Plan Review Details - Permit 19050988
Plan Review Stops For Permit 19050988
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-08-16 Cont ID  
Sent By cthroop Date 2019-08-16 Time 08:36 Rev Time 0.00
Received By cthroop Date 2019-08-16 Time 08:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-08-14 Cont ID  
Sent By cthroop Date 2019-08-14 Time 16:01 Rev Time 0.00
Received By cthroop Date 2019-08-14 Time 16:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-08-12 Cont ID  
Sent By cthroop Date 2019-08-12 Time 14:49 Rev Time 0.00
Received By cthroop Date 2019-08-09 Time 07:55 Sent To  
Notes
2019-08-12 14:53:41BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED. I
 HAVE INCLUDED THEM BELOW FOR YOUR REBIEW.
  
  
 ADDRESS: 5009 S FLAGLER PERMIT # 19050988
 TYPE: BLD-RES NEW SFR
  
 BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 1. PROVIDE SOILS REPORT REVIEWED AND APPROVED BY
 DESIGNER OF RECORD.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. SEPERATE GAS PERMIT IS REQUIRED.
 PERMITS
 105.1 REQUIRED.
  
 3. DESIGNER TO SELECT ICYNENE PRODUCT FROM PAGE 7 OF 8
 OF THE PRODUCT APPROVAL TO BE INSTALLED. INSTALLATION
 INSTRUCTIONS SHALL BE ON-SITE AT TIME OF APPLICATION.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE INSULATION SUBMITTALS.
  
 4. PRODUCT APPROVALS AND NOA'S SUBMITTED FOR REVIEW DO
 NOT MATCH THOSE ITEMS LISTED ON THE NOA COVER PAGE.
 THERE ARE MULTIPLE COPIES OF THE NOA COVER PAGE
 INCLUDED IN SUBMITTAL. REMOVE THOSE THAT DO NOT APPLY
 TO THIS PROJECT.
 ALL PRODUCT APPROVALS AND NOA'S SHALL BE REVIEWED AND
 APPROVED IN WRITING BY DESIGNER.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 NEW COMMENT:
  
 1. DESIGNER SHALL REVIEW AND APPROVE ALL PRODUCT
 APPROVALS. PLEASE INDICATE WHICH MODEL OR SYSTEM SHALL
 BE INSTALLED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-17 Cont ID  
Sent By cthroop Date 2019-07-17 Time 10:45 Rev Time 0.00
Received By cthroop Date 2019-07-01 Time 10:23 Sent To  
Notes
2019-07-17 10:54:08ADDRESS: 5009 S FLAGLER PERMIT # 19050988
 TYPE: BLD-RES NEW SFR
  
 BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 1. PROVIDE SOILS REPORT REVIEWED AND APPROVED BY
 DESIGNER OF RECORD.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. SEPERATE GAS PERMIT IS REQUIRED.
 PERMITS
 105.1 REQUIRED.
  
 3. DESIGNER TO SELECT ICYNENE PRODUCT FROM PAGE 7 OF 8
 OF THE PRODUCT APPROVAL TO BE INSTALLED. INSTALLATION
 INSTRUCTIONS SHALL BE ON-SITE AT TIME OF APPLICATION.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE INSULATION SUBMITTALS.
  
 4. PRODUCT APPROVALS AND NOA'S SUBMITTED FOR REVIEW DO
 NOT MATCH THOSE ITEMS LISTED ON THE NOA COVER PAGE.
 THERE ARE MULTIPLE COPIES OF THE NOA COVER PAGE
 INCLUDED IN SUBMITTAL. REMOVE THOSE THAT DO NOT APPLY
 TO THIS PROJECT.
 ALL PRODUCT APPROVALS AND NOA'S SHALL BE REVIEWED AND
 APPROVED IN WRITING BY DESIGNER.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-08-14 Cont ID  
Sent By cthroop Date 2019-08-14 Time 16:02 Rev Time 0.00
Received By cthroop Date 2019-08-14 Time 16:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-08-12 Cont ID  
Sent By cthroop Date 2019-08-12 Time 14:56 Rev Time 0.00
Received By cthroop Date 2019-08-09 Time 07:55 Sent To  
Notes
2019-08-12 14:59:29ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 ITEMS 2 & 3 FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED. I
 HAVE INCLUDED THEM MBELOW FOR YOUR REVIEW.
  
  
 2. LIGHTING IN CLOSETS IS SHOWN AS A 3 INCH LED
 FIXTURE. PER CODE, LIGHTING WITH OPEN OR PARTIALLY
 ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS
 SHALL NOT BE PERMITTED IN CLOTHES CLOSETS. PROVIDE
 CLARIFICATION AND/OR CORRECTION. NEC 410.16; FBC RE
 E4003.12
 3. HIS AND HER CLOSET SHOW A CHANDELIER FIXTURE IN THE
 CLOSET. PER CODE, LIGHTING WITH OPEN OR PARTIALLY
 ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS
 SHALL NOT BE PERMITTED IN CLOTHES CLOSETS. PROVIDE
 CORRECTION. NEC 410.16; FBC RE E4003.12
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-07-17 Cont ID  
Sent By jpearson Date 2019-07-17 Time 09:58 Rev Time 0.00
Received By jpearson Date 2019-07-17 Time 08:29 Sent To  
Notes
2019-07-17 08:58:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ALL RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS
 SHALL HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8(A)(9); FBC RE E3902.9
 2. LIGHTING IN CLOSETS IS SHOWN AS A 3 INCH LED
 FIXTURE. PER CODE, LIGHTING WITH OPEN OR PARTIALLY
 ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS
 SHALL NOT BE PERMITTED IN CLOTHES CLOSETS. PROVIDE
 CLARIFICATION AND/OR CORRECTION. NEC 410.16; FBC RE
 E4003.12
 3. HIS AND HER CLOSET SHOW A CHANDELIER FIXTURE IN THE
 CLOSET. PER CODE, LIGHTING WITH OPEN OR PARTIALLY
 ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS
 SHALL NOT BE PERMITTED IN CLOTHES CLOSETS. PROVIDE
 CORRECTION. NEC 410.16; FBC RE E4003.12
 4. HER BATH SHOWS A CHANDELIER APPROXIMATELY 12 INCHES
 FROM THE EDGE OF THE TUB. NO PARTS OF CORD-CONNECTED
 LUMINAIRES, CHAIN-, CABLE-, OR CORD-SUSPENDED
 LUMINAIRES, LIGHTING TRACK, PENDANTS, OR
 CEILING-SUSPENDED (PADDLE) FANS SHALL BE LOCATED WITHIN
 A ZONE MEASURED 3 FEET HORIZONTALLY AND 8 FEET
 VERTICALLY FROM THE TOP OF THE BATHTUB RIM OR SHOWER
 STALL THRESHOLD. PROVIDE CORRECTION. NEC 410.10(D); FBC
 RE E4003.11
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2019-08-12 Cont ID  
Sent By cthroop Date 2019-08-12 Time 15:00 Rev Time 0.00
Received By cthroop Date 2019-08-09 Time 07:55 Sent To  
Notes
2019-08-12 15:01:24GAS SHALL BE BY SEPERATE PERMIT.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-07-18 Cont ID  
Sent By cthroop Date 2019-07-18 Time 10:54 Rev Time 0.00
Received By cthroop Date 2019-07-17 Time 10:39 Sent To  
Notes
2019-07-18 10:56:15GAS PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE GAS REGULATOR SPECIFICATIONS.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-08-20 Cont ID  
Sent By cpuell Date 2019-08-20 Time 06:08 Rev Time 0.00
Received By cpuell Date 2019-08-15 Time 12:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-08-14 Cont ID  
Sent By lmarchan Date 2019-08-14 Time 16:18 Rev Time 0.00
Received By lmarchan Date 2019-08-13 Time 06:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-13 Cont ID  
Sent By lmarchan Date 2019-08-13 Time 13:47 Rev Time 0.00
Received By lmarchan Date 2019-07-29 Time 16:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-18 Cont ID  
Sent By cthroop Date 2019-07-18 Time 11:27 Rev Time 0.00
Received By cthroop Date 2019-06-17 Time 15:38 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-08-21 Cont ID  
Sent By lmarchan Date 2019-08-21 Time 16:18 Rev Time 0.00
Received By lmarchan Date 2019-08-13 Time 10:52 Sent To  
Notes
2019-08-15 16:06:38RECEIPT MU-2019-0815-44 - $22.46 PAID
2019-08-13 10:52:208/13/19 EMAILED IMPACT FEE OFFICE. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-07-12 Cont ID  
Sent By cthroop Date 2019-07-12 Time 11:17 Rev Time 0.00
Received By cthroop Date 2019-07-01 Time 10:23 Sent To  
Notes
2019-07-12 11:17:46PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-08-12 Cont ID  
Sent By cthroop Date 2019-08-12 Time 14:55 Rev Time 0.00
Received By cthroop Date 2019-08-09 Time 07:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-07-17 Cont ID  
Sent By cthroop Date 2019-07-17 Time 15:04 Rev Time 0.00
Received By cthroop Date 2019-07-01 Time 10:23 Sent To  
Notes
2019-07-17 15:13:19MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. OWNER/AGENT SHALL SIGN ENERGY SUBMITTAL.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
  
