Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-09-05 Cont ID  
Sent By tklarge Date 2019-09-05 Time 08:45 Rev Time 0.00
Received By tklarge Date 2019-09-05 Time 08:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-08-04 Cont ID  
Sent By tklarge Date 2019-08-04 Time 10:46 Rev Time 0.00
Received By tklarge Date 2019-08-04 Time 10:46 Sent To  
Notes
2019-08-04 10:46:301) TWO DIFFERENT DETAILS HAVE BEEN SUBMITTED FOR THE
 ENCLOSURE OF THE GAS LINE THROUGH THE STAIRWELL.ONE
 DETAIL IS SIGNED AND SEALED BY AN ARCHITECT AND SHOWS A
 RATED SOFFIT AND ANOTHER IS DONE BY BUCKEYE PLUMBING
 SHOWING BASICALLY A RATED BOX BEAM. I HAVE NO IDEA
 WHICH DETAIL IS TO BE USED. THE DETAIL TO BE USED SHALL
 BE SIGNED AND SEALED BY AN ARCHITECT. THE
 ENCLOSURE/SOFFIT SHALL HAVE A MINIMUM FIRE RESISTAVE
 RATING OF 2 HOURS.THE DETAIL FOR THE ENCLOSING OF THE
 GAS PIPE SHALL BE A LISTED FIRE-RESISTIVE ASSEMBLY IN
 ACCORDANCE WITH 2017 FBC SECS.714, 714.3, 715. SUBMIT
 TWO COPIES OF A SIGNED AND SEALED DETAIL FROM AN
 ARCHITECT. 2017 FBC SEC. 1023.2.
 2) THE PLANS DONE BY THE ARCHITECT SHOW AN EXISTING
 RAIN WATER LEADER IN THIS SAME STAIRWELL. THIS MAY ALSO
 NEED TO BE ADDRESSED.
 3) SHOW THE SOFFIT DIMENSIONS ( LXWXH) ON THE DRAWING
 BY MNA ARCHITECTS. WPB AMEND. TO FBC SEC. 107.2.1.
 4) THE DRAWING BY MNA ARCHITECTS DOES NOT INDICATE THE
 REQUIRED 2 HOUR FIRE RESISTANCE RATING OF THE
 SOFFIT.THIS MUST BE NOTED ON THE PLANS.
 5) SHOW THE CLEAR HEIGHT DIMENSION FROM THE FLOOR TO
 THE BOTTOM OF THE SOFFIT. THE DISTANCE SHALL BE NOT
 LESS THAN 7 FEET 6 INCHES PER 2017 FBC SEC.1003.2.
 6) SUBMIT THE LISTED FIRE SAFING ASSEMBLY DETAILS FOR
 SEALING THE PIPE PENETRATIONS THROUGH THE STAIR AND THE
 SOFFIT.2017 FBC SEC. 714.
 7) INDICATE ON THE PLANS HOW THE METAL TRACK STUDS WILL
 BE ATTACHED TO THE CONCRETE. SHOW TYPE, LENGTH,
 DIAMETER AND SPACING OF FASTENERS ON THE PLANS PER AN
 APPROVED LISTED FIRE RESISTANT ASSEMBLY.
 8) A BUILDING PERMIT WILL BE REQUIRED FOR THE SOFFIT BY
 A BUILDING CONTRACTOR AND ALSO A FIRE SPRINKLER PERMIT
 FOR THE WORK BEING DONE TO THE EXISTING FIRE LINE BY A
 CATEGORY I OR II FIRE PROTECTION CONTRACTOR. .
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-08-30 Cont ID  
Sent By pleduc Date 2019-08-30 Time   Rev Time 0.00
Received By pleduc Date 2019-08-30 Time 10:52 Sent To P
Notes
2019-08-30 10:55:33ANY FIRE SPRINKLER WORK SHALL BE DONE UNDER PERMIT AND
 SEPARATE SHOP DRAWINGS
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-08-05 Cont ID  
Sent By pleduc Date 2019-08-05 Time   Rev Time 0.00
Received By pleduc Date 2019-08-05 Time 10:28 Sent To I
Notes
2019-08-05 10:32:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) A 2HR WALL CHASE IS INDICATED BUT NO "LISTED" WALL
 DIAGRAM SHOWING CONSTRUCTION FEATURES TO MEET THAT
 RATING.
  
 PLEASE PROVIDE A LISTED WALL DETAIL.
  
  
 2) FIRE SPRINKLER WORK IS INDICATED.
  
