Plan Review Details - Permit 19050059
Plan Review Stops For Permit 19050059
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-05-21 Cont ID  
Sent By jgomez Date 2019-05-21 Time 16:44 Rev Time 0.00
Received By jgomez Date 2019-05-21 Time 16:31 Sent To  
Notes
2019-05-21 16:46:41PROVISO REMAINDER.
 PROVIDE INFORMATION FOR REVIEW PRIOR TO INSPECTIONS TO
 AVOID CONFLICTS/DELAYS:
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE ENERGY CALCULATIONS FOR THE MAIN
 HOUSE. ONLY COVER PAGE WAS SUBMITTED.
 2-PROVIDE PRODUCT APPROVAL FOR: A)INSWING ARCHED ENTRY
 DOOR SIZE AS SHOWN ON PLANS. B) PROVIDE CURRENT
 POLYSTICK TU-PLUS PRODUCT APPROVAL. FL5259-R10
 SUBMITTED IS TOO OLD. AND CLEARLY IDENTIFY WHICH
 ASSEMBLY IS GOING TO BE USED.
 3- PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR THE
 FOOTING OF PRIVACY WALL WHEN THE WALL IS LOCATED AT THE
 PROPERTY LINE. FOOTING CAN NOT ENCROACH BEYOND THE
 PROPERTY LINE.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-05-24 Cont ID  
Sent By jleahy Date 2019-05-24 Time 07:19 Rev Time 0.00
Received By jpearson Date 2019-05-24 Time 07:19 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-05-24 Time   Rev Time 0.00
Received By cpuell Date 2019-05-14 Time 10:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-05-22 Cont ID  
Sent By jgomez Date 2019-05-22 Time 08:30 Rev Time 0.00
Received By jgomez Date 2019-05-22 Time 08:12 Sent To  
Notes
2019-05-22 10:03:16PROVISO:
 1-NO MORE THAN ONE WET-VENTED FIXTURE DRAIN SHALL
 DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN
 CONNECTION.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-05-22 Cont ID  
Sent By jgomez Date 2019-05-22 Time 08:32 Rev Time 0.00
Received By jgomez Date 2019-05-22 Time 08:32 Sent To  
Notes
***NONE***