Plan Review Details - Permit 19050376
Plan Review Stops For Permit 19050376
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-07-05 Cont ID  
Sent By rmcdouga Date 2019-07-05 Time 08:14 Rev Time 0.00
Received By rmcdouga Date 2019-07-05 Time 07:27 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-05-22 Cont ID  
Sent By rmcdouga Date 2019-05-22 Time 10:27 Rev Time 0.00
Received By rmcdouga Date 2019-05-22 Time 08:11 Sent To Z
Notes
2019-05-22 10:27:25PLAN
 REVIEW COMMENTS
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SITE PLANS THAT WERE SUBMITTED DO NOT SHOW THE
 PROPOSED STRUCTURE. PROVIDE TWO SETS OF A SITE PLAN OR
 SURVEY THAT SHOWS THE PROPOSED STRUCTURE AND DISTANCES
 TO LOT LINES. FBC 107.2.1
  
 2) THE PROPOSED SIX FOOT HIGH CONSTRUCTION FENCE MAY
 NOT BE ADEQUATE PROTECTION IN AREAS WHERE CONSTRUCTION
 BARRIERS ARE REQUIRED. THE REQUIREMENTS ARE BASED ON
 THE HEIGHT OF THE BUILDING AND THE DISTANCE FROM
 CONSTRUCTION TO THE LOT LINE. SEE FBC 3306.1 PROTECTION
 REQUIRED. PEDESTRIANS SHALL BE PROTECTED DURING
 CONSTRUCTION, REMODELING AND DEMOLITION ACTIVITIES AS
 REQUIRED BY THIS CHAPTER AND TABLE 3306.1. SIGNS SHALL
 BE PROVIDED TO DIRECT PEDESTRIAN TRAFFIC.
  
 2A) FBC 3306.5 BARRIERS.
 BARRIERS SHALL BE NOT LESS THAN 8 FEET (2438 MM) IN
 HEIGHT AND SHALL BE PLACED ON THE SIDE OF THE WALKWAY
 NEAREST THE CONSTRUCTION. BARRIERS SHALL EXTEND THE
 ENTIRE LENGTH OF THE CONSTRUCTION SITE. OPENINGS IN
 SUCH BARRIERS SHALL BE PROTECTED BY DOORS THAT ARE
 NORMALLY KEPT CLOSED.
  
 2B) FBC 3306.6 BARRIER DESIGN.
 BARRIERS SHALL BE DESIGNED TO RESIST LOADS REQUIRED IN
 CHAPTER 16 UNLESS CONSTRUCTED AS FOLLOWS:
 1.BARRIERS SHALL BE PROVIDED WITH 2-INCH BY 4-INCH (51
 MM BY 102 MM) TOP AND BOTTOM PLATES.
 2.THE BARRIER MATERIAL SHALL BE BOARDS NOT LESS THAN
 3/4-INCH (19.1 MM) THICK OR WOOD STRUCTURAL PANELS NOT
 LESS THAN 1/4-INCH (6.4 MM) THICK.
 3.WOOD STRUCTURAL USE PANELS SHALL BE BONDED WITH AN
 ADHESIVE IDENTICAL TO THAT FOR EXTERIOR WOOD STRUCTURAL
 USE PANELS.
 4.WOOD STRUCTURAL USE PANELS 1/4 INCH (6.4 MM) OR 5/16
 INCH (23.8 MM) IN THICKNESS SHALL HAVE STUDS SPACED NOT
 MORE THAN 2 FEET (610 MM) ON CENTER.
 5.WOOD STRUCTURAL USE PANELS 3/8 INCH (9.5 MM) OR 1/2
 INCH (12.7 MM) IN THICKNESS SHALL HAVE STUDS SPACED NOT
 MORE THAN 4 FEET (1219 MM) ON CENTER PROVIDED A 2-INCH
 BY 4-INCH (51 MM BY 102 MM) STIFFENER IS PLACED
 HORIZONTALLY AT MID-HEIGHT WHERE THE STUD SPACING IS
 GREATER THAN 2 FEET (610 MM) ON CENTER.
 6.WOOD STRUCTURAL USE PANELS 5/8 INCH (15.9 MM) OR
 THICKER SHALL NOT SPAN OVER 8 FEET (2438 MM).
  
