Plan Review Details - Permit 19050677
Plan Review Stops For Permit 19050677
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-07-17 Cont ID  
Sent By pvalenti Date 2019-07-17 Time 15:11 Rev Time 0.00
Received By pvalenti Date 2019-07-17 Time 15:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-06-07 Cont ID  
Sent By pvalenti Date 2019-06-07 Time 14:24 Rev Time 0.00
Received By pvalenti Date 2019-06-07 Time 14:12 Sent To  
Notes
2019-06-07 14:26:38***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2ND BUILDING PLAN REVIEW DENIED:
  
 1. OK; FBC B 107.1 THE PLANS HAVE BEEN SIGNED AND
 SEALED BY DESIGNER OF RECORD.
 2. FAIL; FBC B 107.2.1 PROVIDE A SURVEY SHOWING THE
 STRUCTURE AND COMPLETE DRIVEWAY ON LOT INCLUDING SET
 BACK MEASUREMENTS.
 3. FAIL; FBC B 107.1 PROVIDE THE PRODUCT APPROVAL FOR
 THE NEW WINDOW TO BE INSTALLED.
 4. OK; FBC B 109.3 THE EVALUATION BREAKDOWN WAS
 SUBMITTED BY NEWBOLD CONSTRUCTION AND HAS BEEN ADJUSTED
 TO A VALUATION OF $9,570.00.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-29 Cont ID  
Sent By pvalenti Date 2019-05-29 Time 13:12 Rev Time 0.00
Received By pvalenti Date 2019-05-29 Time 13:12 Sent To  
Notes
2019-05-29 13:41:59***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING PLAN REVIEW DENIED
  
 1. FBC B 107.1 THE PLANS NEED TO BE SIGNED BY THE
 DESIGNER.
 2. FBC B 107.2.1 PROVIDE A SURVEY SHOWING THE STRUCTURE
 AND COMPLETE DRIVEWAY ON LOT INCLUDING SET BACK
 MEASUREMENTS.
 3. FBC B 107.1 PROVIDE THE PRODUCT APPROVAL FOR THE NEW
 WINDOW TO BE INSTALLED.
 4. FBC B 109.3 THE VALUATION APPEARS TO BE LOW. PLEASE
 EVALUATE AND PROVIDE COST BREAKDOWN.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-07-16 Cont ID  
Sent By jpearson Date 2019-07-16 Time 10:08 Rev Time 0.00
Received By jpearson Date 2019-07-16 Time 08:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-06-17 Cont ID  
Sent By jpearson Date 2019-06-17 Time 15:31 Rev Time 0.00
Received By jpearson Date 2019-06-17 Time 15:31 Sent To  
Notes
2019-06-17 15:31:28CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. MATH IS NOT CORRECT. NEC 220; FBC RE E3602.2
 2. NOTE 1 STATES THAT AT LEAST 50% OF ALL LAMPS SHALL
 BE ENERGY EFFICIENT. CURRENT ENERGY CODE REQUIRES A
 MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY
 LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH
 EFFICACY LAMPS. PROVIDE CORRECTION TO NOTE. FBC EC
 C405.1, R404.1
 3. CORRECTED.
 4. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. THERE IS NO
 EVIDENCE OF THIS ON PLAN. PROVIDE CORRECTION. NEC
 210.11(C)(3) , FBC RE E3703.4
 5. ACCEPTED BY BUILDING.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-29 Cont ID  
Sent By jpearson Date 2019-05-29 Time 10:23 Rev Time 0.00
Received By jpearson Date 2019-05-29 Time 10:23 Sent To  
Notes
2019-05-29 10:18:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. MATH IS NOT CORRECT. NEC 220; FBC RE E3602.2
 2. NOTE 1 STATES THAT AT LEAST 50% OF ALL LAMPS SHALL
 BE ENERGY EFFICIENT. CURRENT ENERGY CODE REQUIRES A
 MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY
 LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH
 EFFICACY LAMPS. PROVIDE CORRECTION TO NOTE. FBC EC
 C405.1, R404.1
 3. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 4. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. THERE IS NO
 EVIDENCE OF THIS ON PLAN. PROVIDE CORRECTION. NEC
 210.11(C)(3) , FBC RE E3703.4
 5. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2019-07-01 Cont ID  
Sent By gjohnson Date 2019-07-01 Time 12:42 Rev Time 0.00
Received By gjohnson Date 2019-07-01 Time 12:42 Sent To  
Notes
2019-07-01 12:43:39GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-07-17 Cont ID  
Sent By pvalenti Date 2019-07-17 Time 15:29 Rev Time 0.00
Received By pvalenti Date 2019-06-25 Time 11:12 Sent To  
Notes
2019-06-27 11:12:41R07

