
 YOU ARE USING. BUSS DUCT, BATTERIES, AC, UPS, SWITCH
 GEAR, CABLES DLO
  
 3) RISER DIAGRAM PLEASE INDICATE WHICH IS EXISTING WORK
 AND WHICH IS NEW WORK.
  
 4) HOW MANY MAINS ARE IN THE BUILDING 3000A LOOKS TO BE
 NEW. WHAT IS THE EXISTING SIZE AND HOW AMNY MAINS ARE
 THERE IN BUILDING????????
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE
 A RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED
 PAGES INTO THE ORIGINAL SUBMITTAL AND REMOVE
 OR VOID THE PREVIOUSLY REVIEWED SHEETS.
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-06-05 Cont ID  
Sent By jleahy Date 2019-06-05 Time 16:02 Rev Time 0.00
Received By jleahy Date 2019-06-05 Time 16:02 Sent To  
Notes
2019-06-05 16:16:18FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 VALUE OF THE WORK SHALL INCLUDE ALL CUSTOMER SUPPLIED
 MATERIALS
  
 SUBMIT CUTSHEETS FOR ALL NEW EQUIPMENT MSB, UPS ECT,
 ECT.
  
 LOAD CALCULATIONS FOR THE NEW SWITCH GEAR(SUPPLIED BY
 OWNER)
  
 LOAD CALCULATION FOR UPS SYSTEM

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-07-30 Cont ID  
Sent By shill Date 2019-07-30 Time 15:25 Rev Time 0.00
Received By shill Date 2019-07-26 Time 14:41 Sent To  
Notes
2019-07-30 14:41:49RESUB ROUTED TO HMOSER

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-07-23 Cont ID  
Sent By hmoser Date 2019-07-23 Time 10:05 Rev Time 0.00
Received By hmoser Date 2019-07-16 Time 15:13 Sent To  
Notes
2019-07-22 12:08:217/22 TO HM DESK
  
2019-07-19 13:37:317/19 TO JL DESK
  
2019-07-17 09:56:007/17 TO CC DESK
  
  
2019-07-16 15:14:09TO AV DESK
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-03 Cont ID  
Sent By shill Date 2019-07-03 Time 17:01 Rev Time 0.00
Received By shill Date 2019-06-26 Time 16:23 Sent To  
Notes
2019-06-27 16:23:44RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-05 Cont ID  
Sent By shill Date 2019-06-05 Time 17:26 Rev Time 0.00
Received By shill Date 2019-05-24 Time 15:11 Sent To  
Notes
2019-05-28 15:11:54ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2019-07-24 Cont ID  
Sent By hmoser Date 2019-07-24 Time 08:41 Rev Time 0.00
Received By hmoser Date 2019-07-24 Time 08:41 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-07-23 Cont ID  
Sent By hmoser Date 2019-07-23 Time 10:02 Rev Time 0.00
Received By hmoser Date 2019-07-22 Time 15:15 Sent To B
Notes
2019-07-23 10:02:43PLAN DENIED
 1) PROVIDE MANUFACTURERS SPECIFICATIONS ON THE BATTERY
 CABINETS FURNISHED BY THE PROPERTY OWNER.
 PER SECTION 107 FBC 2014
 2) PROVIDE A CLEAR APPENDIX CAN NOT READ THE
 VENTILATION
 CALCULATIONS PROVIDE ON THE BACK OF THE LETTER. TWO
 REQUIRED.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-07-01 Cont ID  
Sent By ccole Date 2019-07-01 Time 11:53 Rev Time 0.00
Received By ccole Date 2019-07-01 Time 11:40 Sent To  
Notes
2019-07-01 12:05:202ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19051286
 7/1/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) EXHAUST VENTILATION IS REQUIRED FOR THE UPS SYSTEM,
 HOWEVER DETERMINING HOW THE SYSTEM WILL BE VENTILATED
 IS DEPENDENT ON SUBMITTAL OF MSDS SHEETS FOR THE
 BATTERIES, AND CLARIFICATION OF HOW THE BATTERIES ARE
 BEING STORED, AND BATTERY QUANTITIES- SEE FBC M CODE
 SECTIONS BELOW.
  
 502.4 STATIONARY STORAGE BATTERY SYSTEMS.
 STATIONARY STORAGE BATTERY SYSTEMS, AS REGULATED BY THE
 FLORIDA FIRE PREVENTION CODE, SHALL BE PROVIDED WITH
 VENTILATION IN ACCORDANCE WITH THIS CHAPTER AND SECTION
 502.4.1 OR 502.4.2.
 EXCEPTION: LITHIUM-ION AND LITHIUM METAL POLYMER
 BATTERIES SHALL NOT REQUIRE ADDITIONAL VENTILATION
 BEYOND THAT WHICH WOULD NORMALLY BE REQUIRED FOR HUMAN
 OCCUPANCY OF THE SPACE.
  
 502.4.1 HYDROGEN LIMIT IN ROOMS.
 FOR FLOODED LEAD ACID, FLOODED NICKEL CADMIUM AND VRLA
 BATTERIES, THE VENTILATION SYSTEM SHALL BE DESIGNED TO
 LIMIT THE MAXIMUM CONCENTRATION OF HYDROGEN TO 1.0
 PERCENT OF THE TOTAL VOLUME OF THE ROOM.
  
 502.4.2 VENTILATION RATE IN ROOMS.
 CONTINUOUS VENTILATION SHALL BE PROVIDED AT A RATE OF
 NOT LESS THAN 1 CUBIC FOOT PER MINUTE PER SQUARE FOOT
 (CFM/FT2) OF FLOOR AREA OF THE ROOM.
  
 502.4.3 SUPERVISION.
 MECHANICAL VENTILATION SYSTEMS REQUIRED BY SECTION
 502.4 SHALL BE SUPERVISED BY AN APPROVED CENTRAL,
 PROPRIETARY OR REMOTE STATION SERVICE OR SHALL INITIATE
 AN AUDIBLE AND VISUAL SIGNAL AT A CONSTANTLY ATTENDED
 ON-SITE LOCATION.
  
 502.5 VALVE-REGULATED LEAD-ACID BATTERIES IN CABINETS.
 VALVE-REGULATED LEAD-ACID (VRLA) BATTERIES INSTALLED IN
 CABINETS, AS REGULATED BY THE FLORIDA FIRE PREVENTION
 CODE, SHALL BE PROVIDED WITH VENTILATION IN ACCORDANCE
 WITH SECTION 502.5.1 OR 502.5.2.
  
 502.5.1 HYDROGEN LIMIT IN CABINETS.
 THE CABINET VENTILATION SYSTEM SHALL BE DESIGNED TO
 LIMIT THE MAXIMUM CONCENTRATION OF HYDROGEN TO 1.0
 PERCENT OF THE TOTAL VOLUME OF THE CABINET DURING THE
 WORST-CASE EVENT OF SIMULTANEOUS BOOST CHARGING OF ALL
 BATTERIES IN THE CABINET.
  
 502.5.2 VENTILATION RATE IN CABINETS.
 CONTINUOUS CABINET VENTILATION SHALL BE PROVIDED AT A
 RATE OF NOT LESS THAN 1 CUBIC FOOT PER MINUTE PER
 SQUARE FOOT (CFM/FT2) OF THE FLOOR AREA COVERED BY THE
 CABINET. THE ROOM IN WHICH THE CABINET IS INSTALLED
 SHALL BE VENTILATED AS REQUIRED BY SECTION 502.4.1 OR
 502.4.2.
  
 502.5.3 SUPERVISION.
 MECHANICAL VENTILATION SYSTEMS REQUIRED BY SECTION
 502.5 SHALL BE SUPERVISED BY AN APPROVED CENTRAL,
 PROPRIETARY OR REMOTE STATION SERVICE OR SHALL INITIATE
 AN AUDIBLE AND VISUAL SIGNAL AT A CONSTANTLY ATTENDED
 ON-SITE LOCATION.
  
 2) PROVIDE THE FOLLOWING INFORMATION FOR THE UPS
 SYSTEMS AS OUTLINED IN SECTION 414.1.3 FBC B. PLEASE
 NOTE THAT THE WALLS ENCLOSING THE UPS ROOM MAY HAVE TO
 BE FIRE-RATED.
  
 414.1.3 INFORMATION REQUIRED.
 A REPORT SHALL BE SUBMITTED TO THE BUILDING OFFICIAL
 IDENTIFYING THE MAXIMUM EXPECTED QUANTITIES OF
 HAZARDOUS MATERIALS TO BE STORED, USED IN A CLOSED
 SYSTEM AND USED IN AN OPEN SYSTEM, AND SUBDIVIDED TO
 SEPARATELY ADDRESS HAZARDOUS MATERIAL CLASSIFICATION
 CATEGORIES BASED ON TABLES 307.1(1) AND 307.1(2). THE
 METHODS OF PROTECTION FROM SUCH HAZARDS, INCLUDING BUT
 NOT LIMITED TO CONTROL AREAS, FIRE PROTECTION SYSTEMS
 AND GROUP H OCCUPANCIES SHALL BE INDICATED IN THE
 REPORT AND ON THE CONSTRUCTION DOCUMENTS. THE OPINION
 AND REPORT SHALL BE PREPARED BY A QUALIFIED PERSON,
 FIRM OR CORPORATION APPROVED BY THE BUILDING OFFICIAL
 AND PROVIDED WITHOUT CHARGE TO THE ENFORCING AGENCY.
  
 3) REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES INVOLVED IN THE PROPSED ALTERATION PER
 TABLE 403.3.1.1 FBC-17 MECHANICAL. PROVIDE A SCHEDULE
 THAT INDICATES THE REQUIRED AND PROVIDED CFMS OF
 OUTDOOR AIR.
  
 4) THE NOTES ON THE PLANS INDICATE THE EQUIPMENT-
 CHILLERS, IRC'S, CDU'S, AND UPS BATTERY SYSTEMS ARE
 OWNER SUPPLIED, HOWEVER TOTAL VALUE FOR PERMITTING IS
 BASED ON ALL LABOR, MATERIAL, EQUIPMENT, DESIGN FEES,
 PROFIT SAND OVERHEAD. PLEASE REFER TO SECTION 109.3 WPB
 AND PROVIDE BONA-FIDE CONTRACTS, INVOICES, AND
 ESTIMATES TO VERIFY THE TOTAL COST OF THE PROJECT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By hmoser Date 2019-05-29 Time 09:09 Sent To E
Notes
2019-05-29 15:16:51PLAN DENIED
 PAGE M-101 NOTE 13 CONDENSATE CAN NOT DRAIN
 INTO FLOOR DRAIN PER CHAPTER 9 ARTICLE 3 SECTION 9-126
 CITY ORDINANCES
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop Z ZONING
Rev No 1 Status P Date 2019-07-19 Cont ID  
Sent By ajones Date 2019-07-19 Time 11:50 Rev Time 0.00
Received By ajones Date 2019-07-19 Time 11:50 Sent To PC
Notes
2019-07-19 11:51:397/19/19- SEPERATE LANDSCAPE PERMIT REQUIRED.
  
 ANGELLA VANN
 [email protected]
 561-822-1441