 ALL FIRE SPRINKLER WORK SHALL BE DONE UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2019-09-05 Cont ID  
Sent By tklarge Date 2019-09-05 Time 08:34 Rev Time 0.00
Received By tklarge Date 2019-09-05 Time 07:54 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-08-04 Cont ID  
Sent By tklarge Date 2019-08-04 Time 10:46 Rev Time 0.00
Received By tklarge Date 2019-08-04 Time 09:17 Sent To  
Notes
2019-08-04 10:08:591) TWO DIFFERENT DETAILS HAVE BEEN SUBMITTED FOR THE
 ENCLOSURE OF THE GAS LINE THROUGH THE STAIRWELL.ONE
 DETAIL IS SIGNED AND SEALED BY AN ARCHITECT AND SHOWS A
 RATED SOFFIT AND ANOTHER IS DONE BY BUCKEYE PLUMBING
 SHOWING BASICALLY A RATED BOX BEAM. I HAVE NO IDEA
 WHICH DETAIL IS TO BE USED. THE DETAIL TO BE USED SHALL
 BE SIGNED AND SEALED BY AN ARCHITECT. THE
 ENCLOSURE/SOFFIT SHALL HAVE A MINIMUM FIRE RESISTAVE
 RATING OF 2 HOURS. 2017 FBC SEC. 1023.2.
 2) INDICATE THE SPACING OF THE STUDS ON THE DETAIL FOR
 THE SOFFIT. WPB AMEND. TO FBC SEC. 107.2.1.
 3) THE PLANS DONE BY THE ARCHITECT SHOW AN EXISTING
 RAIN WATER LEADER IN THIS SAME STAIRWELL. THIS MAY ALSO
 NEED TO BE ADDRESSED.
 4) SHOW THE SOFFIT DIMENSIONS ( LXWXH) ON THE DRAWING
 BY MNA ARCHITECTS. WPB AMEND. TO FBC SEC. 107.2.1.
 5) THE DRAWING BY MNA ARCHITECTS DOES NOTE THE REQUIRED
 2 HOUR FIRE RESISTANCE RATING OF THE SOFFIT.THIS MUST
 BE NOTED ON THE PLANS.
 6) SHOW THE CLEAR HEIGHT DIMENSION FROM THE FLOOR TO
 THE BOTTOM OF THE SOFFIT. THE DISTANCE SHALL BE NOT
 LESS THAN 7 FEET 6 INCHES PER 2017 FBC SEC.1003.2.
 7) SUBMIT THE LISTED FIRE SAFING ASSEMBLY DETAILS FOR
 SEALING THE PIPE PENETRATIONS THROUGH THE STAIR AND THE
 SOFFIT.2017 FBC SEC. 714.
 8) JOINTS IN THE LAYERED WALLBOARD SHALL BE STAGGERED
 IN RELATION TO LAYERS BELOW.
 9) INDICATE ON THE PLANS HOW THE METAL TRACK STUDS WILL
 BE ATTACHED TO THE CONCRETE. SHOW TYPE, LENGTH,
 DIAMETER AND SPACING OF FASTENERS ON THE PLANS.
 10) A BUILDING PERMIT WILL BE REQUIRED FOR THE SOFFIT
 BY A BUILDING CONTRACTOR AND ALSO A FIRE SPRINKLER
 PERMIT FOR THE WORK BEING DONE TO THE EXISTING FIRE
 LINE BY A CATEGORY I OR II FIRE PROTECTION CONTRACTOR.
 .
 11) THE DETAIL FROM BUCKEYE NOTES THE BOX BEAM TO BE
 SELF SUSPENDED. THIS WILL HAVE TO BE VERIFIED BY AN
 ARCHITECT DUE TO THE LENGTH OF THE BEAM AND WEIGHT OF
 THE MATERIAL ATTACHED IF THIS DESIGN IS TO BE USED.
 12) THE DETAIL FROM BUCKEYE SHALL SPECIFY THE TYPE OF
 SCREWS TO BE USED.WPB AMEND. TO FBC SEC. 107.2.1.
  
 NOTE: PLEASE CALL THIS REVIEWER TO DISCUSS THESE
 COMMENTS BEFORE REBSUBMITTING.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-05-31 Cont ID  
Sent By thunt Date 2019-05-31 Time 07:25 Rev Time 0.00
Received By thunt Date 2019-05-31 Time 07:25 Sent To  
Notes
2019-05-31 07:26:08GAS 1ST REVIEW**DENIED** NOTE - A COMPREHENSIVE REVIEW
 COULD NOT BE DONE AT THIS TIME AND ADDITIONAL PLAN
 REVIEW COMMENTS MAY BE GENERATED UPON THE RE-REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1) PERSON DESIGNING PLAN SHALL TAKE RESPONSIBILITY BY
 SIGNING AND DATING THEM. F.S 471,481, 489
  
 2) IN YOUR SCOPE OF WORK YOU CALL OUT RUNNING PIPING
 INTO THE STAIR WAY. PIPING IN THE STAIRWAY IS
 PROHIBITED EXCEPT FOR EQUIPMENT SERVING THAT STAIRWAY.
 FBC 1023.5
  
 3) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1
  
 4) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. 2017 FBC-FUEL
 GAS SEC.304.9.3 OR FBCR G2407.9.3.
  
 5) PER THE PLAN PROVIDED TOTAL PIPE LENGTH IS 180' WITH
 A DEMAND OF 439,000 BTU'S. PER YOUR SIZING TABLE
 PROVIDED (402.4(2)) THE MAX PERMITTED WOULD BE
 275,000BTU'S. YOUR SYSTEM IS UNDER SIZED. YOU MAY WANT
 TO UP TO A 2 PSI SYSTEM AND INSTALL A PRESSURE
 REGULATOR DOWN THE LINE. IF SO PLEASE PROVED 2PSI
 SIZING TABLE AND MANUFACTURES INSTALLATION MANUAL ON
 THE REGULATOR. FBC-G 402.4(2)
  
 6) THERE IS A 2ND SET OF PLANS IN THIS PACKET FOR A JOB
 OUTSIDE THE CITY LIMITS PLEASE REMOVE THEM WHEN
 RESUBMITTING. FBC 107.3.5
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-09-05 Cont ID  
Sent By tklarge Date 2019-09-05 Time 08:45 Rev Time 0.00
Received By tklarge Date 2019-08-29 Time 14:32 Sent To  
Notes
2019-08-29 14:32:49RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-05 Cont ID  
Sent By cpuell Date 2019-08-05 Time 13:28 Rev Time 0.00
Received By cpuell Date 2019-08-01 Time 13:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-31 Cont ID  
Sent By thunt Date 2019-05-31 Time 07:26 Rev Time 0.00
Received By thunt Date 2019-05-17 Time 15:58 Sent To  
Notes
2019-05-29 15:58:25ROUTED TO PLUMBING INBOX