Plan Review Details - Permit 19050710
Plan Review Stops For Permit 19050710
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-09-13 Cont ID  
Sent By jgomez Date 2019-09-13 Time 08:26 Rev Time 0.00
Received By jgomez Date 2019-09-12 Time 17:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-08-29 Cont ID  
Sent By jgomez Date 2019-08-29 Time 10:13 Rev Time 0.00
Received By jgomez Date 2019-08-29 Time 09:28 Sent To  
Notes
2019-08-27 16:58:10 
 BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- LIFE SAFETY SHEET ALS1.1:
 A)PROVIDE THE OCCUPANT LOAD ON EACH ROOM OR SPACE. AS
 REQUIRED BY SEC. 1004.1.1 AND TABLE 1004.1.2
 FBC-BUILDING. FOR EXAMPLE PROVIDE THE OCCUPANT LOAD AT
 PRIVATE DINING #1, PRIVATE DINING #2, BOOTHS, BARS,
 KITCHEN, ETC.
 NOTE: TAKE INTO CONSIDERATION THE AREAS WITHOUT FIXED
 SEATING (SEC. 1004.1.2 FBC) AND AREAS WITH FIXED
 SEATING (SEC. 1004.4 FBC).
  
 RESPONSE:
 (1) NUMBER OF PEOPLE CALCULATED PER SQUARE FOOTAGE AND
 NUMBER OF SEAT SHOWN ON FLOOR PLAN DON'T MATCH. FOR
 EXAMPLE CALCULATIONS FOR DINING #1 SAYS 26 PEOPLE BUT
 PLAN SHOWS 32 SEATS. SAME APPLIES TO DINING #2 AND
 OTHER AREAS SHOWING THE SEATS. REVISE AS REQUIRED TO
 MATCH.
  
 (2) THERE ARE NO OCCUPANTS SHOWN FOR RAW BAR AREA.
  
 B) OK
 C) OK
 D) OK
 E) OK.
 F) OK.
  
 2-FLOOR PLAN SHEET A1.1.1:
  
 A)PROVIDE COMPLETE APPROVED FIRE RATED WALL ASSEMBLY
 DETAIL BASED ON ANY OF THE METHODS ALLOWED BY SEC.
 703.3 FBC-BUILDING FOR THE TENANT SEPARATION WALL.
  
 RESPONSE:
 ONE HOUR FIRE RATED WALL DETAIL 13/A2.0.1 DOESN'T
 CORRESPOND TO SPECIFIED UL ASSEMBLY NO U415 SPECIFIED
 ON THIS WALL DETAIL. REVISE AS REQUIRED. PROVIDE WALL
 ASSEMBLY DETAIL THAT MATCHES SPECIFIED FIRE RATED
 APPROVED ASSEMBLY.
 NOTE: ASSEMBLY UL U415 IS TYPICAL WALL SHAFT WALLS.
  
 B) OK
 C) OK
  
 D) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 ACCESSIBLE DINING SURFACES AT BAR, RAW BAR AND BOOTH
 AREAS SHOWING COMPLIANCE WITH SEC. 226 FBC
 ACCESSIBILITY.
  
 RESPONSE:
 PARTIALLY COMPLIED. COUNTERS SHOWN AT RAW BAR AND BAR
 AREA SEEM TO COMPLY.
  
 THE FOLLOWING ARE COMMENTS FOR THE BOOTHS SHOWN ON
 PLANS. (NOTE: THERE ARE BOOTHS INSIDE THE RESTAURANT
 AND OUTSIDE THE RESTAURANT):
 (1)AT LEAST 5 PERCENT OF THE SEATING SPACES SHALL
 COMPLY WITH SEC. 902 FBC-ACCESSIBILITY AS REQUIRED BY
 SEC. 226.2 FBC-ACCESSIBILITY. INFORMATION SHOWN DON'T
 COMPLY WITH THE 5 PERCENT REQUIREMENT.
 NOTE: TAKE INTO CONSIDERATION NUMBER OF PEOPLE SEATING
 ON THE BOOTHS. COORDINATE WITH ITEM #1(A) ABOVE.
  
 (2)PROVIDE COMPLETE DETAILS AN SPECIFICATIONS FOR ALL
 BENCHES (CURVED AND STRAIGHT) SHOWN ON PLANS AS
 REQUIRED BY SEC. 202.4 FBC-ACCESSIBILITY AND SEC. 903
 FBC-ACCESSIBILITY
  
 (3) THE SEATING SPACES NEED TO BE DISPERSED. SEC. 226.2
 FBC-ACCESSIBILITY.
 NOTE: THERE ARE CURVED BOOTHS (INSIDE RESTAURANT) AND
 STRAIGHT BOOTHS (OUTSIDE AND INSIDE THE RESTAURANT).
  
 (4)ACCESSIBLE CLEAR SPACE SHOWN BY THE ROUND BOOTHS
 DON'T SEEM TO WORK AND IT DOESN'T COMPLY WITH SEC. 902
 FBC-ACCESSIBILITY. THE WAY IT IS DRAWN IS SHOWS LIKE
 THE BOOTH IS NOT USABLE. PROVIDE AN SKETCH SHOWING HOW
 THE BOOTH IS USED WITH A WHEEL CHAIR IN THE MIDDLE AS
 SHOWN ON PLANS. SEC. 107.2.1.2 CITY AMENDMENTS.
 NOTE: MAKE SURE EGRESS PATH IS NOT BLOCKED WHEN
 DESIGNING SEATING COMPLYING WITH SEC. 902
 FBC-ACCESSIBILITY.
  
 E) OK.
  
 3- OK.
  
 4- MISSING DOOR SCHEDULE AND WALL, FLOOR AND FINISH
 SCHEDULES, INTERIOR DESIGN DRAWINGS, SEC. 107.3.5.1.1
 CITY AMENDMENTS.
  
 RESPONSE:
 KITCHEN DOUBLE ENTRY DOORS (#112). AT LEAST ONE LEAF
 NEEDS TO PROVIDE A CLEAR WIDTH OF 32" MINIMUM AS
 REQUIRED BY SEC. 404.2.2 FBC-ACCESSIBILITY. REVISE AS
 REQUIRED.
  
 5- OK.
  
 6- OK.
  
 7-OK.
  
 8- ARCHITECT SPECIFIED ON LIFE SAFETY PLAN SHEET ALS1.1
 THAT THIS IS A TYPE IIA CONSTRUCTION. ACCORDING TO
 TABLE 601 FBC-BUILDING TYPE IIA CONSTRUCTION REQUIRES 1
 HOUR FIRE RESISTANCE ON THE PRIMARY STRUCTURAL FRAME.
 DETAIL 8/A2.0.1 NEEDS TO BE REVISED. THE COLUMN NEEDS
 TO BE FIRE RATED TO THE BOTTOM OF THE UNDERSIDE OF THE
 STRUCTURAL CEILING ABOVE. THIS DETAIL SPECIFIES FIRE
 RATING UP TO 6" ABOVE SUSPENDED CEILING. REVISE AS
 REQUIRED AND PROVIDE DETAILS/SPECS FOR AN APPROVED
 ASSEMBLY TO FIRE RATE COLUMNS AS REQUIRED BY SEC. 704.1
 FBC-BUILDING.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE
 DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-07-03 Cont ID  
Sent By jgomez Date 2019-07-03 Time 16:50 Rev Time 0.00
Received By jgomez Date 2019-07-02 Time 11:32 Sent To  
Notes
2019-06-28 11:47:22BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1- LIFE SAFETY SHEET ALS1.1:
 A)PROVIDE THE OCCUPANT LOAD ON EACH ROOM OR SPACE. AS
 REQUIRED BY SEC. 1004.1.1 AND TABLE 1004.1.2
 FBC-BUILDING. FOR EXAMPLE PROVIDE THE OCCUPANT LOAD AT
 PRIVATE DINING #1, PRIVATE DINING #2, BOOTHS, BARS,
 KITCHEN, ETC.
 NOTE: TAKE INTO CONSIDERATION THE AREAS WITHOUT FIXED
 SEATING (SEC. 1004.1.2 FBC) AND AREAS WITH FIXED
 SEATING (SEC. 1004.4 FBC).
  
 B) REVISE TOTAL OCCUPANT LOAD SHOWN UNDER LIFE SAFETY
 REQUIREMENTS ON THE UPPER RIGHT CORNER OF THE SHEET.
 NUMBER OF OCCUPANTS NEED TO BE ROUNDED UP NO DOWN.
 THERE ARE NO HALF OCCUPANTS. FOR EXAMPLE 6.8 OCCUPANTS
 WILL BE 7 OCCUPANTS NO 6. SEC. 107.2.1 CITY AMENDMENTS.
 NOTE: COORDINATE WITH ITEM #1(A) ABOVE.
  
