Plan Review Details - Permit 19041338
Plan Review Stops For Permit 19041338
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-05-07 Cont ID  
Sent By jgomez Date 2019-05-07 Time 16:44 Rev Time 0.00
Received By jgomez Date 2019-05-07 Time 16:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-05-06 Cont ID  
Sent By jgomez Date 2019-05-06 Time 14:02 Rev Time 0.00
Received By jgomez Date 2019-05-06 Time 13:27 Sent To  
Notes
2019-05-06 14:02:39RESIDENTIAL (R3) RE-ROOF, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1-OK
  
 2- OK.
  
 3- ROOF TILE ADHESIVE NOA SUBMITTED. CLEARLY MARK
 ADHESIVE PLACEMENT THAT CORRESPONDS TO REVISED PADDY
 SIZE REQUIRED ON ITEM #2 ABOVE. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 RESPONSE:
 PADDY SIZE MARKED ON THE NOA 17-0322.03 DOESN'T MATCH
 PADDY SIZE MARKED ON THE ROOF TILE NOA 18-0829.03.
 REVISE AS REQUIRED.
 NOTE: ROOF TILE NOA CALLS FOR SINGLE PATTY ADHESIVE SET
 SYSTEM NOT TWO PATTY ADHESIVE SET SYSTEM.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-26 Cont ID  
Sent By jgomez Date 2019-04-26 Time 11:55 Rev Time 0.00
Received By jgomez Date 2019-04-26 Time 11:20 Sent To  
Notes
2019-04-26 12:13:01RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- ONLY ONE COPY OF PRODUCT APPROVALS WAS SUBMITTED.
 PROVIDE 2 COPIES OF ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 107.1 CITY AMENDMENTS.
  
 2- ROOFF TILE NOA 18-0829.03 SUBMITTED:
 CLEARLY MARK ROOF TILE FASTENING METHOD AS REQUIRED BY
 CITY POLICY FOR ALL ROOFING PERMITS.
 NOTE: THERE IS A LIGHT MARK NEXT TO THE THE TWO PATTY
 ADHESIVE SET SYSTEM #5 ON PAGE 5 OF 7 OF NOA SUBMITTED.
 THE MINIMUM ATTACHMENT RESISTANCE FOR TWO PATTY
 ADHESIVE SET #5 IS 26.1. IF THIS IS THE PADDY SIZE TO
 BE INSTALLED, THEN IT DOESN'T SEEM TO COMPLY WITH THE
 ATTACHMENT RESISTANCE REQUIRED BY SEC. 2.5 OF RAS 127.
 CLEARLY MARK ANOTHER ADHESIVE SET SYSTEM THAT PROVIDES
 ENOUGH ATTACHMENT RESISTANCE OR PROVIDE COMPLETE
 CALCULATIONS SHOWING THAT THE SELECTED SYSTEM WORKS.
  
 3- ROOF TILE ADHESIVE NOA SUBMITTED. CLEARLY MARK
 ADHESIVE PLACEMENT THAT CORRESPONDS TO REVISED PADDY
 SIZE REQUIRED ON ITEM #2 ABOVE. SEC. 107.2.1 CITY
 AMENDMENTS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-05-07 Cont ID  
Sent By jgomez Date 2019-05-07 Time 16:44 Rev Time 0.00
Received By jgomez Date 2019-05-07 Time 16:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-06 Cont ID  
Sent By jgomez Date 2019-05-06 Time 14:28 Rev Time 0.00
Received By jgomez Date 2019-05-02 Time 15:59 Sent To I
Notes
2019-05-02 16:00:03RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-26 Cont ID  
Sent By jgomez Date 2019-04-26 Time 12:13 Rev Time 0.00
Received By jgomez Date 2019-04-25 Time 15:14 Sent To I
Notes
***NONE***