Plan Review Details - Permit 19050303
Plan Review Stops For Permit 19050303
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-02-04 Cont ID  
Sent By jwitmer Date 2020-02-04 Time 14:48 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2019-10-22 Cont ID  
Sent By jwitmer Date 2019-10-22 Time 11:38 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2019-10-22 11:38:21ASBESTOS COMMERCIAL: PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/_DOCUMENTS/ASBESTOS-
 NOTIFICATION-FORM-PBC-FILLABLE-UPDATE-07-30-2015.PDF
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2020-02-04 Cont ID  
Sent By jwitmer Date 2020-02-04 Time 14:48 Rev Time 0.00
Received By jwitmer Date 2020-02-04 Time 14:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2020-01-07 Cont ID  
Sent By jwitmer Date 2020-01-07 Time 08:09 Rev Time 0.00
Received By jwitmer Date 2020-01-07 Time 07:43 Sent To  
Notes
2020-01-07 08:08:102017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19050303
 ADD: 3601 S DIXIE HWY
 CONT: J & V SERVICES
 TEL: 561-601-1614
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: TUES. JAN. 07/ 2020
 ACTION: DENIED
  
 *******************4X FEE / NOTICE!!!!! FLORIDA STATUTE
 553.80(2)(B) **************************
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 1A) COMPLIED.
  
 1B) 4TH REQUEST. THE PERMIT APPLICATION INDICATES UNDER
 THE DESCRIPTION OF WORK, CHANGED(WHITE OUT) THIS REVIEW
 TO EXISTING SINK ON THE BATHROOM. THE PREVIOUS REVIEWS
 STATED: INTERIOR REMODELING AND THE INSTALLATION OF A
 NEW BATHROOM SINK. THERE HAS BEEN A HOLD AND 4 X FEE
 FOR WORK WITHOUT A PERMIT SINCE 4/22/2019 FOR BUILDING,
 NEW WALLS, ELECTRIC AND PLUMBING. THE PLANS INDICATE
 OFFICE AS BUILT BUT THERE IS NO SINK SHOWN ON THE
 PLANS!!!!!! THE PLANS READ AS BUILT BUT SHOULD READ NEW
 WORK (NOT PERMITTED)!!!!!
 COMMENT FROM THE PREVIOUS REVIEWS 1-3.
 SHEET A-101 LIST IN DETAIL # 1 INDICATES 2 NEW OFFICES
 AND NO RESTROOM OR NEW BATHROOM SINK? A RED TAG WAS
 WRITTEN AND LISTED IN COMPUTER ON 4/22/19 FOR NEW
 WALLS, ELECTRIC AND PLUMBING. THERE ARE NO PLUMBING
 SHEETS INCORPORATED IN THESE PLANS? ADDITIONAL
 INFORMATION IS REQUIRED, A DISCREPANCY IN PLANS AND THE
 RED TAG WRITTEN ON 04/22/19 FOR WORK TO BE COVERED
 UNDER THIS PERMIT, DISCREPANCY OF DESCRIPTION OF WORK.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 2) PLUMBING PASSED BUT THE PLANS A SHEETS STILL SHOW
 NEW WORK OFFICES BEING BUILT PLUS E SHEETS AS BUILT
 ADDITIONAL CEILING FANS AND OUTLETS ADDED. THIS IS NOT
 ONLY A SINK BEING CHANGED OUT. AS BUILT SHOULD READ NEW
 WORK (NOT PERMITTED)!!!!!!!!!!
  
 3) 4TH REQUEST. NO MECHANICAL PLANS WERE SUBMITTED A
 REVIEW STOP WAS ADDED BUT COMPLIANCE FOR TOILET ROOMS
 WOULD BE REQUIRED UNDER THE 2017 MECHANICAL CODE
 SECTION 403.3.2.3 LOCAL EXHAUST, AND TABLE 403.3.1.1
 PUBLIC SPACES, TOILET ROOM?S FOOTNOTE (G).
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-10-22 Cont ID  
Sent By jwitmer Date 2019-10-22 Time 11:34 Rev Time 0.00
Received By jwitmer Date 2019-10-22 Time 10:03 Sent To  
Notes
2019-10-22 11:34:172017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19050303
 ADD: 3601 S DIXIE HWY
 CONT: J & V SERVICES
 TEL: 561-601-1614
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 02/ 2019
 ACTION: DENIED
  
 *******************4X FEE / NOTICE!!!!! FLORIDA STATUTE
 553.80(2)(B) **************************
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 1A) 3RD REQUEST. THERE IS A DISCREPANCY BETWEEN THE
 SCOPE OF WORK LISTED ON THE PERMIT APPLICATION
 (INTERIOR REMODELING AND THE INSTALLATION OF A NEW
 BATHROOM SINK) AND THE SCOPE OF WORK AND LOCATION
 LISTED ON SHEET G-001 THE COVERSHEET. SHEET G-001 THE
 COVERSHEET LIST THE WORK BEING COMPLETED IN THE CITY OF
 MIAMI, MIAMI-DADE COUNTY, MIAMI DEPARTMENT PUBLIC
 WORKS, FLOOD ZONES, DEWATERING AND TRENCHING
 REQUIREMENTS UNDER THE HEADINGS OF SITE WORK, GENERAL
 NOTES & UNDERGROUND CONTRACTORS.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED, A
 DISCREPANCY IN PLANS AND PERMIT APPLICATION DESCRIPTION
 OF WORK.
  
 1B) 3RD REQUEST. THE PERMIT APPLICATION INDICATES UNDER
 THE DESCRIPTION OF WORK, INTERIOR REMODELING AND THE
 INSTALLATION OF A NEW BATHROOM SINK. SHEET A-101 LIST
 IN DETAIL # 1 INDICATES 2 NEW OFFICES AND NO RESTROOM
 OR NEW BATHROOM SINK? A RED TAG WAS WRITTEN AND LISTED
 IN COMPUTER ON 4/22/19 FOR NEW WALLS, ELECTRIC AND
 PLUMBING. THERE ARE NO PLUMBING SHEETS INCORPORATED IN
 THESE PLANS? ADDITIONAL INFORMATION IS REQUIRED, A
 DISCREPANCY IN PLANS AND THE RED TAG WRITTEN ON
 04/22/19 FOR WORK TO BE COVERED UNDER THIS PERMIT,
 DISCREPANCY OF DESCRIPTION OF WORK. 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) 3RD REQUEST. PLEASE SEE COMMENTS FROM PLUMBING PLAN
 REVIEWER IF THERE IS TO BE A NEW OR REMODELED RESTROOM.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
 107.3.5.1.1 BUILDING.
 2017 FBC-EXISTING BUILDING CODE 301.1GENERAL. THE
 REPAIR, ALTERATION, CHANGE OF OCCUPANCY, ADDITION OR
 RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY WITH
 ONE OF THE METHODS LISTED IN SECTIONS 301.1.1 THROUGH
 301.1.3 AS SELECTED BY THE APPLICANT. SECTIONS 301.1.1
 THROUGH 301.1.3 SHALL NOT BE APPLIED IN COMBINATION
 WITH EACH OTHER.
  
 3) 3RD REQUEST. NO MECHANICAL PLANS WERE SUBMITTED A
 REVIEW STOP WAS ADDED BUT COMPLIANCE FOR TOILET ROOMS
 WOULD BE REQUIRED UNDER THE 2017 MECHANICAL CODE
 SECTION 403.3.2.3 LOCAL EXHAUST, AND TABLE 403.3.1.1
 PUBLIC SPACES, TOILET ROOM?S FOOTNOTE (G).
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-07-15 Cont ID  
Sent By jwitmer Date 2019-07-15 Time 12:34 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2019-07-15 12:33:302017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19050303
 ADD: 3601 S DIXIE HWY
 CONT: J & V SERVICES
 TEL: 561-601-1614
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 02/ 2019
 ACTION: DENIED
  