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-24 Cont ID  
Sent By hmoser Date 2019-06-24 Time 13:25 Rev Time 0.00
Received By hmoser Date 2019-05-31 Time 14:38 Sent To  
Notes
2019-06-24 08:14:106/24 TO HM DESK
  
  
2019-06-03 14:38:39R07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-29 Cont ID  
Sent By pvalenti Date 2019-05-29 Time 13:42 Rev Time 0.00
Received By pvalenti Date 2019-05-13 Time 15:18 Sent To  
Notes
2019-05-14 15:18:40R34

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-07-17 Cont ID  
Sent By pvalenti Date 2019-07-17 Time 15:28 Rev Time 0.00
Received By pvalenti Date 2019-07-17 Time 15:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-06-24 Cont ID  
Sent By hmoser Date 2019-06-24 Time 13:23 Rev Time 0.00
Received By hmoser Date 2019-06-24 Time 11:37 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-05-28 Cont ID  
Sent By hmoser Date 2019-05-28 Time 13:09 Rev Time 0.00
Received By hmoser Date 2019-05-28 Time 10:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-07-01 Cont ID  
Sent By gjohnson Date 2019-07-01 Time 12:41 Rev Time 0.00
Received By gjohnson Date 2019-07-01 Time 12:22 Sent To  
Notes
2019-07-01 12:44:02A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-06-11 Cont ID  
Sent By thunt Date 2019-06-11 Time 08:53 Rev Time 0.00
Received By thunt Date 2019-06-11 Time 08:53 Sent To  
Notes
2019-06-11 08:54:00PLEASE REVIEW PROVISO ON PLAN

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-05-16 Cont ID  
Sent By gjohnson Date 2019-05-16 Time 09:15 Rev Time 0.00
Received By gjohnson Date 2019-05-16 Time 07:52 Sent To  
Notes
2019-05-16 09:16:021ST REVIEW: 19050677
  
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLAN SHEETS SHALL BE SIGNED AND SEALED BY ENGINEER
 LISTED ON TOP OF TITLE BLOCK LUIS C MAURY. PER FAC
 61G15-23.003
  
 2. VALUATION FOR THIS JOB APPEARS TO BE LOW PLEASE
 PROVIDE A DETAILED, QUANTITY ESTIMATES, AND/OR BONA
 FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO MEET
 THE
 APPROVAL OF THE BUILDING OFFICIAL. PER WPB AMEND TO FBC
 109.3
  
 3. SHT A1 THE PROPOSED FLOOR PLAN SHOWS AN EXISTING
 WATER HEATER SHT E1 SHOWS A NEW TANKLESS AND THE
 EXISTING TANK TYPE WATER HEATER IS THE OLD HEATER
 REMAINING IN USE PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 4. PLEASE PROVIDE DIMENSIONS OF THE SHOWER SHALL COMPLY
 WITH FBC RES P2708.1
  
 5. PLEASE SHOW CLEANOUT ON THE ISOMETRIC DRAWING WERE
 THE NEW BUILDING DRAIN EXISTS THE STRUCTURE. PER FBC
 RES P3005.2.3
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]