Plan Review Details - Permit 19050035
Plan Review Stops For Permit 19050035
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-08-09 Cont ID  
Sent By dbattles Date 2019-08-09 Time 10:49 Rev Time 0.00
Received By dbattles Date 2019-08-09 Time 10:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-07-02 Cont ID  
Sent By jbrooks Date 2019-07-02 Time 14:41 Rev Time 0.00
Received By jbrooks Date 2019-07-02 Time 14:41 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-05-28 Cont ID  
Sent By jduprey Date 2019-05-28 Time 08:46 Rev Time 0.00
Received By jduprey Date 2019-05-28 Time 08:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-08-07 Cont ID  
Sent By jpearson Date 2019-08-07 Time 15:29 Rev Time 0.00
Received By jpearson Date 2019-08-07 Time 15:29 Sent To B
Notes
2019-08-07 15:31:25TO MISC 2 BLDG.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-06-28 Cont ID  
Sent By fgiaquin Date 2019-06-28 Time 07:18 Rev Time 0.00
Received By fgiaquin Date 2019-06-28 Time 07:03 Sent To B
Notes
2019-06-28 07:17:58ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PRINTED COPIES OF DIGITALLY SIGNED PLANS ARE NOT
 CONSIDERED TO BE SIGNED AND SEALED PER FLORIDA
 STATUTES. A WET SIGNATURE FROM DESIGN PROFESSIONAL IS
 REQUIRED ON EVERY SEAL.
  
 PLEASE SEE REQUIREMENTS BELOW FOR SIGNATURE AND SEALS.
  
 PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE THAT THE
 LICENSEE CREATE BY HAND AN ORIGINAL OF THE LICENSEE?S
 SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE IS NOT ALLOWED
 ON PHYSICALLY TRANSMITTED DOCUMENTS.
 CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL
 SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON
 EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED.
  
 AS FOR CREATING THE SEAL, PHYSICALLY TRANSMITTED
 DOCUMENTS ARE ALLOWED TO BE EMBOSSED, SEALED USING A
 WET STAMP, OR CONTAIN A DIGITALLY CREATED SEAL (AS PART
 OF THE BORDER). IN EACH OF THESE CASES THE SEAL IS TO
 PARTIALLY OVERLAP THE LICENSEE?S SIGNATURE SUCH THAT
 THE SIGNATURE IS NOT MADE ILLEGIBLE.
 CHAPTER 61G15-23.003(2), F.A.C., THE LICENSEE MUST THEN
 USE A WET SEAL, A DIGITALLY CREATED SEAL, OR AN
 EMBOSSING SEAL PLACED PARTIALLY OVERLAPPING THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. THE PLACEMENT OF THE SEAL SHALL NOT RENDER THE
 SIGNATURE ILLEGIBLE.
  
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-27 Cont ID  
Sent By jpearson Date 2019-05-27 Time 11:30 Rev Time 0.00
Received By jpearson Date 2019-05-27 Time 11:30 Sent To B
Notes
2019-05-27 11:30:33CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ZONING COMMENTS MUST BE ADDRESSED BEFORE ELECTRICAL
 CAN APPROVE. THE SIGNED/SEALED SHEETS ALSO NEED THE
 CITY PLACE APPROVAL STAMP, THIS IS CURRENTLY MISSING ON
 THE SIGNED/SEALED PLANS. WPB FBC 107.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-08-09 Cont ID  
Sent By dbattles Date 2019-08-09 Time 10:49 Rev Time 0.00
Received By dbattles Date 2019-07-24 Time 13:59 Sent To  
Notes
2019-07-25 14:00:06RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-24 Cont ID  
Sent By jbrooks Date 2019-07-24 Time 10:00 Rev Time  
Received By lmarchan Date 2019-06-10 Time 13:55 Sent To  
Notes
2019-06-11 13:55:32RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-28 Cont ID  
Sent By jduprey Date 2019-05-28 Time 08:46 Rev Time 0.00
Received By jduprey Date 2019-05-01 Time 11:28 Sent To  
Notes
2019-05-02 11:28:52ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 3 Status P Date 2019-07-31 Cont ID  
Sent By eschneid Date 2019-07-31 Time 16:30 Rev Time 0.25
Received By eschneid Date 2019-07-31 Time 16:24 Sent To E
Notes
2019-07-31 16:31:04PASSED
  
 ALLOWED SIGN AREA - 28 SF
 PROPOSED SIGN AREA - 14.57 SF
  
 PROVISOS:
  
 1) THE WOOD COLUMN COVERS ARE REQUIRED TO BE INSTALLED,
 WITH PERMITS, PRIOR TO THE FINAL INSPECTION.
  
 2) NO EXPOSED ELECTRICAL WIRING IS PERMITTED.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-07-23 Cont ID  
Sent By eschneid Date 2019-07-23 Time 15:46 Rev Time 0.25
Received By eschneid Date 2019-07-23 Time 13:48 Sent To PC
Notes
2019-07-23 15:48:02PASSED
  
 ALLOWED SIGN AREA - 28 SF
 PROPOSED SIGN AREA - 14.57 SF
  
 PROVISOS:
  
 1) THE WOOD COLUMN COVERS ARE REQUIRED TO BE INSTALLED,
 WITH PERMITS, PRIOR TO THE FINAL INSPECTION.
  
 2) NO EXPOSED ELECTRICAL WIRING IS PERMITTED.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-05-23 Cont ID  
Sent By eschneid Date 2019-05-23 Time 17:40 Rev Time 0.25
Received By eschneid Date 2019-05-23 Time 17:40 Sent To E
Notes
2019-05-23 17:41:06PERMIT 19050032
  
 FAILED
  
 PROVIDE RESPONSES IN WRITING.
  
 1) THIS IS NOT A DESIGNATED SIGN ZONE LOCATION IN THE
 CITYPLACE MASTER SIGN PLAN. CITYPLACE MAY APPROVE IN
 WRITING A VARIANCE TO RELOCATE A SIGN WITHIN THE
 HORIZONTAL LINE OF THE SIGN ZONE.
  
 2) THE CITYPLACE MASTER SIGN PLAN MEASURES SIGNAGE
 ALLOWANCE AS FOLLOWS - ONE SQUARE FOOT OF SIGNAGE FOR
 EACH ONE LINEAR FOOT OF STORE FRONTAGE. THE OUTDOOR BAR
 HAS 28 FEET OF FRONTAGE, SO THE SIGN MAY NOT EXCEED 28
 SQUARE FEET. THE PROPOSED SIGN IS 42.44 SQUARE FEET.
  
 3) CITYPLACE MAY APPROVE IN WRITING A VARIANCE TO
 INCREASE IN THE SIGN SQUARE FOOTAGE BY 25 PERCENT;
 HOWEVER, THIS WILL NOT PERMIT THE SQUARE FOOTAGE YOU
 ARE SEEKING. YOU WOULD NEED TO SUBMIT AND HAVE APPROVED
 A MINOR PLANNED DEVELOPMENT AMENDMENT, WHICH WOULD
 ALLOW THE SIGN TO INCREASE THE SIGN AREA BY 50 PERCENT.
 THIS WOULD PERMIT A 42 SQUARE FOOT SIGN, SO YOU WOULD
 NEED TO REDUCE THE HEIGHT OF THE SIGN TO TWO FEET.
  
 4) THE CITYPLACE MATER SIGN PLAN REQUIRES THAT ALL
 FASTENERS BE CONCEALED. THIS APPLIES TO THE ALUMINUM
 MOUNTING STRAPS AND ALL THE TREADED THRU BOLTS. IT
 APPEARS THAT THE PLAN IS TO REMOVE THE WOOD FRAME WHICH
 CURRENTLY COVERS THE COLUMNS. IT IS UNCLEAR FROM THE
 DRAWINGS IS THE WOOD FRAME WILL BE REPLACED AND THUS
 COVER THE SOME OF THE FASTENERS (ALUMINUM MOUNTING
 STRAPS). THERE WOULD STILL BE THRU BOLTS THAT NEED TO
 BE COVERED. IF THE WOOD COVERING IS NOT REPLACED THEN
 THE FASTENERS ARE NOT CONCEALED AND YOU MUST USE A
 DIFFERENT MOUNTING SYSTEM.
  
 ALLOWED SIGN AREA - 28 SF.
 PROPOSED SIGN AREA - 42.44 SF = TOO LARGE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]
  