 C) THE DIAGONAL DISTANCE OF BUILDING SHOWN ON THE LIFE
 SAFETY PLAN IS INCORRECT. DIAGONAL SHOWN IS TAKEN FROM
 THE EGRESS DOOR TO THE BOTTOM CORNER OF THE SPACE. THE
 DIAGONAL NEED TO BE TAKEN FROM ONE CORNER OF THE SPACE
 TO THE OTHER CORNER OF THE SPACE. SEE SEC. 1007.1.1
 FBC-BUILDING AND REVISE AS REQUIRED.(1/3 DISTANCE SHOWN
 BETWEEN EXITS IS OK)
  
 D) UPDATE ALL THE CODE SECTIONS CITED UNDER THE LIFE
 SAFETY REQUIREMENTS. SEE CURRENT FBC 6TH EDITION (2017)
 AND REVISE AS REQUIRED. CHAPTER 553 F.S.
  
 E) SPECIFY THE BUILDING CONSTRUCTION TYPE AS REQUIRED
 BY SEC. 107.3.5.1.1 CITY AMENDMENTS.
  
 F) TENANT SEPARATION NOTE SHOWN UNDER THE LIFE SAFETY
 REQUIREMENTS: CLARIFY WHY NO TENANT SEPARATION IS
 REQUIRED. CLARIFY WHY STATING THAT "ADJACENT TENANT
 SPACES ARE UNOCCUPIED, NO FIRE SEPARATION REQUIRED".
 PROVIDE SECTION SHOWING THAT THIS SEPARATION IS NOT
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 2-FLOOR PLAN SHEET A1.1.1:
 A) PROVIDE COMPLETE APPROVED FIRE RATED WALL ASSEMBLY
 DETAIL BASED ON ANY OF THE METHODS ALLOWED BY SEC.
 703.3 FBC-BUILDING (METHODS FOR DETERMINING FIRE
 RESISTANCE) FOR THE TENANT SEPARATION WALL.
 NOTE: COORDINATE WITH ITEM # 1(F) ABOVE.
  
 B)ACCORDING TO CITY RECORDS THE PREVIOUS TENANT
 OCCUPIED THE WHOLE SPACE INCLUDING THE WEST SIDE OF THE
 WORK AREA SHOWN ON PLANS. IT LOOKS LIKE THE SPACE IS
 GOING TO BE SPLIT INTO TWO TENANTS. NEED TO PROVIDE
 DETAILS AND SPECIFICATIONS SHOWING HOW THE EXISTING
 WALL SEPARATING THE TWO NEW TENANTS IS GOING TO COMPLY
 WITH THE TENANT SEPARATION REQUIREMENTS. SEC. 508.4
 FBC-BUILDING.
  
 C)CLARIFY WHY THE NEW TENANT SEPARATION WALL SEGMENT
 BETWEEN THE NEW KITCHEN AND ADJACENT TENANT SPACE ONLY
 GOES 6" ABOVE THE FINISH CEILING? COORDINATE WITH ITEM
 #2(A) ABOVE.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 D) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 ACCESSIBLE DINING SURFACES AT BAR, RAW BAR AND BOOTH
 AREAS SHOWING COMPLIANCE WITH SEC. 226 FBC
 ACCESSIBILITY.
  
 E) PROVIDE DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE ACCESS TO EMPLOYEE WORK AREA AT BAR
 AND RAW BAR AS REQUIRED BY SEC. 203.9
 FBC-ACCESSIBILITY.
  
 NOTE: 07/11/19. ITEM #3 BELOW WAS REVISED FOR
 CLARIFICATION AND AFTER TALKING TO ROBERT BROWN
 (BUILDING OFFICIAL).
 3-REFLECTED CEILING PLAN SHEET A1.1.2: CURTAIN ON
 PRIVATE DINING 1 EXCEEDS THE 10% OF THE SPECIFIC WALL
 OR CEILING AREA TO WHICH SUCH MATERIALS ARE ATTACHED.
 REVISE AS REQUIRED. SEC. 806.3 FBC-BUILDING.
 ANOTHER CONCERN IN THIS AREA IS THAT THE EGRESS FROM
 THIS PRIVATE DINING AREA WOULD BE BLOCKED BY THE
 CURTAINS. CURTAINS DON'T QUALIFY FOR EGRESS.
 07/11/19 TALKED TO POLLY DAUGHERTY (ARCH.) TO GO OVER
 THESE COMMENTS.
  
