Plan Review Stops For Permit 19050176 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2019-11-18 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-11-18 |
Time |
13:21 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-11-18 |
Time |
07:38 |
Sent To |
|
|
Notes |
2019-11-18 13:29:44 | PLAN REVIEW - BUILDING | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | | | RESULTS: DENIED | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1, DESIGNER'S SEAL IS MISSING ON ALL PLAN PAGES. | | RE-SUBMITTAL REQUIRED. | | FBC 107.1 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT, | | INTERIOR DESIGNER, LANDSCAPE ARCHITECT, OR ENGINEER | | LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE | | REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR | | DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA | | STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED | | FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR | | ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA | | STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER | | OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND | | ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE. | | | | 2. NOTICE ONLY - SINGLE HUNG WINDOWS ARE NON-IMPACT | | RATED. SHUTTER SCHEDULE AND PRODUCT APPROVAL LOCATED ON | | PLAN PAGE'S 21 & 22 OF 26. DESIGNER'S SEAL IS MISSING. | | | | 3. PROVIDE PRODUCT APPROVALS FOR WINDOW MULLIONS AND | | EXTERIOR DOORS. | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | SPECIFICALLY, PROVIDE WINDOW MULLION AND DOOR | | SUBMITTALS. | | | | 4. ROOFING PERMIT REQUIRED. PROVIDE PRODUCT APPROVALS | | FOR PROPOSED ROOFING SYSTEM COMPONENTS. | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | SPECIFICALLY, PROVIDE ROOFING SUBMITTALS. | | | | 5. DEMO PERMIT REQUIRED FOR EXISTING HOUSE - COPY OF | | DEMO CHECKLIST WITH ASBESTOS REQUIREMENTS INCLUDED IN | | SUBMITAL FOR YOUR REVIEW. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | REVIEWED SHEETS DETACHED. | | | | | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2019-08-19 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-08-19 |
Time |
16:55 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-08-16 |
Time |
16:10 |
Sent To |
|
|
Notes |
2019-08-19 17:02:10 | BUILDING PLAN REVIEW | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | | | RESULTS: DENIED | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. ADDRESS 1ST BLDG. REVIEW COMMENTS AND RE-SUBMIT. CT | 2019-08-13 09:24:32 | CHECKED IN WRONG STOP BY ACCIDENT. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2019-05-23 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-05-23 |
Time |
16:10 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2019-05-23 |
Time |
06:52 |
Sent To |
|
|
Notes |
2019-05-23 16:40:33 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | BUILDING PLAN REVIEW (1ST REVIEW) DENIED: | | | | FBC B 107: THE SUBMITTED PLANS ARE NOT COMPLETE. PLEASE | | PROVIDE THE FOLLOWING: | | | | 1. A SURVEY APPROVED BY A LICENSED SURVEYOR COMPLETE | | WITH PROPOSED LOCATION OF HOUSE, ELEVATIONS, SETBACKS, | | AND ALL OTHER REQUIRED INFORMATION. | | 2. A SITE PLAN PAGE AS PART OF THE PLANS. | | 3. DESIGNER OF RECORD SIGNATURES AND SEALS ON ALL PAGES | | PER THE FLORIDA STATE STATUTES CHAPTER 471/FL ADMIN. | | RULES 61G15-23.001 TO 61G15-23.003 AND CHAPTER 481/FL | | ADMIN. RULE 61G1-16.004. | | 4. MORE INFORMATION ON THE EXISTING SITE; IT APPEARS | | THAT THERE IS AN EXISTING STRUCTURE ON THIS LOT AND | | THERE ARE NO INDICATIONS OF A DEMO PERMIT ON RECORD. | | PLEASE CLARIFY. | | 5. A WINDOW/DOOR SUBMITTAL WITH PRODUCT APPROVALS. | | 6. THE PRODUCT AND CONNECTION DETAILS ARE REQUIRED FOR | | REINFORCING STEEL (SCREW-IN) CONNECTIONS BETWEEN WALLS | | AND SLAB. | | 7. THE PLAN DESIGN AND NOTES NEED TO BE REVIEWED, | | UPDATED TO THE CURRENT CODE (2017 SIXTH EDITION OF THE | | FLORIDA BUILDING CODE) AND APPROVED. | | 8. THE DETAILS THAT DO NOT RELATE TO THIS SPECIFIC | | PROJECT NEED TO BE DELETED FROM PLAN PAGES. | | | | | | NOTES: | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY | | RESULT IN NEW PLAN REVIEW COMMENTS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | REVIEWED SHEETS DETACHED. | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2019-11-20 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2019-11-20 |
Time |
07:23 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2019-11-20 |
Time |
07:03 |
Sent To |
|
|
Notes |
2019-11-20 07:23:24 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | 1. CORRECTED. | | 2. CORRECTED. | | 3. CORRECTED. | | 4. CORRECTED. | | 5. CORRECTED. | | 6. CORRECTED. | | 7. CORRECTED. | | 8. THE # 6 EQUIPMENT GROUNDING CONDUCTOR SHOULD NOT BE | | INCLUDED IN THE CONDUIT FROM FROM THE METER TO THE MAIN | | DISCONNECT SWITCH. PROVIDE CORRECTION. NEC 250.6; FBC | | RE E3610.4 (NOT CORRECTED.) | | 9. CORRECTED. | | 10. CORRECTED. | | 11. CORRECTED. | | 12. CORRECTED. | | 13. CORRECTED. | | 14. CORRECTED. | | 15. CORRECTED. | | | | NEW COMMENTS: | | | | 16. CIRCUIT NUMBER 31 SHOWS A 20 AMP CIRCUIT FOR | | BATHROM AND PATIO OUTLETS. PER CODE, A MINIMUM OF ONE | | 20 AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY | | BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE | | NO OTHER OUTLETS. PROVIDE CORRECTION. NEC 210.11(C)(3) | | , FBC RE E3703.4 | | 17. NEW ELECTRICAL SHEETS WERE NOT INSTALLED INTO THE | | PLAN SET. THE OLD SHEETS MUST BE REMOVED AND THE NEW | | SHEETS INSTALLED. IT IS THE RESPONSIBILITY OF THE | | PERSON THAT SUBMITS CORRECTIONS TO INSTALL THESE SHEETS | | INTO THE PLAN SET. PLAN CANNOT BE APPROVED WITH OLD | | SHEETS. PROVIDE CORRECTION. WPB FBC 107.2.1 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2019-08-13 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2019-08-13 |
Time |
09:23 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2019-08-13 |
Time |
09:23 |
Sent To |
|
|
Notes |
2019-08-13 08:41:37 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF | | PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR | | THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC | | 107.1, 107.2.1, 107.3.5.1.2 (A DIGITAL PLAN REQUIRES A | | DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY | | VERIFICATION. PROVIDE CORRECTION. WPB FBC 107.1; FS | | 471/481) | | 2. CORRECTED. | | 3. CORRECTED. | | 4. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE | | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF | | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. | | FBC EC C405.1, R404.1 (NOT PROVIDED.) | | 5. CORRECTED. | | 6. PROVIDE LOCATION OF ELECTRICAL SERVICE AND | | ELECTRICAL PANEL TO CONFIRM CODE COMPLIANCE. WPB FBC | | 107.2.1 (LOCATION OF SERVICE NOT PROVIDED.) | | 7. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT | | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 9NOT | | PROVIDED. PLAN SHOWS DETAILS FROM THE 1993 NEC, WHICH | | IS NOT THE CURRENT CODE. ALSO, RISER DIAGRAM QUOTES NEC | | 250.81, WHICH DOES NOT EXIST. PROVIDE UPDATES TO THESE | | ITEMS AND PROVIDE THE IBTP PER COMMENT.) | | 8. THE # 6 EQUIPMENT GROUNDING CONDUCTOR SHOULD NOT BE | | INCLUDED IN THE CONDUIT FROM FROM THE METER TO THE MAIN | | DISCONNECT SWITCH. PROVIDE CORRECTION. NEC 250.6; FBC | | RE E3610.4 (NOT CORRECTED.) | | 9. CORRECTED. | | 10. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED | | PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1 ( NOT | | CORRECT. A SMOKE ALARM IS REQUIRED OUTSIDE THE SLEEPING | | AREA, AND A CARBON MONOXIDE ALARM IS REQUIRED WITHIN 10 | | FEET OF EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE | | R315.1) | | 11. CORRECTED. | | 12. CORRECTED. | | 13. CORRECTED. | | 14. CORRECTED. | | 15. CORRECTED. | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2019-05-15 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2019-05-15 |
Time |
07:25 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2019-05-15 |
Time |
06:13 |
Sent To |
|
|
Notes |
2019-05-15 06:53:24 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF | | PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR | | THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC | | 107.1, 107.2.1, 107.3.5.1.2 | | 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR | | SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC | | RE E3606.3 | | 3. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. | | NEC 110.3, 110.9; FBC RE E3606.3 | | 4. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE | | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF | | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. | | FBC EC C405.1, R404.1 | | 5. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE | | OUTLETS IN GARAGE, INCLUDING GARAGE DOOR OPENER. | | PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2 | | 6. PROVIDE LOCATION OF ELECTRICAL SERVICE AND | | ELECTRICAL PANEL TO CONFIRM CODE COMPLIANCE. WPB FBC | | 107.2.1 | | 7. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT | | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 | | 8. THE # 6 EQUIPMENT GROUNDING CONDUCTOR SHOULD NOT BE | | INCLUDED IN THE CONDUIT FROM FROM THE METER TO THE MAIN | | DISCONNECT SWITCH. PROVIDE CORRECTION. NEC 250.6; FBC | | RE E3610.4 | | 9. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL | | LOADS PER THE METHOD DESCRIBED IN THE FBC RESIDENTIAL. | | THE 5 AC UNITS TOTAL 8700 VA AND THE LARGEST OF THE | | LOADS MUST BE USED. THE LAUNDRY CIRCUIT SHOULD BE | | CALCULATED AT 1500 VA. THE SMALL APPLIANCE CIRCUITS | | SHOULD BE CALCULATED AT 1500 VA EACH. PROVIDE SPEC | | SHEETS FOR AC UNITS TO CONFIRM STATED LOAD. NEC 110.3, | | 220; FBC RE E3602.2; WPB FBC 107.2.1 | | 10. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED | | PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1 | | 11. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A | | NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 | | 12. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A | | TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST | | ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND | | NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE | | INSTALLED AT THE FRONT AND BACK OF THE DWELLING. | | PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7 | | 13. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR | | SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE | | EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12 | | 14. THE WALL SPACING REQUIREMENTS FOR KITCHEN COUNTER | | SPACE STATE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED | | SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24 | | INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET | | IN THAT SPACE. THE PLAN PROVIDED DOES NOT MEET THIS | | CODE IN SOME AREAS. PROVIDE CORRECTION. NEC | | 210.52(C)(1); FBC RE E3901.4 | | 15. RECEPTACLES INSTALLED TO SERVE THE COUNTER TOP IN | | KITCHEN REQUIRE GFCI PROTECTION, INCLUDING THE ISLAND. | | PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.6 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2019-11-27 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2019-11-27 |
Time |
15:34 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2019-10-31 |
Time |
15:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2019-08-23 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2019-08-23 |
Time |
15:17 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2019-08-12 |
Time |
13:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2019-05-24 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-05-24 |
Time |
16:40 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-05-09 |
Time |
10:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2019-05-23 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-05-23 |
Time |
16:02 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2019-05-23 |
Time |
16:00 |
Sent To |
|
|
Notes |
2019-05-23 16:05:48 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | DENIED: | | | | IMPACT FEES - PAPER SUBMITTALS | | | | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE | | PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE | | RETURN STAMPED AND WITH A COPY OF THE RECEIPT AS | | APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2019-11-18 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-11-18 |
Time |
13:18 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-11-18 |
Time |
07:38 |
Sent To |
|
|
Notes |
2019-11-18 13:21:22 | PLAN REVIEW - MECHANICAL | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | | | RESULTS: DENIED | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. MECHANICAL DESIGN IS APPROVED. | | 2. DESIGNER'S SEAL IS MISSING FORM PLAN PAGE 07 OF 26. | | RE-SUBMIT NEW PLAN PAGE WITH SIGNATURE AND SEAL OF | | DESIGNER. | | FBC 107.1 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT, | | INTERIOR DESIGNER, LANDSCAPE ARCHITECT, OR ENGINEER | | LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE | | REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR | | DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA | | STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED | | FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR | | ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA | | STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER | | OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND | | ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE. | | | | | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2019-08-19 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-08-19 |
Time |
17:02 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-08-16 |
Time |
16:11 |
Sent To |
|
|
Notes |
2019-08-19 17:02:47 | SEE 1ST MECH. REVIEW COMMENTS. CT |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2019-05-24 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-05-24 |
Time |
16:31 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-05-23 |
Time |
07:08 |
Sent To |
|
|
Notes |
2019-05-24 16:40:41 | MECHANICAL PLAN REVIEW | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | RESULTS: DENIED | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH | | EDITION | | FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | 1. DESIGN PROFESSIONALS SIGNATURE AND SEAL IS INVALID. | | FBC 107.1 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT, | | INTERIOR DESIGNER, LANDSCAPE ARCHITECT, OR ENGINEER | | LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE | | REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR | | DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA | | STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED | | FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR | | ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA | | STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER | | OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND | | ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE. | | | | 2. PROVIDE ENERGY SUBMITTAL WITH LOAD CALCULATIONS. | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | COMPLIANCE BY SECTION 405. | | M1401.3EQUIPMENT AND APPLIANCE SIZING. | | HEATING AND COOLING EQUIPMENT AND APPLIANCES SHALL BE | | SIZED IN ACCORDANCE WITH ACCA MANUAL S OR OTHER | | APPROVED SIZING METHODOLOGIES BASED ON BUILDING LOADS | | CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER | | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. | | | | 3. PROVIDE TAMPER PROOF PORTS AT CU. | | M1411.8 LOCKING ACCESS PORT CAPS. | | REFRIGERANT CIRCUIT ACCESS PORTS LOCATED OUTDOORS SHALL | | BE FITTED WITH LOCKING-TYPE TAMPER-RESISTANT CAPS OR | | SHALL BE OTHERWISE SECURED TO PREVENT UNAUTHORIZED | | ACCESS. | | EXCEPTION: NO LOCKING-TYPE TAMPER-RESISTANT CAPS ARE | | REQUIRED IF PORTS ARE LOCATED INSIDE THE CONDENSING | | UNIT CABINET. | | | | 4. PROVIDE CONDENSATE DRAIN DETAIL. | | M1411.3 CONDENSATE DISPOSAL. | | CONDENSATE FROM COOLING COILS AND EVAPORATORS SHALL BE | | CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED PLACE | | OF DISPOSAL. SUCH PIPING SHALL MAINTAIN A MINIMUM | | HORIZONTAL SLOPE IN THE DIRECTION OF DISCHARGE OF NOT | | LESS THAN 1/8 UNIT VERTICAL IN 12 UNITS HORIZONTAL | | (1-PERCENT SLOPE). CONDENSATE SHALL NOT DISCHARGE INTO | | A STREET, ALLEY OR OTHER AREAS WHERE IT WOULD CAUSE A | | NUISANCE. | | | | 5. PROVIDE SERVICE OUTLET AT EXTERIOR CU'S. | | PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR SERVICING | | OF A/C EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER | | CODE. NEC 210.63; FBC RE E3901.12 | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | REVIEWED SHEETS DETACHED. | | | | | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2019-11-15 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2019-11-15 |
Time |
10:54 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2019-11-15 |
Time |
09:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2019-08-19 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-08-19 |
Time |
17:03 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-08-16 |
Time |
16:11 |
Sent To |
|
|
Notes |
2019-08-19 17:03:25 | SEE 2ND BLDG. REVIEW COMMENTS. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2019-05-13 |
|
|
Cont ID |
|
Sent By |
thunt |
Date |
2019-05-13 |
Time |
15:15 |
Rev Time |
0.00 |
Received By |
thunt |
Date |
2019-05-13 |
Time |
12:54 |
Sent To |
|
|
Notes |
2019-05-13 15:15:49 | PLUMBING 1ST REVIEW**DENIED** | | | | 1) PLANS SHALL BE SIGNED AND SEAL BY DESIGN | | PROFESSIONAL. FAC 471, 481 | | | | 2) PROVIDE PIPE SIZES ON PLUMBING ISOMETRIC DRAWING. | | FBC 107.3.5 | | | | 3) MASTER BATHROOM ISOMETRIC SHOW 2 LAV AND NO TUB. | | PLEASE CORRECT. FBC WPB ADMIN. 107.1 | | | | 4) SHT #3 PLUMBING NOT #2 AND #3 CALL OUT PVC PIPING TO | | BE USED ON THE EXTERIOR AND HOT WATER. PVC PIPING IS | | NOT PERMITTED/ APPROVED TO USED FOR WATER DISTRIBUTION/ | | HOT WATER PIPING. FBC-P 604.4 | | | | 5) SHT #3 CALLS UP FOR 1/2" INSULATION. PLEASE CORRECT | | AND SHOW AS R-3 MIN ON ALL HOT WATER PIPING NOT IN THE | | CONDITIONED SPACE. FBC-ENERGY R403.5.3 | | | | 6) PROVIDE R405-2017 OR R402-2017 ENERGY FORM. | | | | 7) PROVIDE SHOWER PAN DETAIL SHOWING 2% MIN AND CALL | | OUT MATERIAL TO BE USED. FBC-R P 2709.3 | | | | | | TIM HUNT | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | BUILDING DIVISION | | CITY OF WEST PALM BEACH | | 401 CLEMATIS STREET, 1ST FLOOR | | WEST PALM BEACH, FL 33401 | | 561-248-2703 | | [email protected] | | [email protected] | | | | | | | | | | | | | | | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
3 |
Status |
F |
Date |
2019-11-18 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-11-18 |
Time |
13:39 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-11-18 |
Time |
07:38 |
Sent To |
|
|
Notes |
2019-11-18 13:41:32 | PLAN REVIEW - ROOFING | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | | | RESULTS: DENIED | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. ROOFING PERMIT REQUIRED. | | | | 2, PROVIDE PRODUCT APPROVALS FOR PROPOSED ROOFING | | SYSTEM COMPONENTS. | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | SPECIFICALLY, PROVIDE ROOFING SUBMITTALS. | | | | | | | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
F |
Date |
2019-08-19 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-08-19 |
Time |
17:02 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-08-16 |
Time |
16:10 |
Sent To |
|
|
Notes |
2019-08-19 17:03:08 | SEE 2ND BLDG. REVIEW COMMENTS. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2019-05-23 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-05-23 |
Time |
16:06 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2019-05-23 |
Time |
16:00 |
Sent To |
|
|
Notes |
2019-05-23 16:09:57 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | ROOFING PLAN REVIEW DENIED: | | | | THE BUILDING PLAN, INCLUDING ROOFING SECTIONS, NEED TO | | BE SIGNED AND SEALED BY THE DESIGN PROFESSIONAL AND A | | ROOFING SUB-PERMIT NEEDS TO BE OBTAINED. |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2019-08-19 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-08-19 |
Time |
16:53 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-08-16 |
Time |
16:10 |
Sent To |
|
|
Notes |
2019-08-19 16:55:21 | SIGNATURE AND SEAL REVIEW | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | | | RESULTS: DENIED | | | | DIGITAL REVIEW | | | | 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH | | FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE | | NEXT REVIEW CYCLE REQUIRE REVIEW. | | | | 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL | | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE | | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT. | | | | | 2019-08-13 08:44:54 | ELECTRICAL SHEETS: PER THE WPB AMENDMENTS TO THE FBC, | | EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED | | BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL | | PLAN REQUIRES A DIGITAL SIGNATURE WITH THE PROPER THIRD | | PARTY VERIFICATION. SELF-CERTIFICATION IS NOT | | ACCEPTABLE FOR ENGINEERS. ADDITIONALLY, THE DIGITAL | | SIGNATURE MUST INCLUDE THE STATEMENT "SIGNED AND | | SEALED" AS PER FAC 61G15-23.004. PROVIDE CORRECTION. | | WPB FBC 107.1; FS 471/481 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
F |
Date |
2019-11-26 |
|
|
Cont ID |
|
Sent By |
awooten |
Date |
2019-11-26 |
Time |
|
Rev Time |
0.00 |
Received By |
awooten |
Date |
2019-11-26 |
Time |
|
Sent To |
|
|
Notes |
2019-11-26 16:50:27 | ***************************ZONING REVIEW | | FAILED************************** (REPEAT COMMENT) | | | | | | PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION | | PERMIT. SHOWING THE FOLLOWING: | | RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM | | BEACH | | SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS | | | | O GROSS LOT SQUARE FOOTAGE MINUS | | O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS | | O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA) | | O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE | | OR PORTION THEREOF | | O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE | | OR PORTION THEREOF | | | | YOU CAN ALSO SUBMIT A CONDITIONAL LANDSCAPE APPROVAL | | FORM. YOU WOULD HAVE TO GET THE LANDSCAPING APPROVED | | AND FINALIZED BEFORE YOU CAN OBTAIN YOUR CERTIFICATE OF | | OCCUPANCY FOR THE HOUSE. PLEASE CALL OR EMAIL ME FOR | | MORE INFORMATION. | | | | ALANA WOOTEN | | ASSOCIATE PLANNER | | 561-822-1449 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2019-08-20 |
|
|
Cont ID |
|
Sent By |
awooten |
Date |
2019-08-20 |
Time |
|
Rev Time |
0.00 |
Received By |
awooten |
Date |
2019-08-20 |
Time |
|
Sent To |
|
|
Notes |
2019-08-20 08:41:43 | ***************************ZONING REVIEW | | FAILED************************** (REPEAT COMMENT) | | | | | | PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION | | PERMIT. SHOWING THE FOLLOWING: | | RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM | | BEACH | | SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS | | | | O GROSS LOT SQUARE FOOTAGE MINUS | | O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS | | O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA) | | O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE | | OR PORTION THEREOF | | O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE | | OR PORTION THEREOF | | | | | | ALANA WOOTEN | | ASSOCIATE PLANNER | | 561-822-1449 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2019-05-15 |
|
|
Cont ID |
|
Sent By |
awooten |
Date |
2019-05-15 |
Time |
|
Rev Time |
|
Received By |
awooten |
Date |
2019-05-15 |
Time |
|
Sent To |
|
|
Notes |
2019-05-15 15:22:55 | ********************************ZONING REVIEW | | FAILED************************* | | | | PROVIDE A SITE PLAN/SURVEY OF PROPERTY SHOWING ALL | | SETBACKS FOR NEW HOUSE. | | | | PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION | | PERMIT. SHOWING THE FOLLOWING: | | RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM | | BEACH | | SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS | | | | O GROSS LOT SQUARE FOOTAGE MINUS | | O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS | | O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA) | | O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE | | OR PORTION THEREOF | | O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE | | OR PORTION THEREOF | | | | PROPOSED DRIVEWAYS POOLSL, AND FENCES REQUIRE A | | SEPARATE PERMIT. | | | | FURTHER REVIEW MAY GENERATE ADDITIONAL COMMENTS. | | | | ALANA WOOTEN | | ASSOCIATE PLANNER | | PLANNING DIVISION | | 561-822-1449 | | [email protected] | | | | |
|
|