Plan Review Stops For Permit 19050677 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2019-07-17 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-07-17 |
Time |
15:11 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2019-07-17 |
Time |
15:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2019-06-07 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-06-07 |
Time |
14:24 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2019-06-07 |
Time |
14:12 |
Sent To |
|
|
Notes |
2019-06-07 14:26:38 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 2ND BUILDING PLAN REVIEW DENIED: | | | | 1. OK; FBC B 107.1 THE PLANS HAVE BEEN SIGNED AND | | SEALED BY DESIGNER OF RECORD. | | 2. FAIL; FBC B 107.2.1 PROVIDE A SURVEY SHOWING THE | | STRUCTURE AND COMPLETE DRIVEWAY ON LOT INCLUDING SET | | BACK MEASUREMENTS. | | 3. FAIL; FBC B 107.1 PROVIDE THE PRODUCT APPROVAL FOR | | THE NEW WINDOW TO BE INSTALLED. | | 4. OK; FBC B 109.3 THE EVALUATION BREAKDOWN WAS | | SUBMITTED BY NEWBOLD CONSTRUCTION AND HAS BEEN ADJUSTED | | TO A VALUATION OF $9,570.00. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2019-05-29 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-05-29 |
Time |
13:12 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2019-05-29 |
Time |
13:12 |
Sent To |
|
|
Notes |
2019-05-29 13:41:59 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | BUILDING PLAN REVIEW DENIED | | | | 1. FBC B 107.1 THE PLANS NEED TO BE SIGNED BY THE | | DESIGNER. | | 2. FBC B 107.2.1 PROVIDE A SURVEY SHOWING THE STRUCTURE | | AND COMPLETE DRIVEWAY ON LOT INCLUDING SET BACK | | MEASUREMENTS. | | 3. FBC B 107.1 PROVIDE THE PRODUCT APPROVAL FOR THE NEW | | WINDOW TO BE INSTALLED. | | 4. FBC B 109.3 THE VALUATION APPEARS TO BE LOW. PLEASE | | EVALUATE AND PROVIDE COST BREAKDOWN. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2019-07-16 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2019-07-16 |
Time |
10:08 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2019-07-16 |
Time |
08:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2019-06-17 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2019-06-17 |
Time |
15:31 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2019-06-17 |
Time |
15:31 |
Sent To |
|
|
Notes |
2019-06-17 15:31:28 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL | | LOADS. MATH IS NOT CORRECT. NEC 220; FBC RE E3602.2 | | 2. NOTE 1 STATES THAT AT LEAST 50% OF ALL LAMPS SHALL | | BE ENERGY EFFICIENT. CURRENT ENERGY CODE REQUIRES A | | MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY | | INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY | | LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY | | INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH | | EFFICACY LAMPS. PROVIDE CORRECTION TO NOTE. FBC EC | | C405.1, R404.1 | | 3. CORRECTED. | | 4. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE | | PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH | | CIRCUITS SHALL HAVE NO OTHER OUTLETS. THERE IS NO | | EVIDENCE OF THIS ON PLAN. PROVIDE CORRECTION. NEC | | 210.11(C)(3) , FBC RE E3703.4 | | 5. ACCEPTED BY BUILDING. | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2019-05-29 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2019-05-29 |
Time |
10:23 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2019-05-29 |
Time |
10:23 |
Sent To |
|
|
Notes |
2019-05-29 10:18:16 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL | | LOADS. MATH IS NOT CORRECT. NEC 220; FBC RE E3602.2 | | 2. NOTE 1 STATES THAT AT LEAST 50% OF ALL LAMPS SHALL | | BE ENERGY EFFICIENT. CURRENT ENERGY CODE REQUIRES A | | MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY | | INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY | | LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY | | INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH | | EFFICACY LAMPS. PROVIDE CORRECTION TO NOTE. FBC EC | | C405.1, R404.1 | | 3. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC | | 210.8(D); FBC RE E3902.10 | | 4. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE | | PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH | | CIRCUITS SHALL HAVE NO OTHER OUTLETS. THERE IS NO | | EVIDENCE OF THIS ON PLAN. PROVIDE CORRECTION. NEC | | 210.11(C)(3) , FBC RE E3703.4 | | 5. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC | | 109.3 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