 *******************4X FEE / NOTICE!!!!! FLORIDA STATUTE
 553.80(2)(B) *****************************
  
  
  
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 1A) 2ND REQUEST. THERE IS A DISCREPANCY BETWEEN THE
 SCOPE OF WORK LISTED ON THE PERMIT APPLICATION
 (INTERIOR REMODELING AND THE INSTALLATION OF A NEW
 BATHROOM SINK) AND THE SCOPE OF WORK AND LOCATION
 LISTED ON SHEET G-001 THE COVERSHEET. SHEET G-001 THE
 COVERSHEET LIST THE WORK BEING COMPLETED IN THE CITY OF
 MIAMI, MIAMI-DADE COUNTY, MIAMI DEPARTMENT PUBLIC
 WORKS, FLOOD ZONES, DEWATERING AND TRENCHING
 REQUIREMENTS UNDER THE HEADINGS OF SITE WORK, GENERAL
 NOTES & UNDERGROUND CONTRACTORS.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED, A
 DISCREPANCY IN PLANS AND PERMIT APPLICATION DESCRIPTION
 OF WORK.
  
 1B) 2ND REQUEST. THE PERMIT APPLICATION INDICATES UNDER
 THE DESCRIPTION OF WORK, INTERIOR REMODELING AND THE
 INSTALLATION OF A NEW BATHROOM SINK. SHEET A-101 LIST
 IN DETAIL # 1 INDICATES 2 NEW OFFICES AND NO RESTROOM
 OR NEW BATHROOM SINK? A RED TAG WAS WRITTEN AND LISTED
 IN COMPUTER ON 4/22/19 FOR NEW WALLS, ELECTRIC AND
 PLUMBING. THERE ARE NO PLUMBING SHEETS INCORPORATED IN
 THESE PLANS? ADDITIONAL INFORMATION IS REQUIRED, A
 DISCREPANCY IN PLANS AND THE RED TAG WRITTEN ON
 04/22/19 FOR WORK TO BE COVERED UNDER THIS PERMIT,
 DISCREPANCY OF DESCRIPTION OF WORK. 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) 2ND REQUEST. PLEASE SEE COMMENTS FROM PLUMBING PLAN
 REVIEWER IF THERE IS TO BE A NEW OR REMODELED RESTROOM.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
 107.3.5.1.1 BUILDING.
 2017 FBC-EXISTING BUILDING CODE 301.1GENERAL. THE
 REPAIR, ALTERATION, CHANGE OF OCCUPANCY, ADDITION OR
 RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY WITH
 ONE OF THE METHODS LISTED IN SECTIONS 301.1.1 THROUGH
 301.1.3 AS SELECTED BY THE APPLICANT. SECTIONS 301.1.1
 THROUGH 301.1.3 SHALL NOT BE APPLIED IN COMBINATION
 WITH EACH OTHER.
  
 3) 2ND REQUEST. NO MECHANICAL PLANS WERE SUBMITTED NOR
 REVIEW STOP ADDED BUT COMPLIANCE FOR TOILET ROOMS WOULD
 BE REQUIRED UNDER THE 2017 MECHANICAL CODE SECTION
 403.3.2.3 LOCAL EXHAUST, AND TABLE 403.3.1.1 PUBLIC
 SPACES, TOILET ROOM?S FOOTNOTE (G).
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-03 Cont ID  
Sent By jwitmer Date 2019-06-03 Time 09:38 Rev Time 0.00
Received By jwitmer Date 2019-06-03 Time 08:44 Sent To  
Notes
2019-06-03 09:38:112017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19050303
 ADD: 3601 S DIXIE HWY
 CONT: J & V SERVICES
 TEL: 561-601-1614
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 02/ 2019
 ACTION: DENIED
  
 1A) THERE IS A DISCREPANCY BETWEEN THE SCOPE OF WORK
 LISTED ON THE PERMIT APPLICATION (INTERIOR REMODELING
 AND THE INSTALLATION OF A NEW BATHROOM SINK) AND THE
 SCOPE OF WORK AND LOCATION LISTED ON SHEET G-001 THE
 COVERSHEET. SHEET G-001 THE COVERSHEET LIST THE WORK
 BEING COMPLETED IN THE CITY OF MIAMI, MIAMI-DADE
 COUNTY, MIAMI DEPARTMENT PUBLIC WORKS, FLOOD ZONES,
 DEWATERING AND TRENCHING REQUIREMENTS UNDER THE
 HEADINGS OF SITE WORK, GENERAL NOTES & UNDERGROUND
 CONTRACTORS.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED, A
 DISCREPANCY IN PLANS AND PERMIT APPLICATION DESCRIPTION
 OF WORK.
  
