Plan Review Details - Permit 19051279
Plan Review Stops For Permit 19051279 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2019-05-29 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2019-05-29 |
Time |
07:24 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2019-05-29 |
Time |
06:40 |
Sent To |
Z |
|
Notes |
2019-05-29 06:46:02 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. DEFINE REASONING FOR PROPOSED ADDITION OF NEW METER? | | STRUCTURE IN BACK WILL NEED TO BE EVALUATED FOR CHANGE | | OF OCCUPANCY. MECHANICAL REVIEW, STRUCTURAL REVIEW, | | PLUMBING REVIEW, ELECTRICAL REVIEW, AND ZONING REVIEWS | | REQUIRED. FBC 107.2.1 FBC 105.1 | | | | FLOOR PLAN AND PICTURES WILL BE REQUIRED WITH | | RESUBMISSION. | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-657-1653 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2019-05-30 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2019-05-30 |
Time |
18:56 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2019-05-24 |
Time |
13:23 |
Sent To |
PC |
|
Notes |
2019-05-28 13:24:01 | ELEC <5K |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2019-05-30 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2019-05-30 |
Time |
18:56 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2019-05-30 |
Time |
18:47 |
Sent To |
PC |
|
Notes |
2019-05-30 18:56:18 | ZONING REVIEW FAILED, DUE TO THE FOLLOWING: | | | | 1) PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH | | INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION. | | 2) INDICATE ON THE SURVEY THE LOLCATION OF THE 2ND | | METER. | | 3) WHAT IS THE PURPOSE OF THE 2ND METER? BASED ON THE | | ZONING DISTRICT OF MULTI-FAMILY 20 (MF20), A 2ND UNIT | | MAY BE PERMITTED PROVIDED THAT YOU MEET MINIMUM | | DEVELOPMENT REGULATION REGULATIONS. PLEASE CONTACT ME | | OR A PLANNER ON CALL FOR FUTHER INFORMATION. | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | PLANNING DEPARTMENT WEBSITE AT | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | CONTACT ME. IF YOU WANT TO MEET IN PERSON TO GO OVER | | THE ABOVE COMMENTS, PLEASE CALL OR E-MAIL ME TO | | SCHEDULE AN APPOINTMENT. | | | | MAGGIE CRUZ | | ASSOCIATE PLANNER | | PLANNING AND ZONING DEPARTMENT | | TEL: 561-822-1442 | | E-MAIL: [email protected] |
|
|
|