 2C) FBC 3306.7 COVERED WALKWAYS.
 COVERED WALKWAYS SHALL HAVE A CLEAR HEIGHT OF NOT LESS
 THAN 8 FEET (2438 MM) AS MEASURED FROM THE FLOOR
 SURFACE TO THE CANOPY OVERHEAD. ADEQUATE LIGHTING SHALL
 BE PROVIDED AT ALL TIMES. COVERED WALKWAYS SHALL BE
 DESIGNED TO SUPPORT ALL IMPOSED LOADS. IN NO CASE SHALL
 THE DESIGN LIVE LOAD BE LESS THAN 150 PSF (7.2 KN/M2)
 FOR THE ENTIRE STRUCTURE.
  
 3) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-15 Cont ID  
Sent By jduprey Date 2019-05-15 Time 09:18 Rev Time 0.00
Received By jduprey Date 2019-05-15 Time 09:18 Sent To  
Notes
2019-05-15 09:18:44BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1. PLEASE ADDRESS ZONNING COMMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-05-21 Cont ID  
Sent By pleduc Date 2019-05-21 Time   Rev Time 0.00
Received By pleduc Date 2019-05-21 Time 11:17 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-05-14 Cont ID  
Sent By pleduc Date 2019-05-14 Time   Rev Time 0.00
Received By pleduc Date 2019-05-14 Time 15:48 Sent To B
Notes
2019-05-14 15:54:21THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) AN EMERGENCY ENTRANCE/EXIT IS INDICATED WITH NO
 DIMENSION.
  
 PER NFPA 1
  
 18.2.3 FIRE DEPARTMENT ACCESS ROADS.
 18.2.3.1 REQUIRED ACCESS.
 18.2.3.1.1 APPROVED FIRE DEPARTMENT ACCESS ROADS SHALL
 BE PROVIDED
 FOR EVERY FACILITY, BUILDING, OR PORTION OF A BUILDING
 HEREAFTER
 CONSTRUCTED OR RELOCATED.
 18.2.3.1.2 FIRE DEPARTMENT ACCESS ROADS SHALL CONSIST
 OF ROADWAYS, FIRE
 LANES, PARKING LOT LANES, OR A COMBINATION THEREOF.
  
 18.2.3.4.1 DIMENSIONS.
 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED
 WIDTH OF NOT LESS THAN 20 FT (6.1 M).
  
 PLEASE PROVIDE AN APPLICABLE SIZED OPENING.
  
  
  
 2) IT IS STRONGLY ENCOURAGED TO HAVE THE GATE LOCKED
 WITH A KNOX PADLOCK FOR 24 HE EMERGENCY ACCESS.
  
 18.2.2.2 ACCESS TO GATED SUBDIVISIONS OR DEVELOPMENTS.
 THE AHJ
 SHALL HAVE THE AUTHORITY TO REQUIRE FIRE DEPARTMENT
 ACCESS BE PROVIDED
 TO GATED SUBDIVISIONS OR DEVELOPMENTS THROUGH THE USE
 OF AN APPROVED
 DEVICE OR SYSTEM.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-07-05 Cont ID  
Sent By rmcdouga Date 2019-07-05 Time 08:15 Rev Time 0.00
Received By rmcdouga Date 2019-07-03 Time 15:08 Sent To  
Notes
2019-07-03 15:09:03RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-03 Cont ID  
Sent By lmarchan Date 2019-07-03 Time 15:07 Rev Time 0.00
Received By lmarchan Date 2019-05-17 Time 14:51 Sent To  
Notes
2019-05-22 07:03:505/22 TO RM DESK
  