 1B) THE PERMIT APPLICATION INDICATES UNDER THE
 DESCRIPTION OF WORK, INTERIOR REMODELING AND THE
 INSTALLATION OF A NEW BATHROOM SINK. SHEET A-101 LIST
 IN DETAIL # 1 INDICATES 2 NEW OFFICES AND NO RESTROOM
 OR NEW BATHROOM SINK? A RED TAG WAS WRITTEN AND LISTED
 IN COMPUTER ON 4/22/19 FOR NEW WALLS, ELECTRIC AND
 PLUMBING. THERE ARE NO PLUMBING SHEETS INCORPORATED IN
 THESE PLANS? ADDITIONAL INFORMATION IS REQUIRED, A
 DISCREPANCY IN PLANS AND THE RED TAG WRITTEN ON
 04/22/19 FOR WORK TO BE COVERED UNDER THIS PERMIT,
 DISCREPANCY OF DESCRIPTION OF WORK. 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) PLEASE SEE COMMENTS FROM PLUMBING PLAN REVIEWER IF
 THERE IS TO BE A NEW OR REMODELED RESTROOM.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
 107.3.5.1.1 BUILDING.
 2017 FBC-EXISTING BUILDING CODE 301.1GENERAL. THE
 REPAIR, ALTERATION, CHANGE OF OCCUPANCY, ADDITION OR
 RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY WITH
 ONE OF THE METHODS LISTED IN SECTIONS 301.1.1 THROUGH
 301.1.3 AS SELECTED BY THE APPLICANT. SECTIONS 301.1.1
 THROUGH 301.1.3 SHALL NOT BE APPLIED IN COMBINATION
 WITH EACH OTHER.
  
 3) NO MECHANICAL PLANS WERE SUBMITTED NOR REVIEW STOP
 ADDED BUT COMPLIANCE FOR TOILET ROOMS WOULD BE REQUIRED
 UNDER THE 2017 MECHANICAL CODE SECTION 403.3.2.3 LOCAL
 EXHAUST, AND TABLE 403.3.1.1 PUBLIC SPACES, TOLIET
 ROOMS FOOTNOTE (G).
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-12-31 Cont ID  
Sent By jpearson Date 2019-12-31 Time 08:44 Rev Time 0.00
Received By jpearson Date 2019-12-31 Time 08:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-10-23 Cont ID  
Sent By jpearson Date 2019-10-23 Time 08:22 Rev Time 0.00
Received By jpearson Date 2019-10-23 Time 08:22 Sent To  
Notes
2019-10-23 07:16:00CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. SCOPE OF WORK IS CONFUSING AND DOES NOT DETAIL THE
 PROPOSED WORK. THE PLAN SHOWS EVERYTHING AS EXISTING.
 WHAT WORK IS PROPOSED? PROVIDE CLARIFICATION AND PLAN
 DETAILING PROPOSED WORK. WPB FBC 107.2.1 (NOT
 ADDRESSED.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-07-16 Cont ID  
Sent By jpearson Date 2019-07-16 Time 11:20 Rev Time 0.00
Received By jpearson Date 2019-07-16 Time 10:29 Sent To I
Notes
2019-07-16 11:05:34CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. SCOPE OF WORK IS CONFUSING AND DOES NOT DETAIL THE
 PROPOSED WORK. THE PLAN SHOWS EVERYTHING AS EXISTING.
 WHAT WORK IS PROPOSED? PROVIDE CLARIFICATION AND PLAN
 DETAILING PROPOSED WORK. WPB FBC 107.2.1 (NOT
 ADDRESSED.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-30 Cont ID  
Sent By jpearson Date 2019-05-30 Time 10:28 Rev Time 0.00
Received By jpearson Date 2019-05-30 Time 08:12 Sent To  
Notes
2019-05-30 10:28:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SCOPE PF WORK IS CONFUSING AND DOES NOT DETAIL THE
 PROPOSED WORK. THE PLAN SHOWS EVERYTHING AS EXISTING.
 WHAT WORK IS PROPOSED? PROVIDE CLARIFICATION AND PLAN
 DETAILING PROPOSED WORK. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-10-11 Cont ID  
Sent By pleduc Date 2019-10-11 Time   Rev Time 0.00
Received By pleduc Date 2019-10-11 Time 13:48 Sent To  
Notes
2019-10-11 13:51:03THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET E 101 - THERE ARE NO INDICATIONS OF EXISTING
 OR PROPOSED EXIT SIGNS WITH THE LARGE ROOM AREA.
  