 4- MISSING DOOR SCHEDULE AND WALL, FLOOR AND FINISH
 SCHEDULES, INTERIOR DESIGN DRAWINGS, SEC. 107.3.5.1.1
 CITY AMENDMENTS.
  
 5- SHEET A1.1.3; ALL DETAILS ARE MISSING THE SIZES AND
 FASTENING SPECIFICATIONS. SEC. 1604.1 FBC-BUILDING.
  
 6- SHEET A2.0.1: ALL DETAILS ARE MISSING THE FASTENING
 SPECIFICATIONS. SEC. 1604.1 FBC-BUILDING.
  
 7-SHEET S-1.0:
 ENGINEER TO PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 FOR NEW LOAD BEARING WALL DETAIL 2/S-1.0. SPECIFY ALL
 FRAMING MEMBERS SIZE, SPACING FASTENING, CONNECTIONS
 (TOP & BOTTOM) ETC. SEC. 1604.1 FBC-BUILDING.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE
 DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-07-31 Cont ID  
Sent By jpearson Date 2019-07-31 Time 12:02 Rev Time 0.00
Received By jpearson Date 2019-07-31 Time 11:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-06-26 Cont ID  
Sent By jpearson Date 2019-06-26 Time 15:48 Rev Time 0.00
Received By jpearson Date 2019-06-26 Time 14:51 Sent To  
Notes
2019-06-26 15:13:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE GFCI PROTECTION FOR ALL OUTSIDE RECEPTACLES.
 NEC 210.8
 2. PROVIDE GFCI PROTECTION FOR ALL KITCHEN AND BAR AREA
 RECEPTACLES. NEC 210.8
 3. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
 4. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2
 5. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 6. PROVIDE EXTERIOR LIGHTING CONTROLS AS SPECIFIED IN
 THE FBC ENERGY CONSERVATION. FBC EC C405.2.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-08-02 Cont ID  
Sent By pleduc Date 2019-08-02 Time   Rev Time 0.00
Received By pleduc Date 2019-08-02 Time 14:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-05-20 Cont ID  
Sent By pleduc Date 2019-05-20 Time   Rev Time 0.00
Received By pleduc Date 2019-05-20 Time 10:18 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2019-09-17 Cont ID  
Sent By tklarge Date 2019-09-17 Time 13:20 Rev Time 0.00
Received By tklarge Date 2019-09-17 Time 13:20 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2019-09-12 Cont ID  
Sent By tklarge Date 2019-09-12 Time 13:43 Rev Time 0.00
Received By tklarge Date 2019-09-12 Time 12:50 Sent To  
Notes
2019-09-12 13:11:021) THE COVER SHEET FROM HKD DESIGN FOR THE CHARBROILER
 MODEL JBKC-36 SHOWS THE BTU CAPACITY AS 65.0 MBTU AND
 PAGE 2 OF THE SPECIFICATION SHEET LISTS THE BTU
 CAPACITY OF THEAT MODEL AS 90 MBTU. THE GAS RISER ON
 SHT.P2.1.1 SHOWS THE CAPACITY AS 130 MBTU. THE GAS LOAD
 SUMMARY TABLE ON SHT. P1.1.2. ALSO SHOWS 130 MBTU.
 CLARIFY.
 2) THE COVER SHEET FROM HKD DESIGN FOR THE GAS FRYER
 MODEL SR142G LISTS ONE GAS FRYER AT 105 MBTU BUT THE
 GAS RISER NOTES 2 GAS FRYERS. IS IT ONE OR TWO? THE GAS
 LOAD SUMMARY TABLE ON SHT. P1.1.2 LISTS ONLY ONE FRYER.
 CLARIFY. WPB AMEND. TO FBC SEC. 107.2.1.
 3) THE COVER SHEET FROM HKD DESIGN FOR THE 36 INCH HD
 RANGE MODEL JTRH-36 IP-36 SHOWS THE BTU CAPACITY AS 70
 MBTU AND SHT. 2 OF THE SPECIFICATIONS SHOWS 70 MBTU BUT
 THE GAS RISER SHOWS THE MBTU AS 35 . THE GAS LOAD
 SUMMARY ON SHT.P1.1.2 ALSO SHOWS THE MBTUH AS 35. THE
 GAS RISER AND THE GAS LOAD SUMMARY TABLE ONLY LIST ONE
 UNIT. CLARIFY
 4) THE SUBMITTED SPECIFICATIONS FOR THE PASTA COOKER
 SHOW THE BTU CAPACITY AS 105 MBTU AND 140 MBTU.THE GAS
 RISER ON SHT. P2.1.1 AND GAS LOAD SUMMARY TABLE ON SHT.
 P1.1.2 SHOW THE MBTU CAPACITY AS 45. INDICATE ON THE
 SPECIFICATIONS WHICH MODEL OF THIS APPLIANCE IS USED
 AND REVISE THE CORRECT BTU CAPACITY ON THE GAS RISER
 AND GAS LOAD SUMMARY TABLE.
 5) THE COVER SHEET FROM HKD DESIGN FOR THE 48 INCH
 RANGE MODEL JBR-8-36 AND THE SPECIFICATION SHEET SHOWS
 THE BTU CAPACITY AS 270 MBTU. THE GAS RISER ON SHT.
 P2.1.1 DOES NOT SHOW THIS APPLIANCE AND THE GAS LOAD
 SUMMARY TABLE ON SHT. P1.1.2 DOES NOT LIST THIS
 EQUIPMENT AT ALL. CLARIFY.
 6) SPECIFICATIONS HAVE BEEN SUBMITTED FOR A SECTIONAL
 RANGE STOCK POT APPLIANCE.THIS APPLIANCE IS NOT SHOWN
 ON THE GAS RISER BUT IS LISTED IN THE GAS LOAD SUMMARY
 TABLE.ON SHT. P1.1.2. INDICATE THE MODEL NUMBER AND
 CORRESPONDING BTU LOAD OF THE APPLIANCE ON THE
 SPECIFICATION SHEETS. WPB AMEND. TO FBC SEC. 107.2.1.
 7) THE TOTAL BTU LOAD THAT IS SHOWN ON THE GAS RISER ON
 SHT. P2.1.1 MUST MATCH THE TOTAL BTU LOAD THAT IS SHOWN
 ON THE GAS LOAD SUMMARY TABLE ON SHT. P1.1.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-08-23 Cont ID  
Sent By tklarge Date 2019-08-23 Time 10:53 Rev Time 0.00
Received By tklarge Date 2019-08-23 Time 10:13 Sent To  
Notes
2019-08-23 10:53:111) SUBMIT TWO COPIES OF MANUFACTURER'S SPECIFICATIONS
 FOR EACH PIECE OF GAS EQUIPMENT LISTED ON SHT.P1.1.2.
 THE ONLY SPECIFICATION THAT WAS IN THE PERMIT
 APPLICATION FOLDER WAS FOR THE GAS FLOOR FRYER.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-06-18 Cont ID  
Sent By thunt Date 2019-06-18 Time 12:19 Rev Time 0.00
Received By thunt Date 2019-06-18 Time 12:19 Sent To  
Notes
2019-06-18 12:20:01GAS 1ST REVIEW**DENIED**NOTE - A COMPREHENSIVE REVIEW
 COULD NOT BE DONE AT THIS TIME AND ADDITIONAL PLAN
 REVIEW COMMENTS MAY BE GENERATED UPON THE RE-REVIEW OF
 SUBMITTED CORRECTIONS
  
 1) SUBMIT AN COMPLETE ISOMETRIC DRAWING THAT CLEARLY
 SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017
 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. 2017 FBC-FUEL
 GAS SEC.304.9.3
  
 3) PROVIDE AN EXISTING FLOOR PLAN SHOWING ALL EXISTING
 EQUIPMENT. FBC 107.3.5
  
 4) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3. GAS
 APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1.
  
 5) EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE SHALL BE
 BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE
 UPSTREAM. UNION TO BE DOWN STREAM OF MANUAL VALVE.
 SECS. 10.4, 10.5 OF NFPA 96-08.
  
 6) PLEASE NOTE THE TANKLESS WATER HEATER WAS REPLACED
 IN 2016 UNDER PERMIT#16020422 WITH NO INSPECTIONS. CODE
 VIOLATIONS MAY EXIST THAT YOU WILL BE REQUIRED TO TAKE
 CARE OF.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-09-17 Cont ID  
Sent By tklarge Date 2019-09-17 Time 13:20 Rev Time 0.00
Received By tklarge Date 2019-09-13 Time 14:29 Sent To  
Notes
2019-09-16 14:29:29RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-09-13 Cont ID  
Sent By jgomez Date 2019-09-13 Time 09:28 Rev Time 0.00
Received By jgomez Date 2019-09-09 Time 14:34 Sent To  
Notes
2019-09-10 14:35:02RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-29 Cont ID  
Sent By jgomez Date 2019-08-29 Time 10:13 Rev Time 0.00
Received By jgomez Date 2019-07-26 Time 14:37 Sent To I
Notes
2019-07-30 14:37:08C09

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-07-03 Cont ID  
Sent By jgomez Date 2019-07-03 Time 16:52 Rev Time 0.00
Received By jgomez Date 2019-05-14 Time 13:50 Sent To I
Notes
2019-05-15 13:50:29C36

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-07-03 Cont ID  
Sent By jgomez Date 2019-07-03 Time 16:52 Rev Time 0.00
Received By jgomez Date 2019-07-03 Time 16:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-08-23 Cont ID  
Sent By hmoser Date 2019-08-23 Time 15:04 Rev Time 0.00
Received By hmoser Date 2019-08-23 Time 13:45 Sent To  
Notes
2019-08-23 15:04:50PASS PROVISO
 1) REFER TO SECTION 403.2.4.3 FLORIDA ENERGY CODE 2017
 SHUTOFF DAMPERS. OUTDOOR AIR INTAKE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6673
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-06-13 Cont ID  
Sent By ccole Date 2019-06-13 Time 14:04 Rev Time 0.00
Received By ccole Date 2019-06-13 Time 12:00 Sent To  
Notes
2019-06-13 14:43:401ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19050710
 6/13/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.1.1: SWITCH THE LOCATIONS OF KEYNOTES #2 &
 3 ON THE PLANS (CHILLED WATER AND CONDENSATE AT FCU'S)-
 SECTION 107.2.1 WPB.
  
 2) M1.1.1: PROVIDE AUTOMATIC DAMPERS FOR THE O/A DUCTS
 SUPPLYING THE NEW FCU'S- SECTION C403.2.4.2 FBC EC.
  
 3) M2.1.1: PROVIDE AN FCU INSTALLATION DETAIL- SECTION
 107.2.1 WPB.
  
 4) REFER TO SECTION C403.2.6.1 FBC EC AND INDICATE HOW
 COMPLIANCE IS BEING MET.
  
 C403.2.6.1 DEMAND CONTROLLED VENTILATION.
  
 DEMAND CONTROL VENTILATION (DCV) SHALL BE PROVIDED FOR
 SPACES LARGER THAN 500 SQUARE FEET (46.5 M2) AND WITH
 AN AVERAGE OCCUPANT LOAD OF 25 PEOPLE PER 1,000 SQUARE
 FEET (93 M2) OF FLOOR AREA (AS ESTABLISHED IN TABLE
 403.3.1.1 OF THE FLORIDA BUILDING CODE, MECHANICAL) AND
 SERVED BY SYSTEMS WITH ONE OR MORE OF THE FOLLOWING:
  
 1.AN AIR-SIDE ECONOMIZER.
  
 2.AUTOMATIC MODULATING CONTROL OF THE OUTDOOR AIR
 DAMPER.
  
 3.A DESIGN OUTDOOR AIRFLOW GREATER THAN 3,000 CFM (1416
 L/S).
  
 EXCEPTION: DEMAND CONTROL VENTILATION IS NOT REQUIRED
 FOR SYSTEMS AND SPACES AS FOLLOWS:
  
 1.SYSTEMS WITH ENERGY RECOVERY COMPLYING WITH SECTION
 C403.2.7.
  
 2.MULTIPLE-ZONE SYSTEMS WITHOUT DIRECT DIGITAL CONTROL
 OF INDIVIDUAL ZONES COMMUNICATING WITH A CENTRAL
 CONTROL PANEL.
  
 3.SYSTEMS WITH A DESIGN OUTDOOR AIRFLOW LESS THAN 1,200
 CFM (566 L/S).
  
 4.SPACES WHERE THE SUPPLY AIRFLOW RATE MINUS ANY MAKEUP
 OR OUTGOING TRANSFER AIR REQUIREMENT IS LESS THAN 1,200
 CFM (566 L/S).
  
 5.VENTILATION PROVIDED FOR PROCESS LOADS ONLY.
  
