Plan Review Details - Permit 19050176
Plan Review Stops For Permit 19050176
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-11-18 Cont ID  
Sent By cthroop Date 2019-11-18 Time 13:21 Rev Time 0.00
Received By cthroop Date 2019-11-18 Time 07:38 Sent To  
Notes
2019-11-18 13:29:44PLAN REVIEW - BUILDING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1, DESIGNER'S SEAL IS MISSING ON ALL PLAN PAGES.
 RE-SUBMITTAL REQUIRED.
 FBC 107.1 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT,
 INTERIOR DESIGNER, LANDSCAPE ARCHITECT, OR ENGINEER
 LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR
 DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA
 STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR
 ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA
 STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE.
  
 2. NOTICE ONLY - SINGLE HUNG WINDOWS ARE NON-IMPACT
 RATED. SHUTTER SCHEDULE AND PRODUCT APPROVAL LOCATED ON
 PLAN PAGE'S 21 & 22 OF 26. DESIGNER'S SEAL IS MISSING.
  
 3. PROVIDE PRODUCT APPROVALS FOR WINDOW MULLIONS AND
 EXTERIOR DOORS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW MULLION AND DOOR
 SUBMITTALS.
  
 4. ROOFING PERMIT REQUIRED. PROVIDE PRODUCT APPROVALS
 FOR PROPOSED ROOFING SYSTEM COMPONENTS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 5. DEMO PERMIT REQUIRED FOR EXISTING HOUSE - COPY OF
 DEMO CHECKLIST WITH ASBESTOS REQUIREMENTS INCLUDED IN
 SUBMITAL FOR YOUR REVIEW.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-08-19 Cont ID  
Sent By cthroop Date 2019-08-19 Time 16:55 Rev Time 0.00
Received By cthroop Date 2019-08-16 Time 16:10 Sent To  
Notes
2019-08-19 17:02:10BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ADDRESS 1ST BLDG. REVIEW COMMENTS AND RE-SUBMIT. CT
2019-08-13 09:24:32CHECKED IN WRONG STOP BY ACCIDENT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-23 Cont ID  
Sent By pvalenti Date 2019-05-23 Time 16:10 Rev Time 0.00
Received By pvalenti Date 2019-05-23 Time 06:52 Sent To  
Notes
2019-05-23 16:40:33***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING PLAN REVIEW (1ST REVIEW) DENIED:
  
 FBC B 107: THE SUBMITTED PLANS ARE NOT COMPLETE. PLEASE
 PROVIDE THE FOLLOWING:
  
 1. A SURVEY APPROVED BY A LICENSED SURVEYOR COMPLETE
 WITH PROPOSED LOCATION OF HOUSE, ELEVATIONS, SETBACKS,
 AND ALL OTHER REQUIRED INFORMATION.
 2. A SITE PLAN PAGE AS PART OF THE PLANS.
 3. DESIGNER OF RECORD SIGNATURES AND SEALS ON ALL PAGES
 PER THE FLORIDA STATE STATUTES CHAPTER 471/FL ADMIN.
 RULES 61G15-23.001 TO 61G15-23.003 AND CHAPTER 481/FL
 ADMIN. RULE 61G1-16.004.
 4. MORE INFORMATION ON THE EXISTING SITE; IT APPEARS
 THAT THERE IS AN EXISTING STRUCTURE ON THIS LOT AND
 THERE ARE NO INDICATIONS OF A DEMO PERMIT ON RECORD.
 PLEASE CLARIFY.
 5. A WINDOW/DOOR SUBMITTAL WITH PRODUCT APPROVALS.
 6. THE PRODUCT AND CONNECTION DETAILS ARE REQUIRED FOR
 REINFORCING STEEL (SCREW-IN) CONNECTIONS BETWEEN WALLS
 AND SLAB.
 7. THE PLAN DESIGN AND NOTES NEED TO BE REVIEWED,
 UPDATED TO THE CURRENT CODE (2017 SIXTH EDITION OF THE
 FLORIDA BUILDING CODE) AND APPROVED.
 8. THE DETAILS THAT DO NOT RELATE TO THIS SPECIFIC
 PROJECT NEED TO BE DELETED FROM PLAN PAGES.
  
  
 NOTES:
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-11-20 Cont ID  
Sent By jpearson Date 2019-11-20 Time 07:23 Rev Time 0.00
Received By jpearson Date 2019-11-20 Time 07:03 Sent To  
Notes
2019-11-20 07:23:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. THE # 6 EQUIPMENT GROUNDING CONDUCTOR SHOULD NOT BE
 INCLUDED IN THE CONDUIT FROM FROM THE METER TO THE MAIN
 DISCONNECT SWITCH. PROVIDE CORRECTION. NEC 250.6; FBC
 RE E3610.4 (NOT CORRECTED.)
 9. CORRECTED.
 10. CORRECTED.
 11. CORRECTED.
 12. CORRECTED.
 13. CORRECTED.
 14. CORRECTED.
 15. CORRECTED.
  
 NEW COMMENTS:
  
 16. CIRCUIT NUMBER 31 SHOWS A 20 AMP CIRCUIT FOR
 BATHROM AND PATIO OUTLETS. PER CODE, A MINIMUM OF ONE
 20 AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY
 BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE
 NO OTHER OUTLETS. PROVIDE CORRECTION. NEC 210.11(C)(3)
 , FBC RE E3703.4
 17. NEW ELECTRICAL SHEETS WERE NOT INSTALLED INTO THE
 PLAN SET. THE OLD SHEETS MUST BE REMOVED AND THE NEW
 SHEETS INSTALLED. IT IS THE RESPONSIBILITY OF THE
 PERSON THAT SUBMITS CORRECTIONS TO INSTALL THESE SHEETS
 INTO THE PLAN SET. PLAN CANNOT BE APPROVED WITH OLD
 SHEETS. PROVIDE CORRECTION. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-08-13 Cont ID  
Sent By jpearson Date 2019-08-13 Time 09:23 Rev Time 0.00
Received By jpearson Date 2019-08-13 Time 09:23 Sent To  
Notes
2019-08-13 08:41:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR
 THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC
 107.1, 107.2.1, 107.3.5.1.2 (A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. PROVIDE CORRECTION. WPB FBC 107.1; FS
 471/481)
 2. CORRECTED.
 3. CORRECTED.
 4. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1 (NOT PROVIDED.)
 5. CORRECTED.
 6. PROVIDE LOCATION OF ELECTRICAL SERVICE AND
 ELECTRICAL PANEL TO CONFIRM CODE COMPLIANCE. WPB FBC
 107.2.1 (LOCATION OF SERVICE NOT PROVIDED.)
 7. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 9NOT
 PROVIDED. PLAN SHOWS DETAILS FROM THE 1993 NEC, WHICH
 IS NOT THE CURRENT CODE. ALSO, RISER DIAGRAM QUOTES NEC
 250.81, WHICH DOES NOT EXIST. PROVIDE UPDATES TO THESE
 ITEMS AND PROVIDE THE IBTP PER COMMENT.)
 8. THE # 6 EQUIPMENT GROUNDING CONDUCTOR SHOULD NOT BE
 INCLUDED IN THE CONDUIT FROM FROM THE METER TO THE MAIN
 DISCONNECT SWITCH. PROVIDE CORRECTION. NEC 250.6; FBC
 RE E3610.4 (NOT CORRECTED.)
 9. CORRECTED.
 10. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1 ( NOT
 CORRECT. A SMOKE ALARM IS REQUIRED OUTSIDE THE SLEEPING
 AREA, AND A CARBON MONOXIDE ALARM IS REQUIRED WITHIN 10
 FEET OF EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE
 R315.1)
 11. CORRECTED.
 12. CORRECTED.
 13. CORRECTED.
 14. CORRECTED.
 15. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-15 Cont ID  
Sent By jpearson Date 2019-05-15 Time 07:25 Rev Time 0.00
Received By jpearson Date 2019-05-15 Time 06:13 Sent To  
Notes
2019-05-15 06:53:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR
 THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC
 107.1, 107.2.1, 107.3.5.1.2
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 3. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9; FBC RE E3606.3
 4. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 5. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE
 OUTLETS IN GARAGE, INCLUDING GARAGE DOOR OPENER.
 PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2
 6. PROVIDE LOCATION OF ELECTRICAL SERVICE AND
 ELECTRICAL PANEL TO CONFIRM CODE COMPLIANCE. WPB FBC
 107.2.1
 7. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 8. THE # 6 EQUIPMENT GROUNDING CONDUCTOR SHOULD NOT BE
 INCLUDED IN THE CONDUIT FROM FROM THE METER TO THE MAIN
 DISCONNECT SWITCH. PROVIDE CORRECTION. NEC 250.6; FBC
 RE E3610.4
 9. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS PER THE METHOD DESCRIBED IN THE FBC RESIDENTIAL.
 THE 5 AC UNITS TOTAL 8700 VA AND THE LARGEST OF THE
 LOADS MUST BE USED. THE LAUNDRY CIRCUIT SHOULD BE
 CALCULATED AT 1500 VA. THE SMALL APPLIANCE CIRCUITS
 SHOULD BE CALCULATED AT 1500 VA EACH. PROVIDE SPEC
 SHEETS FOR AC UNITS TO CONFIRM STATED LOAD. NEC 110.3,
 220; FBC RE E3602.2; WPB FBC 107.2.1
 10. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1
 11. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
 12. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7
 13. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12
 14. THE WALL SPACING REQUIREMENTS FOR KITCHEN COUNTER
 SPACE STATE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED
 SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24
 INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET
 IN THAT SPACE. THE PLAN PROVIDED DOES NOT MEET THIS
 CODE IN SOME AREAS. PROVIDE CORRECTION. NEC
 210.52(C)(1); FBC RE E3901.4
 15. RECEPTACLES INSTALLED TO SERVE THE COUNTER TOP IN
 KITCHEN REQUIRE GFCI PROTECTION, INCLUDING THE ISLAND.
 PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.6
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-11-27 Cont ID  
Sent By cpuell Date 2019-11-27 Time 15:34 Rev Time 0.00
Received By cpuell Date 2019-10-31 Time 15:02 Sent To  
Notes
2019-11-01 15:02:23R30

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-08-23 Cont ID  
Sent By lmarchan Date 2019-08-23 Time 15:17 Rev Time 0.00
Received By lmarchan Date 2019-08-12 Time 13:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-24 Cont ID  
Sent By cthroop Date 2019-05-24 Time 16:40 Rev Time 0.00
Received By cthroop Date 2019-05-09 Time 10:11 Sent To  
Notes
2019-05-07 10:11:36R07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-05-23 Cont ID  
Sent By pvalenti Date 2019-05-23 Time 16:02 Rev Time 0.00
Received By pvalenti Date 2019-05-23 Time 16:00 Sent To  
Notes
2019-05-23 16:05:48***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 DENIED:
  
 IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-11-18 Cont ID  
Sent By cthroop Date 2019-11-18 Time 13:18 Rev Time 0.00
Received By cthroop Date 2019-11-18 Time 07:38 Sent To  
Notes
2019-11-18 13:21:22PLAN REVIEW - MECHANICAL
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. MECHANICAL DESIGN IS APPROVED.
 2. DESIGNER'S SEAL IS MISSING FORM PLAN PAGE 07 OF 26.
 RE-SUBMIT NEW PLAN PAGE WITH SIGNATURE AND SEAL OF
 DESIGNER.
 FBC 107.1 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT,
 INTERIOR DESIGNER, LANDSCAPE ARCHITECT, OR ENGINEER
 LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR
 DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA
 STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR
 ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA
 STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE.
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-08-19 Cont ID  
Sent By cthroop Date 2019-08-19 Time 17:02 Rev Time 0.00
Received By cthroop Date 2019-08-16 Time 16:11 Sent To  
Notes
2019-08-19 17:02:47SEE 1ST MECH. REVIEW COMMENTS. CT

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-05-24 Cont ID  
Sent By cthroop Date 2019-05-24 Time 16:31 Rev Time 0.00
Received By cthroop Date 2019-05-23 Time 07:08 Sent To  
Notes
2019-05-24 16:40:41MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 1. DESIGN PROFESSIONALS SIGNATURE AND SEAL IS INVALID.
 FBC 107.1 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT,
 INTERIOR DESIGNER, LANDSCAPE ARCHITECT, OR ENGINEER
 LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR
 DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA
 STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR
 ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA
 STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE.
  
 2. PROVIDE ENERGY SUBMITTAL WITH LOAD CALCULATIONS.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
 M1401.3EQUIPMENT AND APPLIANCE SIZING.
 HEATING AND COOLING EQUIPMENT AND APPLIANCES SHALL BE
 SIZED IN ACCORDANCE WITH ACCA MANUAL S OR OTHER
 APPROVED SIZING METHODOLOGIES BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
  
 3. PROVIDE TAMPER PROOF PORTS AT CU.
 M1411.8 LOCKING ACCESS PORT CAPS.
 REFRIGERANT CIRCUIT ACCESS PORTS LOCATED OUTDOORS SHALL
 BE FITTED WITH LOCKING-TYPE TAMPER-RESISTANT CAPS OR
 SHALL BE OTHERWISE SECURED TO PREVENT UNAUTHORIZED
 ACCESS.
 EXCEPTION: NO LOCKING-TYPE TAMPER-RESISTANT CAPS ARE
 REQUIRED IF PORTS ARE LOCATED INSIDE THE CONDENSING
 UNIT CABINET.
  
 4. PROVIDE CONDENSATE DRAIN DETAIL.
 M1411.3 CONDENSATE DISPOSAL.
 CONDENSATE FROM COOLING COILS AND EVAPORATORS SHALL BE
 CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED PLACE
 OF DISPOSAL. SUCH PIPING SHALL MAINTAIN A MINIMUM
 HORIZONTAL SLOPE IN THE DIRECTION OF DISCHARGE OF NOT
 LESS THAN 1/8 UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (1-PERCENT SLOPE). CONDENSATE SHALL NOT DISCHARGE INTO
 A STREET, ALLEY OR OTHER AREAS WHERE IT WOULD CAUSE A
 NUISANCE.
  
 5. PROVIDE SERVICE OUTLET AT EXTERIOR CU'S.
 PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR SERVICING
 OF A/C EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER
 CODE. NEC 210.63; FBC RE E3901.12
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-11-15 Cont ID  
Sent By gjohnson Date 2019-11-15 Time 10:54 Rev Time 0.00
Received By gjohnson Date 2019-11-15 Time 09:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-08-19 Cont ID  
Sent By cthroop Date 2019-08-19 Time 17:03 Rev Time 0.00
Received By cthroop Date 2019-08-16 Time 16:11 Sent To  
Notes
2019-08-19 17:03:25SEE 2ND BLDG. REVIEW COMMENTS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-05-13 Cont ID  
Sent By thunt Date 2019-05-13 Time 15:15 Rev Time 0.00
Received By thunt Date 2019-05-13 Time 12:54 Sent To  
Notes
2019-05-13 15:15:49PLUMBING 1ST REVIEW**DENIED**
  
 1) PLANS SHALL BE SIGNED AND SEAL BY DESIGN
 PROFESSIONAL. FAC 471, 481
  
 2) PROVIDE PIPE SIZES ON PLUMBING ISOMETRIC DRAWING.
 FBC 107.3.5
  
 3) MASTER BATHROOM ISOMETRIC SHOW 2 LAV AND NO TUB.
 PLEASE CORRECT. FBC WPB ADMIN. 107.1
  
 4) SHT #3 PLUMBING NOT #2 AND #3 CALL OUT PVC PIPING TO
 BE USED ON THE EXTERIOR AND HOT WATER. PVC PIPING IS
 NOT PERMITTED/ APPROVED TO USED FOR WATER DISTRIBUTION/
 HOT WATER PIPING. FBC-P 604.4
  
 5) SHT #3 CALLS UP FOR 1/2" INSULATION. PLEASE CORRECT
 AND SHOW AS R-3 MIN ON ALL HOT WATER PIPING NOT IN THE
 CONDITIONED SPACE. FBC-ENERGY R403.5.3
  
 6) PROVIDE R405-2017 OR R402-2017 ENERGY FORM.
  
 7) PROVIDE SHOWER PAN DETAIL SHOWING 2% MIN AND CALL
 OUT MATERIAL TO BE USED. FBC-R P 2709.3
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  
  
  
  
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2019-11-18 Cont ID  
Sent By cthroop Date 2019-11-18 Time 13:39 Rev Time 0.00
Received By cthroop Date 2019-11-18 Time 07:38 Sent To  
Notes
2019-11-18 13:41:32PLAN REVIEW - ROOFING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.
  
 2, PROVIDE PRODUCT APPROVALS FOR PROPOSED ROOFING
 SYSTEM COMPONENTS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2019-08-19 Cont ID  
Sent By cthroop Date 2019-08-19 Time 17:02 Rev Time 0.00
Received By cthroop Date 2019-08-16 Time 16:10 Sent To  
Notes
2019-08-19 17:03:08SEE 2ND BLDG. REVIEW COMMENTS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-05-23 Cont ID  
Sent By pvalenti Date 2019-05-23 Time 16:06 Rev Time 0.00
Received By pvalenti Date 2019-05-23 Time 16:00 Sent To  
Notes
2019-05-23 16:09:57***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 ROOFING PLAN REVIEW DENIED:
  
 THE BUILDING PLAN, INCLUDING ROOFING SECTIONS, NEED TO
 BE SIGNED AND SEALED BY THE DESIGN PROFESSIONAL AND A
 ROOFING SUB-PERMIT NEEDS TO BE OBTAINED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-08-19 Cont ID  
Sent By cthroop Date 2019-08-19 Time 16:53 Rev Time 0.00
Received By cthroop Date 2019-08-16 Time 16:10 Sent To  
Notes
2019-08-19 16:55:21SIGNATURE AND SEAL REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 DIGITAL REVIEW
  
 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
  
2019-08-13 08:44:54ELECTRICAL SHEETS: PER THE WPB AMENDMENTS TO THE FBC,
 EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL
 PLAN REQUIRES A DIGITAL SIGNATURE WITH THE PROPER THIRD
 PARTY VERIFICATION. SELF-CERTIFICATION IS NOT
 ACCEPTABLE FOR ENGINEERS. ADDITIONALLY, THE DIGITAL
 SIGNATURE MUST INCLUDE THE STATEMENT "SIGNED AND
 SEALED" AS PER FAC 61G15-23.004. PROVIDE CORRECTION.
 WPB FBC 107.1; FS 471/481

Review Stop Z ZONING
Rev No 3 Status F Date 2019-11-26 Cont ID  
Sent By awooten Date 2019-11-26 Time   Rev Time 0.00
Received By awooten Date 2019-11-26 Time   Sent To  
Notes
2019-11-26 16:50:27***************************ZONING REVIEW
 FAILED************************** (REPEAT COMMENT)
  
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
  
 YOU CAN ALSO SUBMIT A CONDITIONAL LANDSCAPE APPROVAL
 FORM. YOU WOULD HAVE TO GET THE LANDSCAPING APPROVED
 AND FINALIZED BEFORE YOU CAN OBTAIN YOUR CERTIFICATE OF
 OCCUPANCY FOR THE HOUSE. PLEASE CALL OR EMAIL ME FOR
 MORE INFORMATION.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2019-08-20 Cont ID  
Sent By awooten Date 2019-08-20 Time   Rev Time 0.00
Received By awooten Date 2019-08-20 Time   Sent To  
Notes
2019-08-20 08:41:43***************************ZONING REVIEW
 FAILED************************** (REPEAT COMMENT)
  
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
  
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2019-05-15 Cont ID  
Sent By awooten Date 2019-05-15 Time   Rev Time  
Received By awooten Date 2019-05-15 Time   Sent To  
Notes
2019-05-15 15:22:55********************************ZONING REVIEW
 FAILED*************************
  
 PROVIDE A SITE PLAN/SURVEY OF PROPERTY SHOWING ALL
 SETBACKS FOR NEW HOUSE.
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
  
 PROPOSED DRIVEWAYS POOLSL, AND FENCES REQUIRE A
 SEPARATE PERMIT.
  
 FURTHER REVIEW MAY GENERATE ADDITIONAL COMMENTS.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  
  