Plan Review Details - Permit 19051010
Plan Review Stops For Permit 19051010
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-05-23 Cont ID  
Sent By pvalenti Date 2019-05-23 Time 17:37 Rev Time 0.00
Received By pvalenti Date 2019-05-23 Time 17:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-06-06 Cont ID  
Sent By jpearson Date 2019-06-06 Time 06:33 Rev Time 0.00
Received By jpearson Date 2019-06-06 Time 06:33 Sent To  
Notes
2019-06-06 06:36:39ELECTRICAL PERMIT APP RECEIVED BY EMAIL.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-27 Cont ID  
Sent By jpearson Date 2019-05-27 Time 10:49 Rev Time 0.00
Received By jpearson Date 2019-05-27 Time 10:49 Sent To I
Notes
2019-05-27 10:49:27CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN REVIEW NEEDS AN ELECTRICAL PERMIT
 APPLICATION FROM AN ELECTRICAL CONTRACTOR FOR APPROVAL.
 PLEASE EMAIL THE ELECTRICAL PERMIT APPLICATION TO
 [email protected] AND CC [email protected] AND
 [email protected] SO WE RECEIVE IT ALSO. WHEN THIS EMAIL
 IS RECEIVED ONE OF THE REVIEWERS WILL APPROVE THE PLAN
 REVIEW. THE ORIGINAL PERMIT APPLICATION MUST BE
 SUBMITTED WHEN THE PERMIT IS PICKED UP. WPB FBC 105.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-05-24 Cont ID  
Sent By pleduc Date 2019-05-24 Time   Rev Time 0.00
Received By pleduc Date 2019-05-24 Time 15:00 Sent To E
Notes
2019-05-24 15:02:155/24/19
  
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS AND BY CERTIFIED CONTRACTORS.
  
  
 2) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE DEMO AND
 CONSTRUCTION PERIOD.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-05-27 Time   Rev Time 0.00
Received By lmarchan Date 2019-05-21 Time 14:24 Sent To  
Notes
2019-05-22 14:24:46ROUTED TO SHILL