 6) SUBMIT PRODUCT DATA SHEETS FOR THE NEW GAS-FIRED
 COOKING APPLIANCES- SECTION 623.1 FBC FG.
  
 7) PLEASE NOTE THAT SEPARATE PERMITS AND PLANS ARE
 REQUIRED FOR COMMERCIAL KITCHEN HOODS AND FIRE
 SUPPRSSION SYSTEMS, AND WALK-IN COOLERS AND FREEZERS-
 SECTION 107.2.1 WPB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-09-17 Cont ID  
Sent By tklarge Date 2019-09-17 Time 09:38 Rev Time 0.00
Received By tklarge Date 2019-09-17 Time 09:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2019-09-12 Cont ID  
Sent By tklarge Date 2019-09-12 Time 13:55 Rev Time 0.00
Received By tklarge Date 2019-09-11 Time 11:50 Sent To B
Notes
2019-09-12 13:55:501) SHT. A3.02 - DETAIL "A" - IF A TROUGH LAVATORY IS
 INSTALLED IN THE MEN'S ROOM, THE LAVATORY AND WALL
 SPOUT SHALL COMPLY WITH THE 2017 FBC-ACCESS.
 SEC.308.2.2. DETAIL "A" SHOWS A TROUGH LAVATORY FIXTURE
 AND DETAIL 4 SHOWS 2 INDEPENDENT WALL HUNG LAVATORIES.
 CLARIFY.
 2) SHT. A4.01 - DETAIL #3 - THE HEIGHT OF THE LAVATORY
 SPOUT SHALL COMPLY WITH THE 2017 FBC-ACCESS.
 SEC.308.2.2.
 3) SHT. P2.1.1 - DETAIL #3 - SANITARY ISOMETRIC DRAWING
 - THE ICE BIN SHALL NOT DISCHARGE TO THE GREASE WASTE
 SYSTEM PER THE 2017 FBC-PLUMBING SEC.1003.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-08-23 Cont ID  
Sent By tklarge Date 2019-08-23 Time 11:10 Rev Time 0.00
Received By tklarge Date 2019-08-15 Time 13:50 Sent To  
Notes
2019-08-23 11:10:411) SHT. P1.1.3 - THE GREASE INTERCEPTOR SIZING
 CALCULATIONS STATE THAT THERE ARE 3,000 GALLONS OF
 GREASE TRAP CAPACITY PROVIDED. SUBMIT DOCUMENTATION
 THAT CONFIRMS THERE IS INDEED THIS AMOUNT OF CAPACITY
 AVAILABLE IN THE EXISTING GREASE INTERCEPTOR. WPB
 AMEND. TO FBC SEC.107.2.1.
 2) SHT. P2.1.1 - INDICATE ON THE SANITARY RISER
 DIAGRAMS WHICH ONES ARE CONNECTING TO THE SANITARY
 SYSTEM AND WHICH ONES ARE CONNECTING TO THE GREASE
 WASTE SYSTEM. WASTES THAT DO NOT REQUIRE TREATMENT OR
 SEPARATION SHALL NOT DISCHARGE INTO ANY INTERCEPTOROR
 SEPARATOR. FBC_PLUMBING SEC.1003.2.
 3) SHT. P1.1.3 - SIZING CALCULATIONS FOR THE GREASE
 INTERCEPTOR CAPACITY SHALL COMPLY WITH THE STANDARDS
 LISTED IN FBC-PLUMBING SEC.1003.3.4. THE INFORMATION ON
 THE PLANS ALSO REFER TO MDC REGULATIONS. WHAT IS THIS
 REFERENCED STANDARD? THIS IS NOT A RECOGNIZED
 STANDARD/REGULATION IN THE FBC-PLUMBING,CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-06-18 Cont ID  
Sent By thunt Date 2019-06-18 Time 12:46 Rev Time 0.00
Received By thunt Date 2019-06-18 Time 11:06 Sent To  
Notes
2019-06-18 12:46:46PLUMBING 1ST REVIEW**DENIED**NOTE - A COMPREHENSIVE
 REVIEW COULD NOT BE DONE AT THIS TIME AND ADDITIONAL
 PLAN REVIEW COMMENTS MAY BE GENERATED UPON THE
 RE-REVIEW OF SUBMITTED CORRECTIONS
  
 1) PROVIDE A COMPLETE EXISTING FLOOR PLAN SHOWING ALL
 EXISTING EQUIPMENT. FBC 107.3.5 AS CITY RECORDS #
 15110078 SHOW A COMPLETE DIFFERENT LAY OUT TO INCLUDE
 THE RESTROOMS.
  
 2) PROVIDE DISTANCE FROM WATER HEATER TO FURTHEST HOT
 WATER OUTLET OF NEW PIPING. IF THE TOTAL DEVELOPED
 LENGTH IS OVER 50' THAN A HOT WATER RETURN SYSTEM SHALL
 BE INSTALL AND INSULATED.FBC P607.2, FBC-ENERGY C404.6.
  
 3) PROVIDE GREASE INTERCEPTOR SIZING CALCULATIONS.
 THERE IS NO RECORD OF AN EXISTING INTERCEPTOR. IF ONE
 EXISTS PLEASE PROVIDE INSPECTION REPORT ON CONDITION
 AND SIZE. IF THE INTERCEPTOR IS UNDERSIZED BASED ON
 REQUIREMENTS FBC-P 1003.3.4, 1003.3.4.1 THEN THE
 CORRECT REQUIRED SIZE INTERCEPTOR WILL NEED TO BE
 INSTALLED WITH ITS OWN STANDALONE PERMIT. FBC P 1003.1
  
 4) PROVIDE A COMPLETE SANITARY RISER DRAWING. PROVIDE
 PIPE SIZE OF EXISTING FLOOR SINKS AS YOU CALL OUT
 ADDITIONAL DFU LOAD RUNNING NEW SINKS INTO THEM. FBC
 107.3.5
  
 5) ADD NOTE THAT HAND SINKS SHALL BE TEMPERED BY MEANS
 OF AN APPROVED ASSE 1070 DEVICE. FBC-P 607.1.2
  
 6) PROVIDE BATHROOM FIXTURE DETAIL SHOWING COMPLIANCE
 WITH FLORIDA ACCESSIBILITY. EXAMPLE:GRAB BAR LOCATIONS,
 MIRROR MOUNTING, TOILET PAPER MOUNTING, ETC. PLEASE
 REFER TO CHAPTER 6 PLUMBING FIXTURES FBC-ACCESSIBILITY
  
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2019-08-02 Cont ID  
Sent By eschneid Date 2019-08-02 Time 16:11 Rev Time 0.25
Received By eschneid Date 2019-08-02 Time 15:27 Sent To  
Notes
2019-08-02 16:12:03IF ANY ROOFTOP EQUIPMENT REQUIRES REPLACEMENT,
 CONTRACTOR MUST PROVIDE VERIFICATION TO ZONING THAT IT
 IS SCREENED MEETING CITYPLACE DRI REQUIREMENTS PRIOR TO
 INSTALL.
  
 AWNING REPLACEMENT REQUIRES SEPARATE PERMIT.

Review Stop Z ZONING
Rev No 1 Status F Date 2019-05-28 Cont ID  
Sent By eschneid Date 2019-05-28 Time 11:23 Rev Time 0.75
Received By eschneid Date 2019-05-28 Time 10:05 Sent To  
Notes
2019-05-28 11:23:18FAILED
  
 1) SHEET M2.1.1 LISTS 12 HVAC KEY NOTES INCLUDING "NEW
 CHW FCU"; HOWEVER, THERE IS NO LOCATION SHOWN FOR THIS
 EQUIPMENT ON THE MECHANICAL ROOF PLAN. PLEASE EXPLAIN
 THIS DISCREPANCY.
  
 2) IF THERE IS NEW EQUIPMENT BEING INSTALLED ON THE
 ROOF. IN ACCORDANCE WITH THE CITYPLACE DRI, PLEASE
 PROVIDE VERIFICATION THAT ALL ROOFTOP MECHANICAL
 EQUIPMENT, INCLUDING BUT NOT LIMITED TO SUCH ITEMS AS
 PUBLIC AND PRIVATE UTILITY SERVICE CONNECTIONS;
 HEATING, VENTILATING, AND AIR CONDITIONING SYSTEMS;
 COMMUNICATIONS DEVICES; AND RELATED EQUIPMENT, SHALL BE
 SCREENED FROM PUBLIC VIEW THROUGH ANY COMBINATION OF
 LANDSCAPING, WALLS AND EQUIPMENT LOCATION. PLEASE
 PROVIDE PLANS OR OTHER EVIDENCE THAT THE NEW ROOFTOP
 MECHANICAL EQUIPMENT WILL BE SCREENED FROM PUBLIC VIEW.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.