  
2019-05-20 14:51:36RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-15 Cont ID  
Sent By jduprey Date 2019-05-15 Time 09:18 Rev Time 0.00
Received By jduprey Date 2019-05-07 Time 13:49 Sent To  
Notes
2019-05-08 13:50:13ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2019-07-03 Cont ID  
Sent By jroach Date 2019-07-03 Time 09:37 Rev Time 0.00
Received By jroach Date 2019-07-03 Time 09:37 Sent To  
Notes
2019-07-03 09:38:15ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 07.03.2019
 PERMIT NO.: 19050376
 ___________________________________________
  
 REVIEW STATUS: REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 A. TEMPORARY CONSTRUCTION FENCES MAY NOT BE ERECTED
 UNTIL A DEMOLITION PERMIT OR BUILDING PERMIT FOR THE
 LAND DISTURBING CONSTRUCTION OR LAND DEVELOPMENT
 ACTIVITIES HAS BEEN ISSUED, AND NO MORE THAN TEN DAYS
 PRIOR TO THE COMMENCEMENT OF LAND DISTURBING
 CONSTRUCTION OR LAND DEVELOPMENT ACTIVITIES. IF LAND
 DISTURBING CONSTRUCTION OR LAND DEVELOPMENT ACTIVITIES
 DO NOT COMMENCE WITHIN TEN DAYS OF FENCE INSTALLATION,
 THEN, WITHIN 15 DAYS OF THE TEN-DAY PERIOD, THE FENCE
 SHALL BE REMOVED AND THE SITE SHALL BE TILLED AND
 PLANTED WITH GROUND COVER TO INCLUDE SODDING OR SEEDING
 WHICH SHALL HAVE IRRIGATION AND SHALL BE MAINTAINED IN
 ACCORDANCE WITH SECTIONS 74-2 AND 94-446 OF THIS CODE.
  
 B. IN THE EVENT THAT THE DEMOLITION PERMIT OR BUILDING
 PERMIT EXPIRES, ALL TEMPORARY CONSTRUCTION FENCES SHALL
 BE REMOVED WITHIN TEN DAYS OF THE PERMIT EXPIRATION
 DATE, AND WITHIN 15 DAYS OF REMOVAL OF THE FENCES, THE
 SITE SHALL BE BROUGHT TO GRADE, TILLED AND PLANTED WITH
 GROUND COVER TO INCLUDE SODDING OR SEEDING WHICH SHALL
 HAVE IRRIGATION AND SHALL BE MAINTAINED IN ACCORDANCE
 WITH SECTION 74-2 AND 94-446 OF THIS CODE. ALL
 TEMPORARY CONSTRUCTION FENCING SHALL BE MAINTAINED IN A
 SATISFACTORY MANNER BY THE PERMITTEE OR LANDOWNER,
 DURING THE ENTIRE PERIOD OF THE LAND DISTURBING
 CONSTRUCTION AND LAND DEVELOPMENT ACTIVITIES, TO ENSURE
 ADEQUATE PERFORMANCE, TO PREVENT NUISANCE CONDITIONS
 AND TO MAINTAIN THE PUBLIC HEALTH, SAFETY AND WELFARE.
  
 C. TEMPORARY CONSTRUCTION FENCES SHALL BE INSTALLED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE AND
 OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA)
 STANDARDS.
  
 D. ALL TEMPORARY CONSTRUCTION FENCING SHALL BE
 MAINTAINED IN A SATISFACTORY MANNER BY THE PERMITTEE OR
 LANDOWNER, DURING THE ENTIRE PERIOD OF THE LAND
 DISTURBING CONSTRUCTION AND LAND DEVELOPMENT
 ACTIVITIES, TO ENSURE ADEQUATE PERFORMANCE, TO PREVENT
 NUISANCE CONDITIONS AND TO MAINTAIN THE PUBLIC HEALTH,
 SAFETY AND WELFARE.
  
 E. GATES SHALL BE CHAINED AND LOCKED WITH A LOCK
 SUBSTANTIAL ENOUGH TO ENSURE CLOSURE AND SECURITY WHEN
 WORKERS ARE NOT ON THE JOB SITE.
  
