Plan Review Details - Permit 19041308
Plan Review Stops For Permit 19041308
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-05-02 Cont ID  
Sent By rmcdouga Date 2019-05-02 Time 14:36 Rev Time 0.00
Received By rmcdouga Date 2019-05-02 Time 14:19 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-05-02 Cont ID  
Sent By rmcdouga Date 2019-05-02 Time 14:36 Rev Time 0.00
Received By rmcdouga Date 2019-05-02 Time 14:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-14 Cont ID  
Sent By tklarge Date 2019-05-14 Time 10:13 Rev Time 0.00
Received By tklarge Date 2019-05-14 Time 10:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-02 Cont ID  
Sent By rmcdouga Date 2019-05-02 Time 14:36 Rev Time 0.00
Received By rmcdouga Date 2019-04-25 Time 14:58 Sent To  
Notes
2019-04-26 14:58:36ROUTED TO ZONING INBOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-05-14 Cont ID  
Sent By tklarge Date 2019-05-14 Time 10:13 Rev Time 0.00
Received By tklarge Date 2019-05-14 Time 10:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-05-01 Cont ID  
Sent By thunt Date 2019-05-01 Time 16:14 Rev Time 0.00
Received By thunt Date 2019-05-01 Time 16:14 Sent To  
Notes
2019-05-01 16:14:55PLUMBING 1ST REVIEW**DENIED**
  
 1) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM
 ITS PUMP CURVE AND THE SIMPLIFIED TOTAL DYNAMIC HEAD
 CALCULATION IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC
 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 EDITION
 ADDRESSES FLOW RATE IN GALLONS PER MINUTE (GPM). IT
 REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED
 THE LISTED MAXIMUM FLOW RATE OF THE SUCTION OUTLET
 FITTING ASSEMBLY (DRAIN COVER).THE TDH CALCULATIONS
 MUST INCLUDE ALL OF THE SYSTEM COMPONENTS INCLUDING
 SUCTION AND RETURN PIPING, FITTINGS, VALVES, HEATER,
 FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS EXCEPT
 THE PUMP.
  
 2) INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS FOR
 THE PUMP BEING INSTALLED ON THIS SYSTEM. WPB AMEND. TO
 FBC SEC. 107.2.1.
  
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2019-05-01 Cont ID  
Sent By mcruz Date 2019-05-01 Time 11:51 Rev Time 0.00
Received By mcruz Date 2019-05-01 Time 11:49 Sent To  
Notes
***NONE***