Plan Review Details - Permit 19041376
Plan Review Stops For Permit 19041376
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-06-04 Cont ID  
Sent By shill Date 2019-06-04 Time 17:17 Rev Time 0.00
Received By shill Date 2019-06-04 Time 17:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-05-16 Cont ID  
Sent By jleahy Date 2019-05-16 Time 14:22 Rev Time 0.00
Received By jleahy Date 2019-05-16 Time 14:21 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-06-11 Cont ID  
Sent By thunt Date 2019-06-11 Time 16:58 Rev Time 0.00
Received By thunt Date 2019-06-11 Time 16:58 Sent To  
Notes
2019-06-11 16:59:26SEE PROVISO CHANGING THE BTU FOR THE GENERATOR AN TOTAL
 LOAD ON SYSTEM CHANGED TO MATCH GENERATOR MANUFACTURES
 INSTALLATION MAUNAL.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-05-01 Cont ID  
Sent By thunt Date 2019-05-01 Time 16:00 Rev Time 0.00
Received By thunt Date 2019-05-01 Time 16:00 Sent To  
Notes
2019-05-01 16:02:03GAS 1ST REVIEW**DENIED**NOTE - A COMPREHENSIVE REVIEW
 COULD NOT BE DONE AT THIS TIME AND ADDITIONAL PLAN
 REVIEW COMMENTS MAY BE GENERATED UPON THE RE-REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1)THE NOC, MODEL HIGHLIGHT ON MANUFACTURE MANUAL, AND
 ON THE ELC SIZING SHEET ALL CALL OUT FOR A 16KW
 GENERATOR. GAS ISOMETRIC CALLS BOTH 16KW AND 22KW BUT
 LIST ONLY THE 22KW BTU LOAD WHICH IS LESS THEN THE 16
 KW. PLEASE CLARIFY WHICH GENERATOR IS BEING SPEC OUT
 AND CORRECT PLAN. FBC 107.2.1
  
 2) ISOMETRIC DRAWING IS ONLY SHOWING 50' OF P.E PIPING
 BUT ON THE GAS FLAT LOCATED ON THE SURVEY SHEET YOU
 CALL OUT AND LIST 20' 3/4" CSST, 18' 3/4" SCH 40 GALV,
 AND 15' 3/4" P.E PIPE. PLEASE CLARIFY AND CORRECT. FBC
 107.2.1. 1SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY
 SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017
 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES
 SEC. G2413.4.1, G2413.4.2.
  
 3) PROVIDE PIPE MATERIAL AND PIPE SIZE WHERE YOU ARE
 CONNECTING INTO THE EXISTING GAS SYSTEM. SHOW THE TYPE
 OF PIPE MATERIAL BEING INSTALLED, ALL PIPE SIZES, AND
 THE CORRESPONDING EHD NUMBER OF THE CORRUGATED
 STAINLESS STEEL TUBING (IF APPLICABLE) FOR EACH PIPE
 SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 4) YOU CALL OUT 3 DIFFERENT PIPING MATERIALS BUT ONLY
 SUPPLIED 1 SIZING TABLE FOR 2 LB. SUBMIT TWO COPIES OF
 ALL APPLICABLE SIZING TABLES USED TO SIZE THE GAS
 SYSTEM INCLUDING THE .5LB CHARTS AFTER THE PRESSURE
 REGULATOR OR PLACE A NOTE ON THE PLANS/DRAWINGS
 SPECIFYING WHICH SIZING TABLE(S) FROM THE GAS CODE OR
 OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS GAS
 SYSTEM. REFER TO THE 2017 FBC-FUEL GAS SECS. 401.4,
 401.8, 402.3, AND TABLES 402.4 (1) THRU 402.4 (37) OR
 2017 FBC-RES. SEC. G2413.3, G2412.8, G2413.1, G2413.2,
 & G2413.3.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status F Date 2019-06-11 Cont ID  
Sent By thunt Date 2019-06-11 Time 16:59 Rev Time 0.00
Received By thunt Date 2019-06-05 Time 15:29 Sent To  
Notes
2019-06-06 15:29:30RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-06-04 Cont ID  
Sent By shill Date 2019-06-04 Time 17:17 Rev Time 0.00
Received By shill Date 2019-04-26 Time 12:52 Sent To  
Notes
2019-04-29 12:52:56ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2019-06-11 Cont ID  
Sent By ajones Date 2019-06-11 Time 09:47 Rev Time 0.00
Received By ajones Date 2019-06-11 Time 09:47 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-05-01 Cont ID  
Sent By mcruz Date 2019-05-01 Time 12:14 Rev Time 0.00
Received By mcruz Date 2019-05-01 Time 12:13 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved