Plan Review Details - Permit 19050032
Plan Review Stops For Permit 19050032
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-08-08 Cont ID  
Sent By pvalenti Date 2019-08-08 Time 07:48 Rev Time 0.00
Received By pvalenti Date 2019-08-08 Time 07:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-07-02 Cont ID  
Sent By pvalenti Date 2019-07-02 Time 13:45 Rev Time 0.00
Received By pvalenti Date 2019-07-02 Time 13:45 Sent To  
Notes
2019-07-02 13:58:24***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING 2ND REVIEW DENIED:
  
 PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE THAT THE
 LICENSEE CREATE BY HAND AN ORIGINAL OF THE LICENSEE?S
 SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE IS NOT ALLOWED
 ON PHYSICALLY TRANSMITTED DOCUMENTS.
 CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL
 SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON
 EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-05-28 Cont ID  
Sent By pvalenti Date 2019-05-28 Time 10:44 Rev Time 0.00
Received By pvalenti Date 2019-05-28 Time 10:44 Sent To  
Notes
2019-05-28 11:37:52***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
  
 APPROVED WITH PROVISO:
  
 AT TIME OF INSPECTION PROVIDE THE WELDERS PERFORMANCE
 QUALIFICATION RECORDS AND PROVIDE A WELDING PROCEDURE
 SPECIFICATION FOR THIS PROJECT.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-08-07 Cont ID  
Sent By jpearson Date 2019-08-07 Time 15:34 Rev Time 0.00
Received By jpearson Date 2019-08-07 Time 15:34 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-06-28 Cont ID  
Sent By fgiaquin Date 2019-06-28 Time 07:01 Rev Time 0.00
Received By fgiaquin Date 2019-06-28 Time 06:55 Sent To B
Notes
2019-06-28 06:59:33ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PRINTED COPIES OF DIGITALLY SIGNED PLANS ARE NOT
 CONSIDERED TO BE SIGNED AND SEALED PER FLORIDA
 STATUTES. A WET SIGNATURE FROM DESIGN PROFESSIONAL IS
 REQUIRED ON EVERY SEAL.
  
 PLEASE SEE REQUIREMENTS BELOW FOR SIGNATURE AND SEALS.
  
 PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE THAT THE
 LICENSEE CREATE BY HAND AN ORIGINAL OF THE LICENSEE?S
 SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE IS NOT ALLOWED
 ON PHYSICALLY TRANSMITTED DOCUMENTS.
 CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL
 SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON
 EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED.
  
 AS FOR CREATING THE SEAL, PHYSICALLY TRANSMITTED
 DOCUMENTS ARE ALLOWED TO BE EMBOSSED, SEALED USING A
 WET STAMP, OR CONTAIN A DIGITALLY CREATED SEAL (AS PART
 OF THE BORDER). IN EACH OF THESE CASES THE SEAL IS TO
 PARTIALLY OVERLAP THE LICENSEE?S SIGNATURE SUCH THAT
 THE SIGNATURE IS NOT MADE ILLEGIBLE.
 CHAPTER 61G15-23.003(2), F.A.C., THE LICENSEE MUST THEN
 USE A WET SEAL, A DIGITALLY CREATED SEAL, OR AN
 EMBOSSING SEAL PLACED PARTIALLY OVERLAPPING THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. THE PLACEMENT OF THE SEAL SHALL NOT RENDER THE
 SIGNATURE ILLEGIBLE.
  
