Plan Review Details - Permit 19050879
Plan Review Stops For Permit 19050879
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-01-22 Cont ID  
Sent By rmcdouga Date 2020-01-22 Time 15:03 Rev Time 0.00
Received By rmcdouga Date 2020-01-21 Time 17:27 Sent To P
Notes
2020-01-22 15:03:09THE RESIDENTIAL FIRE AREA OF THE MIXED USE BUILDING IS
 REQUIRED TO BE FIRE SPRINKLERED. THE BUILDING OFFICIAL
 HAS DETERMINED THAT SPRINKLERING THE SPACE BELOW THE
 RESIDENTIAL FIRE AREA WOULD PROVIDE MORE PROTECTION
 THAN SPRINKLERING THE SPACE ABOVE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-01 Cont ID  
Sent By jwitmer Date 2019-07-01 Time 08:51 Rev Time 0.00
Received By jwitmer Date 2019-07-01 Time 07:00 Sent To  
Notes
2019-07-01 08:50:282017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19050879 PRIME PERMIT: 19010578
 ADD: 2717 POINSETTIA AVE.
 CONT: DILO FIRE SPRINKLERS
 TEL: 561-748-7255
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 01/2019
 ACTION: DENIED
  
 1) SHEET FP-1 UNDER THE HEADING OF SCOPE OF WORK AND
 GENERAL NOTE # 1 BOTH INDICATE THE INSTALLATION OF A
 PARTIAL FIRE SPRINKLER SYSTEM IN A CONGREGATE CARE
 FACILITY. IN THE TITLE BLOCK THE USE OF THIS BUILDING
 1ST FLOOR A BIRTHING CENTER AND THE 2ND FLOOR AN R-3
 SINGLE FAMILY RESIDENCE. PLEASE CORRECT. 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) THE FIRE CHIEFS QUESTION AS TO WHY ONLY A PORTION OF
 THE 1ST FLOOR IS BEING FIRE SPRINKLERED. THE DESIGNER
 OF RECORD SHOULD PROVIDE A LETTER ON THEIR LETTERHEAD
 EXPLAINING WHY. THE 2ND FLOOR OCCUPANCY IS A SINGLE R-3
 DWELLING UNIT. BEING IN A MIXED USE BUILDING THE
 FLORIDA BUILDING CODE- BUILDING CODE IS USED. IN A
 MIXED USE BUILDING UNDER THE 2017 FBC-B SECTION
 903.2.8.1 WILL REQUIRE AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH 903.3.1.3 WHICH IS A NFPA 13D SPRINKLER
 SYSTEM.
  
 THE SECOND FLOOR HAS ONLY ONE MEANS OF EGRESS PLUS THE
 REQUIRED EGRESS WINDOWS. THE CODE 2017 FBC-B TABLE
 707.3.10 ALSO REQUIRES A 2 HR. FLOOR / CEILING
 ASSEMBLY. THERE IS ALSO RADIANT CEILING DAMPERS WITHIN
 THE FLOOR /CEILING ASSEMBLY UNDER THE R-3 PORTION OF
 THE BUILDING, WHERE FIRE ALARMS DEVICES ARE ALSO
 INSTALLED AS WELL AS THE STAIRWELL AND SECOND STORY
 LIVING QUARTERS.
  
 WE TOOK THIS CASE TO THE BUILDING OFFICIAL ASKING HIM
 THE CODE REALLY DOESN?T STATE WHERE THE R-13D
 SPRINKLERS ARE TO BE INSTALLED IN THE 2ND STORY PORTION
 OF THE BUILDING OR IN THE FIRE RATED FLOOR/ CEILING
 ASSEMBLY? HE AGREED IT WOULD MAKE MORE SINCE TO INSTALL
 THE SPRINKLERS IN THE 2ND FLOOR/CEILING ASSEMBLY TO
 HELP PROTECT THE 2 HOUR FIRE RATED ASSEMBLY.
  
 A LETTER WITH SIMILAR NARRATIVE SHOULD BE SUBMITTED
 FROM THE DESIGN PROFESSIONAL. PLEASE ALSO NOTE THE NFPA
 13D FOUND IN THE 2017 FBC-B SECTION 903.3.13 STATES THE
 SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 13 D.
 NFPA 13D SECTION 6.5 DEALS WITH COMMON SUPPLY PIPES
 WHERE SERVE BOTH FIRE SPRINKLERS AND DOMESTIC USE, THEY
 SHALL COMPLY WITH 6.5.2 AND 6.5.3.
  
 6.5.2 IN COMMON WATER SUPPLY CONECTIONS SERVING MORE
 THAN ONE DWELLING UNIT, 5 GPM SHALL BE ADDED TO THE
 FIRE SPRINKLER DEMAND TO DETERMINE THE SIZE OF COMMON
 PIPING AND THE SIZEE OF TOTAL WATER SUPPLY REQUIREMENTS
 WHERE NO PROVISIONS IS MADE TO PREVENT FLOW INTO
 DOMESTIC WATER SYSTEM UPON OPERATION OF A SPRINKLER.
  
 6.5.3. WHERE WATER TREATMENT AND FILTRATION ARE
 INSTALLED, ON OF THE FOLLOWING CONDITIONS SHALL BE MET:
 (1). THE FLOW RESTRICTION AND PRESSUREE LOSS THROUGH
 THE WATER TREATMENT EQUIPMENT SHALL BE TAKEN INTO
 ACCOUNT IN THE HYDROLIC CALCULATIONS.
 (2). AN AUTOMATIC BYPASS SHALL BE INSTALLED AROUND THE
 WATER TREATEMENT EQUIPMENT THAT DIRECTS ALL WATER
 DIRECTLY TO THE SYSTEM.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2020-01-28 Cont ID  
Sent By rrossano Date 2020-01-28 Time   Rev Time 0.00
Received By rrossano Date 2020-01-28 Time   Sent To I
Notes
2020-01-28 09:43:24PASSED WITH PROVISO:
  
 FP-1 PLAN MUST BE APPROVED BY PUBLIC UTILITIES METER
 DEPARTMENT. ADDITIONAL REQUIREMENTS MAY BE NECESSARY AT
 POINT OF SERVICE - RE: METER BYPASS, ETC. PLEASE
 CONTACT MARK HURLEY, CUSTOMER SERVICE SUPERVISOR AT
 561-822-2262 OR [email protected].
  
 THANKS,
  
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR WPB, FL 33401 (MAILING
 ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1098
 FAX: (561) 494-1116 MOBILE: (561) 246-9525
 EMAIL: [email protected] WWW.WPB.ORG/ENGINEERING
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2019-06-21 Cont ID  
Sent By Mgonzale Date 2019-06-21 Time   Rev Time 0.50
Received By mgonzale Date 2019-06-21 Time   Sent To B
Notes
2019-06-21 15:36:43A SEPARATE ENGINEERING SUBMITTAL IS REQUIRED.
  
 CONTACT MANNY GONALEZ (561) 818-1322
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-01-17 Cont ID  
Sent By ccarvaja Date 2020-01-29 Time 11:22 Rev Time 0.00
Received By pleduc Date 2020-01-17 Time 11:06 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-05-28 Cont ID  
Sent By pleduc Date 2019-05-28 Time   Rev Time 0.00
Received By pleduc Date 2019-05-28 Time 14:10 Sent To ENG
Notes
2019-05-28 14:18:31THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) UNDER WHAT CODE ARE YOU PROVIDING PROTECTION OF ONLY
 A PORTION OF THE 1ST FLOOR?
  
 PLEASE PROVIDE DETAILS.
  
  
  
 2) THE SUBMITTAL SHOWS CONNECTION TO THE DOMESTIC LINE.
  
 IF THIS CONNECTION OFF OA AN EXISTING LINE AND METER OR
 ONE SPECIFICALLY DESIGNATED AS A FIRE LINE?
  
 A SEPARATE DESIGNATED FIRE LINE WITH ITS OWN METER IS
 REQUIRED.
  
 PLEASE PROVIDE DETAILS,
  
  
  
 3) THIS PLAN IS BEING SENT TO THE BUILDING REVIEW AS
 THEIR COMMENTS ARE QUITE EXTENSIVE AND I WANT TO ENSURE
 THIS DESING MEETS THEIR COMMENTS.
  
  
 4) THIS PLAN IS BEING SENT TO ENGINEERING FOR THEIR
 COMMENTS ON A SEPARATE DESIGNATED FIRE LINE AND METER.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-01-29 Cont ID  
Sent By ccarvaja Date 2020-01-29 Time 11:22 Rev Time 0.00
Received By ccarvaja Date 2020-01-15 Time 13:15 Sent To FIRE
Notes
2020-01-15 13:18:37SENT TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-02 Cont ID  
Sent By tklarge Date 2019-07-02 Time 10:41 Rev Time 0.00
Received By tklarge Date 2019-05-17 Time 13:16 Sent To  
Notes
2019-05-20 13:16:10ROUTED TO FIRE INBOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-01-27 Cont ID  
Sent By tklarge Date 2020-01-27 Time 08:38 Rev Time 0.00
Received By tklarge Date 2020-01-27 Time 06:20 Sent To ENG
Notes
2020-01-27 08:14:10THE RESIDENTIAL FIRE AREA OF THE MIXED USE BUILDING IS
 REQUIRED TO BE FIRE SPRINKLERED. THE BUILDING OFFICIAL
 HAS DETERMINED THAT SPRINKLERING THE SPACE BELOW THE
 RESIDENTIAL FIRE AREA WOULD PROVIDE MORE PROTECTION
 THAN SPRINKLERING THE SPACE ABOVE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-07-02 Cont ID  
Sent By tklarge Date 2019-07-02 Time 10:37 Rev Time 0.00
Received By tklarge Date 2019-07-01 Time 09:58 Sent To I
Notes
2019-07-02 09:57:231) A SEPARATE PERMIT WILL BE REQUIRED FOR THE BACKFLOW
 PREVENTERWPB AMEND. TO FBC SEC. 105.1.
 2) THE BACKFLOW DEVICE SHALL BE LEAD FREE PER THE CITY
 OF WPB CROSS CONNECTION CONTROL MANUAL.
 3) SUBMIT TWO COPIES OF THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS SHOWING THIS DEVICE IS APPROVED FOR
 INSTALLATION IN THE VERTICAL POSITION. WPB AMEND. TO
 FBC SEC. 107.2.1.
 4) SUBMIT A NARRATIVE EXPLAINING WHY ONLY A PORTION OF
 THE FIRST FLOOR OF THE STRUCTURE IS BEING SPRINKLERED.
 SPRINKLERS SHALL BE INSTALLED IN ALL AREAS EXCEPT WHERE
 OMISSION IS PERMITTED PER 2013 NFPA 13 D SECS. 8.3.2 &
 8.3.8. NFPA 13D SEC. 8.3.
 5) SHT. FP-1 - GENERAL NOTE #1 AND SCOPE OF WORK NOTE
 STATES THAT THIS IS AN EXISTING CONGREGATE HOUSING
 FACILITY YET THE PLANS NOTE THIS AS A BIRTHING CENTER.
 CLARIFY.
 6) A SINGLE CONTROL VALVE ARRANGED TO SHUT OFF BOTH THE
 DOMESTIC SYSTEM AND THE SPRINKLER SYSTEM SHALL BE
 INSTALLED UNLESS A SEPARATE SHUTOFF VALVE FOR THE
 SPRINKLER SYSTEM IS INSTALLED IN ACCORDANCE WITH NFPA
 13D SEC. 7.1.2. NFPA 13D SEC. 7.1.1.
 7) A WARNING SIGN COMPLYING WITH NFPA 13D SHALL BE
 INSTALLED ADJACENT TO THE MAIN SHUTOFF VALE. NFPA 13D
 SEC.6.3.4.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  