Plan Review Details - Permit 19041453
Plan Review Stops For Permit 19041453
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-05-30 Time   Rev Time 0.00
Received By lmarchan Date 2019-05-21 Time 14:00 Sent To  
Notes
2019-05-22 14:01:05RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-05-03 Time   Rev Time 0.00
Received By lmarchan Date 2019-04-29 Time 09:35 Sent To  
Notes
2019-05-01 09:35:33REVISION ROUTED TO CCOLE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-05-30 Cont ID  
Sent By ccole Date 2019-05-30 Time 09:24 Rev Time 0.00
Received By ccole Date 2019-05-30 Time 09:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-05-03 Cont ID  
Sent By ccole Date 2019-05-03 Time 17:01 Rev Time 0.00
Received By ccole Date 2019-05-03 Time 17:01 Sent To I
Notes
2019-05-03 17:08:441ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19041453
 5/3/19
  
 CODES IN EFFECT:
  
  
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: THE RETRUN TRANSFER DUCTS FROM BEDROOMS
 1, 2, & 3 ARE UNDERSIZED PER SECTION M1602.3 FBC R. THE
 TRANSFER DUCTS SHALL BE SIZED 1-1/2 TIMES THE CROSS
 SECTIONAL AREA OF THE SUPPLY DUCT ENTERING THE ROOM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  