 2. BUILDER TO SIGN EPL CARD.
  
 3. PROVIDE TIE DOWN DETAIL FOR CU'S
 FBC 107.3.5.3 ? PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
 4. PROVIDE DETAIL FOR CONDENSATE DRAINS OF ALL AIR
 HANDLERS.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 4 Status P Date 2019-08-16 Cont ID  
Sent By cthroop Date 2019-08-16 Time 08:36 Rev Time 0.00
Received By cthroop Date 2019-08-16 Time 08:33 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status F Date 2019-08-14 Cont ID  
Sent By cthroop Date 2019-08-14 Time 16:02 Rev Time 0.00
Received By cthroop Date 2019-08-14 Time 16:01 Sent To  
Notes
2019-08-14 16:04:32NFIP REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SECTION C2 (E) SHOULD BE AT DFE OF 9.5 FEET NAVD.
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2019-08-12 Cont ID  
Sent By cthroop Date 2019-08-12 Time 15:04 Rev Time 0.00
Received By cthroop Date 2019-08-09 Time 07:55 Sent To  
Notes
2019-08-12 15:06:47BUILDING PLAN REVIEW - NFIP
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED. I
 HAVE INCLUDED THEM BELOW FOR YOUR REVIEW.
  
 BUILDING PLAN REVIEW - NFIP
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NFIP REVIEW
 CITY OF WEST PALM BEACH ORDINANCE NO. 4658-16
  
 1. BASED ON THE SUBMITTED SURVEY, THIS LOT AND PROPOSED
 IMPROVEMENTS ARE LOCATED IN AN AE FLOOD ZONE WITH A
 BASE FLOOD ELEVATION (BFE) OF 7.0 FEET NAVD.
 2. AS OF OCTOBER 5, 2017, THE FEDERAL EMERGENCY
 MANAGEMENT AGENCY (FEMA) ESTABLISHED A NEW FLOOD
 INSURANCE RATE MAP (FIRM) UTILIZING THE RECENTLY
 COMPLETED FLOOD HAZARD DETERMINATION (FHD) FOR THE CITY
 OF WEST PALM BEACH, FL.
 3. ALL NEW BASE FLOOD ELEVATIONS (BFE) SHALL BE BASED
 ON NAVD88 DATUM. ON AUGUST 23, 2017, THE CITY OF WEST
 PALM BEACH, BY ORDINANCE, ESTABLISHED A TWO FOOT
 FREEBOARD ABOVE THE (BFE).
 4. YOU MAY SUBMIT A SURVEY SHOWING ALL EXISTING AND
 PROPOSED ELEVATIONS BASED ON NAVD88 DATUM PLUS TWO FEET
 OF FREEBOARD OR THE ENGINEER OF RECORD (EOR) MAY ADD A
 STATEMENT TO THE STRUCTURAL PLAN THAT THE DESIGN FLOOD
 ELEVATION (DFE) WILL BE 9.4 FEET NAVD88 BASED ON THE
 (BFE) OF 7.00 FEET FOR FLOOD ZONE AE PLUS A CORRECTION
 FACTOR OF .4 FEET PLUS TWO FEET OF FREEBOARD.
  
 A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS
 REQUIRED AT TIME OF PERMIT APPLICATION.
 NOTE: ALL EQUIPMENT SERVICING THE BUILDINGS ON THIS
 SITE ARE REQUIRED TO BE AT OR ABOVE 9 FEET 4 INCHES
 NAVD.
  
 AN UNDER CONSTRUCTION (FORMBOARD) SURVEY WITH FINISHED
 FLOOR ELEVATION IS REQUIRED.
  
 A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
 THIS EC MAY BE SUBMITTED FOR REVIEW PRIOR TO BUILDING
 FINAL.
  
 GARAGE - VENTS
  
 G1001.4 ENCLOSURES BELOW DESIGN FLOOD ELEVATION.
 FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD ELEVATION
 SHALL BE AT OR ABOVE GRADE ON ALL SIDES AND CONFORM TO
 THE FOLLOWING:
  
 1. IN FLOOD HAZARD AREAS NOT SUBJECT TO HIGH-VELOCITY
 WAVE ACTION, ENCLOSED AREAS SHALL HAVE FLOOD OPENINGS
 TO ALLOW FOR THE AUTOMATIC INFLOW AND OUTFLOW OF
 FLOODWATERS.
  
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2019-07-12 Cont ID  
Sent By cthroop Date 2019-07-12 Time 11:54 Rev Time 0.00
Received By cthroop Date 2019-07-01 Time 10:26 Sent To  
Notes
2019-07-12 12:00:38BUILDING PLAN REVIEW - NFIP
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NFIP REVIEW
 CITY OF WEST PALM BEACH ORDINANCE NO. 4658-16
  
 1. BASED ON THE SUBMITTED SURVEY, THIS LOT AND PROPOSED
 IMPROVEMENTS ARE LOCATED IN AN AE FLOOD ZONE WITH A
 BASE FLOOD ELEVATION (BFE) OF 7.0 FEET NAVD.
 2. AS OF OCTOBER 5, 2017, THE FEDERAL EMERGENCY
 MANAGEMENT AGENCY (FEMA) ESTABLISHED A NEW FLOOD
 INSURANCE RATE MAP (FIRM) UTILIZING THE RECENTLY
 COMPLETED FLOOD HAZARD DETERMINATION (FHD) FOR THE CITY
 OF WEST PALM BEACH, FL.
 3. ALL NEW BASE FLOOD ELEVATIONS (BFE) SHALL BE BASED
 ON NAVD88 DATUM. ON AUGUST 23, 2017, THE CITY OF WEST
 PALM BEACH, BY ORDINANCE, ESTABLISHED A TWO FOOT
 FREEBOARD ABOVE THE (BFE).
 4. YOU MAY SUBMIT A SURVEY SHOWING ALL EXISTING AND
 PROPOSED ELEVATIONS BASED ON NAVD88 DATUM PLUS TWO FEET
 OF FREEBOARD OR THE ENGINEER OF RECORD (EOR) MAY ADD A
 STATEMENT TO THE STRUCTURAL PLAN THAT THE DESIGN FLOOD
 ELEVATION (DFE) WILL BE 9.4 FEET NAVD88 BASED ON THE
 (BFE) OF 7.00 FEET FOR FLOOD ZONE AE PLUS A CORRECTION
 FACTOR OF .4 FEET PLUS TWO FEET OF FREEBOARD.
  
 A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS
 REQUIRED AT TIME OF PERMIT APPLICATION.
 NOTE: ALL EQUIPMENT SERVICING THE BUILDINGS ON THIS
 SITE ARE REQUIRED TO BE AT OR ABOVE 9 FEET 4 INCHES
 NAVD.
  
 AN UNDER CONSTRUCTION (FORMBOARD) SURVEY WITH FINISHED
 FLOOR ELEVATION IS REQUIRED.
  
 A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
 THIS EC MAY BE SUBMITTED FOR REVIEW PRIOR TO BUILDING
 FINAL.
  
 GARAGE - VENTS
  
 G1001.4 ENCLOSURES BELOW DESIGN FLOOD ELEVATION.
 FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD ELEVATION
 SHALL BE AT OR ABOVE GRADE ON ALL SIDES AND CONFORM TO
 THE FOLLOWING:
  
 1. IN FLOOD HAZARD AREAS NOT SUBJECT TO HIGH-VELOCITY
 WAVE ACTION, ENCLOSED AREAS SHALL HAVE FLOOD OPENINGS
 TO ALLOW FOR THE AUTOMATIC INFLOW AND OUTFLOW OF
 FLOODWATERS.
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-08-12 Cont ID  
Sent By cthroop Date 2019-08-12 Time 15:00 Rev Time 0.00
Received By cthroop Date 2019-08-09 Time 07:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-07-18 Cont ID  
Sent By cthroop Date 2019-07-18 Time 10:56 Rev Time 0.00
Received By cthroop Date 2019-07-01 Time 10:23 Sent To  
Notes
2019-07-18 11:27:28PLUMBING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. BAR SINK SHALL BE TIED IN PAST WET VENT.
 P3108.1HORIZONTAL WET VENT PERMITTED.
  
 2. IN TWO BATH GROUPS THE SHOWER AND WATER CLOSET HAVE
 BEEN TIED TOGETHER PRIOR TO CONNECTING TO THE WET VENT.
 THESE FIXTURES MUST BE INDEPENDENTLY CONNECTED TO THE
 WET VENT.
 P3108.1HORIZONTAL WET VENT PERMITTED.
  
 3. THE DISHWASHER MUST BE CONNECTED TO THE SINK
 TAILPIECE, NOT THE VENT.
 P2717.2 SINK AND DISHWASHER.
 THE COMBINED DISCHARGE FROM A DISHWASHER AND A ONE- OR
 TWO-COMPARTMENT SINK, WITH OR WITHOUT A FOOD-WASTE
 DISPOSER, SHALL BE SERVED BY A TRAP OF NOT LESS THAN
 11/2 INCHES (38 MM) IN OUTSIDE DIAMETER. THE DISHWASHER
 DISCHARGE PIPE OR TUBING SHALL RISE TO THE UNDERSIDE OF
 THE COUNTER AND BE FASTENED OR OTHERWISE HELD IN THAT
 POSITION BEFORE CONNECTING TO THE HEAD OF THE
 FOOD-WASTE DISPOSER OR TO A WYE FITTING IN THE SINK
 TAILPIECE.
  
 4. WATER CLOSET CONNECTED DIRECTLY TO 4 INCH DRAIN MUST
 BE VENTED. CONNECT TO WET VENT OR ADD SEPERATE VENT.
 P3108.1HORIZONTAL WET VENT PERMITTED
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2019-08-14 Cont ID  
Sent By cthroop Date 2019-08-14 Time 16:02 Rev Time 0.00
Received By cthroop Date 2019-08-14 Time 16:01 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2019-08-12 Cont ID  
Sent By cthroop Date 2019-08-12 Time 15:28 Rev Time 0.00
Received By cthroop Date 2019-08-09 Time 07:55 Sent To  
Notes
2019-08-12 15:32:41BUILDING PLAN REVIEW - ROOFING
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 REVIEWS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED. I HAVE
 INCLUDED THEM BELOW FOR YOUR REVIEW.
  