 F. SCREENING GRAPHICS (IF ANY) SHALL BE APPROVED WITH
 THE SUBMITTAL OF A SEPARATE PERMIT APPLICATION PURSUANT
 TO THE PROVISIONS OF CHAPTER 94, ARTICLE XIII, SIGN
 REGULATIONS, OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS OF THIS CODE.
  
 G. ALL WIND SCREENING MATERIALS SHALL BE REMOVED UPON
 THE ISSUANCE OF A HURRICANE WARNING FOR AN AREA
 INCLUDING THE CITY. SCREENING MATERIALS SHALL BE
 REINSTALLED NOT MORE THAN TEN DAYS AFTER THE HURRICANE
 THREAT HAS ENDED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-05-14 Cont ID  
Sent By jroach Date 2019-05-14 Time 10:21 Rev Time 0.00
Received By jroach Date 2019-05-14 Time 10:21 Sent To FIRE
Notes
2019-05-14 10:21:29ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 05.14.2019
 PERMIT NO.: 19050376
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PORTIONS OF THE PROPOSED FENCE ARE SHOWN EXTENDING
 ONTO ADJACENT PROPERTY THAT IS NOT OWNED BY PBAU. SUCH
 FENCING SHALL BE REMOVED FROM THE SCOPE OF THE PERMIT
 APPLICATION.
  
 2. STAFF WOULD LIKE TO DISCUSS THE IMPACT OF THE
 PROPOSED FENCING/CONSTRUCTION ON EXISTING SURFACE
 PARKING THAT IS TO REMAIN, BUT IS SHOWN INSIDE THE
 BOUNDARIES OF THE PROPOSED FENCE.
  
 3. PURSUANT TO SEC. 94-316(D)(2)C.1. OF THE CITY?S
 ZLDRS, TEMPORARY CONSTRUCTION FENCES INSTALLED PURSUANT
 TO THIS SECTION SHALL BE SUBJECT TO THE VISIBILITY AT
 INTERSECTIONS REQUIREMENTS OF SUBSECTION 94-305(E) OF
 THE ZLDRS.
  
 4. PURSUANT TO SEC. 94-316(D)(2)C.4. OF THE CITY?S
 ZLDRS, NO TEMPORARY CONSTRUCTION FENCE MAY ENCROACH
 BEYOND THE SUBJECT PROPERTY LINE. NO FENCE MAY ENCROACH
 UPON THE PUBLIC RIGHT-OF-WAY WITHOUT OBTAINING THE
 APPROPRIATE PUBLIC RIGHT-OF-WAY PERMIT(S). PLEASE
 PROVIDE PROOF OF A RIGHT-OF-WAY PERMIT FOR THAT PORTION
 OF THE FENCING THAT IS SHOWN IN THE SOUTH DIXIE HIGHWAY
 AND PEMBROKE PLACE RIGHTS-OF-WAY, OR REVISE THE PLANS
 ACCORDINGLY.
  
 5. PURSUANT TO SEC. 94-316(D)(2)C.5. OF THE CITY?S
 ZLDRS, SCREENING DETAILS SHALL BE SUBMITTED WITH THE
 TEMPORARY CONSTRUCTION FENCE PERMIT APPLICATION. WIND
 SCREENING SHALL BE SUBSTANTIAL ENOUGH TO AVOID RIPS OR
 TEARS DUE TO WIND OR SUN, AND SHALL HAVE NO LESS THAN
 85 PERCENT OPACITY.
  
 PLEASE NOTE THAT THE FOLLOWING COMMENTS ARE FOR
 INFORMATIONAL PURPOSES ONLY:
  
 A. TEMPORARY CONSTRUCTION FENCES MAY NOT BE ERECTED
 UNTIL A DEMOLITION PERMIT OR BUILDING PERMIT FOR THE
 LAND DISTURBING CONSTRUCTION OR LAND DEVELOPMENT
 ACTIVITIES HAS BEEN ISSUED, AND NO MORE THAN TEN DAYS
 PRIOR TO THE COMMENCEMENT OF LAND DISTURBING
 CONSTRUCTION OR LAND DEVELOPMENT ACTIVITIES. IF LAND
 DISTURBING CONSTRUCTION OR LAND DEVELOPMENT ACTIVITIES
 DO NOT COMMENCE WITHIN TEN DAYS OF FENCE INSTALLATION,
 THEN, WITHIN 15 DAYS OF THE TEN-DAY PERIOD, THE FENCE
 SHALL BE REMOVED AND THE SITE SHALL BE TILLED AND
 PLANTED WITH GROUND COVER TO INCLUDE SODDING OR SEEDING
 WHICH SHALL HAVE IRRIGATION AND SHALL BE MAINTAINED IN
 ACCORDANCE WITH SECTIONS 74-2 AND 94-446 OF THIS CODE.
  
 B. IN THE EVENT THAT THE DEMOLITION PERMIT OR BUILDING
 PERMIT EXPIRES, ALL TEMPORARY CONSTRUCTION FENCES SHALL
 BE REMOVED WITHIN TEN DAYS OF THE PERMIT EXPIRATION
 DATE, AND WITHIN 15 DAYS OF REMOVAL OF THE FENCES, THE
 SITE SHALL BE BROUGHT TO GRADE, TILLED AND PLANTED WITH
 GROUND COVER TO INCLUDE SODDING OR SEEDING WHICH SHALL
 HAVE IRRIGATION AND SHALL BE MAINTAINED IN ACCORDANCE
 WITH SECTION 74-2 AND 94-446 OF THIS CODE. ALL
 TEMPORARY CONSTRUCTION FENCING SHALL BE MAINTAINED IN A
 SATISFACTORY MANNER BY THE PERMITTEE OR LANDOWNER,
 DURING THE ENTIRE PERIOD OF THE LAND DISTURBING
 CONSTRUCTION AND LAND DEVELOPMENT ACTIVITIES, TO ENSURE
 ADEQUATE PERFORMANCE, TO PREVENT NUISANCE CONDITIONS
 AND TO MAINTAIN THE PUBLIC HEALTH, SAFETY AND WELFARE.
  
 C. TEMPORARY CONSTRUCTION FENCES SHALL BE INSTALLED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE AND
 OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA)
 STANDARDS.
  
 D. ALL TEMPORARY CONSTRUCTION FENCING SHALL BE
 MAINTAINED IN A SATISFACTORY MANNER BY THE PERMITTEE OR
 LANDOWNER, DURING THE ENTIRE PERIOD OF THE LAND
 DISTURBING CONSTRUCTION AND LAND DEVELOPMENT
 ACTIVITIES, TO ENSURE ADEQUATE PERFORMANCE, TO PREVENT
 NUISANCE CONDITIONS AND TO MAINTAIN THE PUBLIC HEALTH,
 SAFETY AND WELFARE.
  
 E. GATES SHALL BE CHAINED AND LOCKED WITH A LOCK
 SUBSTANTIAL ENOUGH TO ENSURE CLOSURE AND SECURITY WHEN
 WORKERS ARE NOT ON THE JOB SITE.
  
 F. SCREENING GRAPHICS (IF ANY) SHALL BE APPROVED WITH
 THE SUBMITTAL OF A SEPARATE PERMIT APPLICATION PURSUANT
 TO THE PROVISIONS OF CHAPTER 94, ARTICLE XIII, SIGN
 REGULATIONS, OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS OF THIS CODE.
  
 G. ALL WIND SCREENING MATERIALS SHALL BE REMOVED UPON
 THE ISSUANCE OF A HURRICANE WARNING FOR AN AREA
 INCLUDING THE CITY. SCREENING MATERIALS SHALL BE
 REINSTALLED NOT MORE THAN TEN DAYS AFTER THE HURRICANE
 THREAT HAS ENDED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved