Plan Review Stops For Permit 19050032 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2019-08-08 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-08-08 |
Time |
07:48 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2019-08-08 |
Time |
07:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2019-07-02 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-07-02 |
Time |
13:45 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2019-07-02 |
Time |
13:45 |
Sent To |
|
|
Notes |
2019-07-02 13:58:24 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | BUILDING 2ND REVIEW DENIED: | | | | PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE THAT THE | | LICENSEE CREATE BY HAND AN ORIGINAL OF THE LICENSEE?S | | SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY CREATED OR | | COPIED IMAGE OF THE LICENSEE?S SIGNATURE IS NOT ALLOWED | | ON PHYSICALLY TRANSMITTED DOCUMENTS. | | CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL | | SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON | | EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE, | | DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S | | SIGNATURE SHALL NOT BE USED. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2019-05-28 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-05-28 |
Time |
10:44 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2019-05-28 |
Time |
10:44 |
Sent To |
|
|
Notes |
2019-05-28 11:37:52 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | | | APPROVED WITH PROVISO: | | | | AT TIME OF INSPECTION PROVIDE THE WELDERS PERFORMANCE | | QUALIFICATION RECORDS AND PROVIDE A WELDING PROCEDURE | | SPECIFICATION FOR THIS PROJECT. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2019-08-07 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2019-08-07 |
Time |
15:34 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2019-08-07 |
Time |
15:34 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2019-06-28 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2019-06-28 |
Time |
07:01 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2019-06-28 |
Time |
06:55 |
Sent To |
B |
|
Notes |
2019-06-28 06:59:33 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PRINTED COPIES OF DIGITALLY SIGNED PLANS ARE NOT | | CONSIDERED TO BE SIGNED AND SEALED PER FLORIDA | | STATUTES. A WET SIGNATURE FROM DESIGN PROFESSIONAL IS | | REQUIRED ON EVERY SEAL. | | | | PLEASE SEE REQUIREMENTS BELOW FOR SIGNATURE AND SEALS. | | | | PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE THAT THE | | LICENSEE CREATE BY HAND AN ORIGINAL OF THE LICENSEE?S | | SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY CREATED OR | | COPIED IMAGE OF THE LICENSEE?S SIGNATURE IS NOT ALLOWED | | ON PHYSICALLY TRANSMITTED DOCUMENTS. | | CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL | | SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON | | EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE, | | DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S | | SIGNATURE SHALL NOT BE USED. | | | | AS FOR CREATING THE SEAL, PHYSICALLY TRANSMITTED | | DOCUMENTS ARE ALLOWED TO BE EMBOSSED, SEALED USING A | | WET STAMP, OR CONTAIN A DIGITALLY CREATED SEAL (AS PART | | OF THE BORDER). IN EACH OF THESE CASES THE SEAL IS TO | | PARTIALLY OVERLAP THE LICENSEE?S SIGNATURE SUCH THAT | | THE SIGNATURE IS NOT MADE ILLEGIBLE. | | CHAPTER 61G15-23.003(2), F.A.C., THE LICENSEE MUST THEN | | USE A WET SEAL, A DIGITALLY CREATED SEAL, OR AN | | EMBOSSING SEAL PLACED PARTIALLY OVERLAPPING THE | | LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE | | SEALED. THE PLACEMENT OF THE SEAL SHALL NOT RENDER THE | | SIGNATURE ILLEGIBLE. | | | | | | | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-657-1653 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2019-05-27 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2019-05-27 |
Time |
11:32 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2019-05-27 |
Time |
11:32 |
Sent To |
B |
|
Notes |
2019-05-27 11:32:29 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. ZONING COMMENTS MUST BE ADDRESSED BEFORE ELECTRICAL | | CAN APPROVE. THE SIGNED/SEALED SHEETS ALSO NEED THE | | CITY PLACE APPROVAL STAMP, THIS IS CURRENTLY MISSING ON | | THE SIGNED/SEALED PLANS. WPB FBC 107.1, 107.2.1 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2019-08-08 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-08-08 |
Time |
07:49 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2019-07-24 |
Time |
13:58 |
Sent To |
|
|
Notes |
2019-07-25 13:58:54 | RESUB ROUTED TO ZONING INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2019-07-24 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2019-07-24 |
Time |
10:00 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2019-06-10 |
Time |
13:56 |
Sent To |
|
|
Notes |
2019-06-11 13:56:32 | RESUB ROUTED TO ZONING INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2019-05-28 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-05-28 |
Time |
11:38 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2019-05-01 |
Time |
11:27 |
Sent To |
|
|
Notes |
2019-05-02 11:27:38 | ROUTED TO ZONING INBOX |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2019-07-31 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2019-07-31 |
Time |
15:28 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2019-07-31 |
Time |
15:28 |
Sent To |
E |
|
Notes |
2019-07-31 16:34:54 | PASSED | | | | ALLOWED SIGN AREA - 28 SF | | PROPOSED SIGN AREA - 16.83 SF | | | | PROVISOS: | | | | 1) THE WOOD COLUMN COVERS ARE REQUIRED TO BE INSTALLED, | | WITH PERMITS, PRIOR TO THE FINAL INSPECTION. | | | | 2) NO EXPOSED ELECTRICAL WIRING IS PERMITTED. | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2019-07-23 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2019-07-23 |
Time |
13:43 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2019-07-23 |
Time |
12:40 |
Sent To |
PC |
|
Notes |
2019-07-23 13:43:31 | PASSED | | | | ALLOWED SIGN AREA - 28 SF | | PROPOSED SIGN AREA - 16.83 SF | | | | PROVISOS: | | | | 1) THE WOOD COLUMN COVERS ARE REQUIRED TO BE INSTALLED, | | WITH PERMITS, PRIOR TO THE FINAL INSPECTION. | | | | 2) NO EXPOSED ELECTRICAL WIRING IS PERMITTED. | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2019-05-23 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2019-05-23 |
Time |
17:14 |
Rev Time |
0.50 |
Received By |
eschneid |
Date |
2019-05-23 |
Time |
17:13 |
Sent To |
E |
|
Notes |
2019-05-23 17:17:40 | FAILED | | | | PROVIDE RESPONSES IN WRITING. | | | | 1) THE FULL HEIGHT OF THE SIGN WAS NOT PROVIDED. | | PROVIDE THE DIMENSION FROM THE TOP OF THE TOP CHANNEL | | TO THE BOTTOM OF THE BOTTOM CHANNEL. | | | | 2) THE CITYPLACE MATER SIGN PLAN REQUIRES THAT ALL | | FASTENERS BE CONCEALED. THE U BOLT FASTENERS ARE NOT | | CONCEALED. | | | | 4) THE BOTTOM OF THE SIGN SHALL HAVE A MINIMUM OF EIGHT | | (8) FEET OF CLEARANCE FROM THE GRADE OF THE PEDESTRIAN | | WALKWAY. PLEASE PROVIDE VERIFICATION THAT THIS STANDARD | | IS MET. | | | | 5) EXPOSED ELECTRICAL WIRING IS NOT PERMITTED BY THE | | CITYPLACE MASTER SIGN PLAN. THE PLANS SHALL CLEARLY | | SHOW HOW THE WIRING WILL BE PROVIDED TO THE SIGN FROM | | ITS SOURCE WITHOUT BEING EXPOSED. THE PROVIDED PLANS DO | | NOT SHOW ANY PENETRATIONS IN THE VERTICAL SUPPORT | | COLUMN TUBING. | | | | ALLOWED SIGN AREA - 28 SF. | | PROPOSED SIGN AREA - UNKNOWN | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | [email protected] | | |
|
|