 BUILDING PLAN REVIEW - ROOFING
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THERE ARE FOUR (2) NOA/PRODUCT APPROVAL COVER
 LETTERS IN THIS SUBMITTAL. PLEASE REMOVE THREE (3) OF
 THEM FROM SUBMITTAL.
 2. THE NOA'S AND PRODUCT APPROVALS SUBMITTED FOR REVIEW
 NEED TO BE LISTED ON THE COVER LETTER.
 3. DESIGNER SHALL SELECT ROOFING SYSTEM TO BE INSTALLED
 FROM NOA/PRODUCT APPROVAL.
 4. DESIGNER SHALL REVIEW AND APPROVE IN WRITING THOSE
 NOA'S/PRODUCT APPROVALS TO BE USED FOR THIS PROJECT.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-07-12 Cont ID  
Sent By cthroop Date 2019-07-12 Time 11:32 Rev Time 0.00
Received By cthroop Date 2019-07-01 Time 10:24 Sent To  
Notes
2019-07-12 11:49:28BUILDING PLAN REVIEW - ROOFING
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THERE ARE FOUR (4) NOA/PRODUCT APPROVAL COVER
 LETTERS IN THIS SUBMITTAL. PLEASE REMOVE THREE (3) OF
 THEM FROM SUBMITTAL.
 2. THE NOA'S AND PRODUCT APPROVALS SUBMITTED FOR REVIEW
 NEED TO BE LISTED ON THE COVER LETTER.
 3. DESIGNER SHALL SELECT ROOFING SYSTEM TO BE INSTALLED
 FROM NOA/PRODUCT APPROVAL.
 4. DESIGNER SHALL REVIEW AND APPROVE IN WRITING THOSE
 NOA'S/PRODUCT APPROVALS TO BE USED FOR THIS PROJECT.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-08-14 Cont ID  
Sent By cthroop Date 2019-08-14 Time 16:01 Rev Time 0.00
Received By cthroop Date 2019-08-14 Time 16:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-08-12 Cont ID  
Sent By cthroop Date 2019-08-12 Time 15:00 Rev Time 0.00
Received By cthroop Date 2019-08-09 Time 07:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-07-12 Cont ID  
Sent By cthroop Date 2019-07-12 Time 11:14 Rev Time 0.00
Received By cthroop Date 2019-07-01 Time 10:23 Sent To  
Notes
2019-07-12 11:17:00STRUCTURAL PLANS SIGNED BY TOM TAVERUS, PE ARE SELF
 CERTIFIED.
 NEW SIGNATURE STOP MAY BE REQUIRED UPON RE-SUBMITTAL OF
 NEW PLAN PAGES. CT

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2019-08-13 Time   Rev Time 0.00
Received By pgreilic Date 2019-08-13 Time 10:23 Sent To  
Notes
2019-08-13 10:24:061.) LANDCSAPE PERMIT REQUIRED
 2.) SEPARATE PERMITS REQUIRED FOR POOL, DRIVEWAY,
 MECHANICAL EQUIPMENT, LANDSCAPING, ETC
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By pgrehili Date 2019-06-26 Time   Rev Time 0.00
Received By pgreilic Date 2019-06-26 Time 09:17 Sent To  
Notes
2019-06-26 10:41:211.) LABEL OVERALL HEIGHT ON ALL ELEVATIONS
 2.) LANDCSAPE PERMIT REQUIRED
 3.) SEPARATE PERMITS REQUIRED FOR POOL, DRIVEWAY,
 MECHANICAL EQUIPMENT, LANDSCAPING, ETC
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]


Account Summary | Usage Policy | Privacy Policy