N |
Date |
2019-07-01 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2019-07-01 |
Time |
12:42 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2019-07-01 |
Time |
12:42 |
Sent To |
|
|
Notes |
2019-07-01 12:43:39 | GAS PLAN REVIEW | | A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE | | REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK. | | PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT | | SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE | | SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC. | | 107.2.1. | | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE | | FBC-R, SEC. G2404.3. | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL | | GAS SEC. 301.3. | | | | A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS | | INSTALLATION OR MODIFICATION OF SYSTEM. | | | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2019-07-17 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-07-17 |
Time |
15:29 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2019-06-25 |
Time |
11:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2019-06-24 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2019-06-24 |
Time |
13:25 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2019-05-31 |
Time |
14:38 |
Sent To |
|
|
Notes |
2019-06-24 08:14:10 | 6/24 TO HM DESK | | | | | 2019-06-03 14:38:39 | R07 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2019-05-29 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-05-29 |
Time |
13:42 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2019-05-13 |
Time |
15:18 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2019-07-17 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-07-17 |
Time |
15:28 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2019-07-17 |
Time |
15:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2019-06-24 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2019-06-24 |
Time |
13:23 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2019-06-24 |
Time |
11:37 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2019-05-28 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2019-05-28 |
Time |
13:09 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2019-05-28 |
Time |
10:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2019-07-01 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2019-07-01 |
Time |
12:41 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2019-07-01 |
Time |
12:22 |
Sent To |
|
|
Notes |
2019-07-01 12:44:02 | A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS | | INSTALLATION OR MODIFICATION OF SYSTEM. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2019-06-11 |
|
|
Cont ID |
|
Sent By |
thunt |
Date |
2019-06-11 |
Time |
08:53 |
Rev Time |
0.00 |
Received By |
thunt |
Date |
2019-06-11 |
Time |
08:53 |
Sent To |
|
|
Notes |
2019-06-11 08:54:00 | PLEASE REVIEW PROVISO ON PLAN |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2019-05-16 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2019-05-16 |
Time |
09:15 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2019-05-16 |
Time |
07:52 |
Sent To |
|
|
Notes |
2019-05-16 09:16:02 | 1ST REVIEW: 19050677 | | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | EDITION | | | | PLUMBING COMMENTS: | | | | 1. PLAN SHEETS SHALL BE SIGNED AND SEALED BY ENGINEER | | LISTED ON TOP OF TITLE BLOCK LUIS C MAURY. PER FAC | | 61G15-23.003 | | | | 2. VALUATION FOR THIS JOB APPEARS TO BE LOW PLEASE | | PROVIDE A DETAILED, QUANTITY ESTIMATES, AND/OR BONA | | FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO MEET | | THE | | APPROVAL OF THE BUILDING OFFICIAL. PER WPB AMEND TO FBC | | 109.3 | | | | 3. SHT A1 THE PROPOSED FLOOR PLAN SHOWS AN EXISTING | | WATER HEATER SHT E1 SHOWS A NEW TANKLESS AND THE | | EXISTING TANK TYPE WATER HEATER IS THE OLD HEATER | | REMAINING IN USE PLEASE CLARIFY. PER WPB AMEND TO FBC | | 107.2.1 | | | | 4. PLEASE PROVIDE DIMENSIONS OF THE SHOWER SHALL COMPLY | | WITH FBC RES P2708.1 | | | | 5. PLEASE SHOW CLEANOUT ON THE ISOMETRIC DRAWING WERE | | THE NEW BUILDING DRAIN EXISTS THE STRUCTURE. PER FBC | | RES P3005.2.3 | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] |
|
|