 PLEASE ENSURE APPLICABLE EXIT SIGNAGE AT ONE OR BOTH
 DOORS HAT LEAD TO AND EXIT.
  
 A FIRE INSPECTOR WILL VERIFY ON FIRE INSPECTIONS
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-06-25 Cont ID  
Sent By pleduc Date 2019-06-25 Time   Rev Time 0.00
Received By pleduc Date 2019-06-25 Time 12:11 Sent To  
Notes
2019-06-25 12:15:49THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET E 101 - THERE ARE NO INDICATIONS OF EXISTING
 OR PROPOSED EXIT SIGNS WITH THE LARGE ROOM AREA.
  
 PLEASE ENSURE APPLICABLE EXIT SIGNAGE AT ONE OR BOTH
 DOORS HAT LEAD TO AND EXIT.
  
 A FIRE INSPECTOR WILL VERIFY ON FIRE INSPECTIONS
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-05-14 Cont ID  
Sent By pleduc Date 2019-05-14 Time   Rev Time 0.00
Received By pleduc Date 2019-05-14 Time 15:08 Sent To  
Notes
2019-05-14 15:18:32THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET E 101 - THERE ARE NO INDICATIONS OF EXISTING
 OR PROPOSED EXIT SIGNS WITH THE LARGE ROOM AREA.
  
 PLEASE ENSURE APPLICABLE EXIT SIGNAGE AT ONE OR BOTH
 DOORS HAT LEAD TO AND EXIT.
  
 A FIRE INSPECTOR WILL VERIFY ON FIRE INSPECTIONS
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2020-02-04 Time   Rev Time 0.00
Received By lmarchan Date 2020-01-30 Time 13:39 Sent To  
Notes
2020-01-31 13:39:58REUSB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2020-01-07 Time   Rev Time 0.00
Received By lmarchan Date 2019-12-31 Time 16:25 Sent To  
Notes
2020-01-02 16:26:00RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-10-23 Time   Rev Time 0.00
Received By lmarchan Date 2019-10-07 Time 13:41 Sent To  
Notes
2019-10-08 13:42:02B12

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-07-16 Time   Rev Time 0.00
Received By lmarchan Date 2019-06-21 Time 14:31 Sent To  
Notes
2019-06-24 14:31:52B06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-03 Cont ID  
Sent By jwitmer Date 2019-06-03 Time 09:38 Rev Time 0.00
Received By jwitmer Date 2019-05-07 Time 14:21 Sent To  
Notes
2019-05-08 14:21:59B22

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2020-02-04 Cont ID  
Sent By ccole Date 2020-02-04 Time 15:14 Rev Time 0.00
Received By ccole Date 2020-02-04 Time 15:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2020-01-06 Cont ID  
Sent By ccole Date 2020-01-06 Time 08:31 Rev Time 0.00
Received By ccole Date 2020-01-06 Time 08:31 Sent To B
Notes
2020-01-06 08:33:233RD REVIEW
 PERMIT #19050303
 1/6/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 NO REPSONSE TO COMMENTS FROM THE 1ST & 2ND REVIEWS
 LISTED BELOW HAVE BEEN PROVIDED. PLEASE COMPLY
  
 1) THE INSTALLING CONTRACTOR OR DESIGNER OF RECORD
 SHALL PROVIDE A TITLE BLOCK AND SIGNATURE ON THE
 MECHANICAL PLAN- SECTION 107.2.1 WPB. IF THE PLAN
 DESIGNER IS A FL. LICENSED ARCHITECT OR ENGINEER HE/SHE
 SHALL ALSO PROVIDE AN ORIGINAL SEAL AND WET SIGNATURE
 PER FL. STATUE AND SECTIONS 61G15-16.003 AND 23.002
 FAC.
  
 2) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS- PLEASE
 COMPLY.1) THE PLAN SHOWS TWO NEW OFFICES TO BE
 CONSTRUCTED. REFER TO SECTION 809.2 FBC-17 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR THE OFFICES PER TABLE 403.3.1.1 FBC-17
 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES THE
 REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 3) RETURN AIR SYSTEM NOT SHOWN- SECTION 601.6 FBC M.
  
 4) INDICATE THE TYPE OF DUCTWORK TO BE INSTALLED-
 SECTION 603 FBC M.
  
 5) THE INCREASE IN VALUE FOR THE MECHANICAL WORK WAS
 NOT PROVIDED ON THE RESUBMITTAL APPLICATION- SECTION
 109.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-10-16 Cont ID  
Sent By ccole Date 2019-10-16 Time 11:56 Rev Time 0.00
Received By ccole Date 2019-10-16 Time 11:52 Sent To  
Notes
2019-10-16 12:03:251ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19050303
 10/16/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE INSTALLING CONTRACTOR OR DESIGNER OF RECORD
 SHALL PROVIDE A TITLE BLOCK AND SIGNATURE ON THE
 MECHANICAL PLAN- SECTION 107.2.1 WPB. IF THE PLAN
 DESIGNER IS A FL. LICENSED ARCHITECT OR ENGINEER HE/SHE
 SHALL ALSO PROVIDE AN ORIGINAL SEAL AND WET SIGNATURE
 PER FL. STATUE AND SECTIONS 61G15-16.003 AND 23.002
 FAC.
  
 2) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS- PLEASE
 COMPLY.1) THE PLAN SHOWS TWO NEW OFFICES TO BE
 CONSTRUCTED. REFER TO SECTION 809.2 FBC-17 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR THE OFFICES PER TABLE 403.3.1.1 FBC-17
 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES THE
 REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 3) RETURN AIR SYSTEM NOT SHOWN- SECTION 601.6 FBC M.
  
 4) INDICATE THE TYPE OF DUCTWORK TO BE INSTALLED-
 SECTION 603 FBC M.
  
 5) THE INCREASE IN VALUE FOR THE MECHANICAL WORK WAS
 NOT PROVIDED ON THE RESUBMITTAL APPLICATION- SECTION
 109.3 WPB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-07-16 Cont ID  
Sent By ccole Date 2019-07-16 Time 09:24 Rev Time 0.00
Received By ccole Date 2019-07-16 Time 09:24 Sent To  
Notes
2019-07-16 09:35:261ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19050303
 7/16/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PLAN SHOWS TWO NEW OFFICES TO BE CONSTRUCTED.
 REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 OFFICES PER TABLE 403.3.1.1 FBC-17 MECHANICAL. PROVIDE
 A SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED
 CFMS OF OUTDOOR AIR.
  
 2) INDICATE HOW AIR IS BEING SUPPLIED TO AND RETURNED
 FROM THE NEW OFFICES- SHOW THE REQUIRED DUCT
 ALTERATIONS- SECTION 603.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-11-06 Cont ID  
Sent By gjohnson Date 2019-11-06 Time 14:30 Rev Time 0.00
Received By gjohnson Date 2019-11-06 Time 14:30 Sent To  
Notes
2019-11-06 14:32:30ENGINEER OF RECORD PLACED NOTE ON PLAN 11/6/19
 APPROVED FOR REPLACEMENT OF 1 EXISTING LAVATORY SINK
 ONLY
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2019-10-21 Cont ID  
Sent By gjohnson Date 2019-10-21 Time 16:36 Rev Time 0.00
Received By gjohnson Date 2019-10-21 Time 14:57 Sent To  
Notes
2019-10-21 17:04:543RD REVIEW: 19050677
  
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS: IT DOES NOT APPEAR THAT THE PLUMBING
 COMMENTS HAVE BEEN ADDRESSED. WITH NO RESPONSE LETTER
 IT IS DIFFICULT TO DETERMINE WHAT . IF ON THE THIRD THE
 SAME COMMENTS HAVE NOT BEEN REPLIED TO 3X THE PLAN
 REVIEW FEE WILL BE CHARGED. PLEASE CONTACT REVIEWER
 PRIOR TO RESUMITTAL TO CLARIFY SCOPE OF WORK SEE
 CONTACT INFO BELOW.
  
 1. PROVIDE FLOOR PLAN SHOWING LOCATION OF NEW BATHROOM
 LAVATORY. PER WPB AMEND TO FBC 107.2.1
  
 2. PLEASE CLARIFY IS THIS A REPLACEMENT OF EXITING SINK
 ARE ARE YOU ADDING A SINK. PER WPB AMEND TO FBC 107.2.1
  
 3. PROVIDE DETAILS FOR THE SINK THAT MEET FBC ACC 606.2
 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING WITH
 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE AND
 TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 4. PROVIDE WATER AND SANITARY ISOMETRIC DRAWINGS. PER
 WPB AMEND TO FBC 107.3.5.1.3(13)
  
 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-07-02 Cont ID  
Sent By jesmith Date 2019-07-02 Time 10:07 Rev Time 0.00
Received By jesmith Date 2019-07-02 Time 10:06 Sent To  
Notes
2019-07-02 10:07:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 30A
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 PLUMBING COMMEMTS: DENIED
 PLEASE NOTE THAT ALL COMMENTS FROM THE FIRST REVIEW
 HAVE NOT BEEN RESPONDED TO. SEE BELOW AND COMPLY PER
 WPB FBC 107.2.1
  
 1. PROVIDE FLOOR PLAN SHOWING LOCATION OF NEW BATHROOM
 LAVATORY. PER WPB AMEND TO FBC 107.2.1
 2. PLEASE CLARIFY IS THIS A REPLACEMENT OF EXITING SINK
 ARE ARE YOU ADDING A SINK. PER WPB AMEND TO FBC 107.2.1
 3. PROVIDE DETAILS FOR THE SINK THAT MEET FBC ACC 606.2
 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING WITH
 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE AND
 TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
 4. PROVIDE WATER AND SANITARY ISOMETRIC DRAWINGS. PER
 WPB AMEND TO FBC 107.3.5.1.3(13)
 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19050303 3601 S DIXIE HWY
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-05-16 Cont ID  
Sent By gjohnson Date 2019-05-16 Time 09:59 Rev Time 0.00
Received By gjohnson Date 2019-05-16 Time 07:51 Sent To  
Notes
2019-05-16 09:59:191ST REVIEW: 19050677
  
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE FLOOR PLAN SHOWING LOCATION OF NEW BATHROOM
 LAVATORY. PER WPB AMEND TO FBC 107.2.1
  
 2. PLEASE CLARIFY IS THIS A REPLACEMENT OF EXITING SINK
 ARE ARE YOU ADDING A SINK. PER WPB AMEND TO FBC 107.2.1
  
 3. PROVIDE DETAILS FOR THE SINK THAT MEET FBC ACC 606.2
 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING WITH
 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE AND
 TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 4. PROVIDE WATER AND SANITARY ISOMETRIC DRAWINGS. PER
 WPB AMEND TO FBC 107.3.5.1.3(13)
  
 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]