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-27 Cont ID  
Sent By jpearson Date 2019-05-27 Time 11:32 Rev Time 0.00
Received By jpearson Date 2019-05-27 Time 11:32 Sent To B
Notes
2019-05-27 11:32:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ZONING COMMENTS MUST BE ADDRESSED BEFORE ELECTRICAL
 CAN APPROVE. THE SIGNED/SEALED SHEETS ALSO NEED THE
 CITY PLACE APPROVAL STAMP, THIS IS CURRENTLY MISSING ON
 THE SIGNED/SEALED PLANS. WPB FBC 107.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-08-08 Cont ID  
Sent By pvalenti Date 2019-08-08 Time 07:49 Rev Time 0.00
Received By pvalenti Date 2019-07-24 Time 13:58 Sent To  
Notes
2019-07-25 13:58:54RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-24 Cont ID  
Sent By lmarchan Date 2019-07-24 Time 10:00 Rev Time 0.00
Received By lmarchan Date 2019-06-10 Time 13:56 Sent To  
Notes
2019-06-11 13:56:32RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-28 Cont ID  
Sent By pvalenti Date 2019-05-28 Time 11:38 Rev Time 0.00
Received By pvalenti Date 2019-05-01 Time 11:27 Sent To  
Notes
2019-05-02 11:27:38ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 3 Status P Date 2019-07-31 Cont ID  
Sent By eschneid Date 2019-07-31 Time 15:28 Rev Time 0.25
Received By eschneid Date 2019-07-31 Time 15:28 Sent To E
Notes
2019-07-31 16:34:54PASSED
  
 ALLOWED SIGN AREA - 28 SF
 PROPOSED SIGN AREA - 16.83 SF
  
 PROVISOS:
  
 1) THE WOOD COLUMN COVERS ARE REQUIRED TO BE INSTALLED,
 WITH PERMITS, PRIOR TO THE FINAL INSPECTION.
  
 2) NO EXPOSED ELECTRICAL WIRING IS PERMITTED.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-07-23 Cont ID  
Sent By eschneid Date 2019-07-23 Time 13:43 Rev Time 0.25
Received By eschneid Date 2019-07-23 Time 12:40 Sent To PC
Notes
2019-07-23 13:43:31PASSED
  
 ALLOWED SIGN AREA - 28 SF
 PROPOSED SIGN AREA - 16.83 SF
  
 PROVISOS:
  
 1) THE WOOD COLUMN COVERS ARE REQUIRED TO BE INSTALLED,
 WITH PERMITS, PRIOR TO THE FINAL INSPECTION.
  
 2) NO EXPOSED ELECTRICAL WIRING IS PERMITTED.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-05-23 Cont ID  
Sent By eschneid Date 2019-05-23 Time 17:14 Rev Time 0.50
Received By eschneid Date 2019-05-23 Time 17:13 Sent To E
Notes
2019-05-23 17:17:40FAILED
  
 PROVIDE RESPONSES IN WRITING.
  
 1) THE FULL HEIGHT OF THE SIGN WAS NOT PROVIDED.
 PROVIDE THE DIMENSION FROM THE TOP OF THE TOP CHANNEL
 TO THE BOTTOM OF THE BOTTOM CHANNEL.
  
 2) THE CITYPLACE MATER SIGN PLAN REQUIRES THAT ALL
 FASTENERS BE CONCEALED. THE U BOLT FASTENERS ARE NOT
 CONCEALED.
  
 4) THE BOTTOM OF THE SIGN SHALL HAVE A MINIMUM OF EIGHT
 (8) FEET OF CLEARANCE FROM THE GRADE OF THE PEDESTRIAN
 WALKWAY. PLEASE PROVIDE VERIFICATION THAT THIS STANDARD
 IS MET.
  
 5) EXPOSED ELECTRICAL WIRING IS NOT PERMITTED BY THE
 CITYPLACE MASTER SIGN PLAN. THE PLANS SHALL CLEARLY
 SHOW HOW THE WIRING WILL BE PROVIDED TO THE SIGN FROM
 ITS SOURCE WITHOUT BEING EXPOSED. THE PROVIDED PLANS DO
 NOT SHOW ANY PENETRATIONS IN THE VERTICAL SUPPORT
 COLUMN TUBING.
  
 ALLOWED SIGN AREA - 28 SF.
 PROPOSED SIGN AREA - UNKNOWN
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]
  