Plan Review Details - Permit 19041065
Plan Review Stops For Permit 19041065
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-05-28 Cont ID  
Sent By dbattles Date 2019-05-28 Time 10:10 Rev Time 0.00
Received By dbattles Date 2019-05-28 Time 10:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-30 Cont ID  
Sent By dbattles Date 2019-04-30 Time 13:50 Rev Time 0.00
Received By dbattles Date 2019-04-30 Time 09:51 Sent To  
Notes
2019-04-30 13:56:05****CORRECTIONS****
 W.P.B. PERMIT: 19041065
 REVIEWED: APRIL 30, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 NO INCREASE IN VALUE WAS STATED ON THE REVISION
 SUBMITTAL SHEET.
 PLEASE INCLUDE IHE INCREASE IN PROJECT VALUE FOR
 REMOVING AND REPLACING THE WINDOW SYSTEM.
  
 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVAL FOR
 WINDOW SYSTEM TO BE INSTALLED.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-05-16 Cont ID  
Sent By jpearson Date 2019-05-16 Time 08:43 Rev Time 0.00
Received By jpearson Date 2019-05-16 Time 08:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-04-24 Cont ID  
Sent By scaldero Date 2019-04-24 Time 13:06 Rev Time 0.00
Received By scaldero Date 2019-04-24 Time 12:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-04 Cont ID  
Sent By gjohnson Date 2019-06-04 Time 11:37 Rev Time 0.00
Received By gjohnson Date 2019-05-23 Time 08:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-05-16 Time   Rev Time 0.00
Received By lmarchan Date 2019-04-22 Time 12:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-05-06 Cont ID  
Sent By ccole Date 2019-05-06 Time 15:22 Rev Time 0.00
Received By ccole Date 2019-05-06 Time 12:50 Sent To  
Notes
***NONE***

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status P Date 2019-06-04 Cont ID  
Sent By gjohnson Date 2019-06-04 Time 11:37 Rev Time 0.00
Received By gjohnson Date 2019-06-04 Time 11:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-06-04 Cont ID  
Sent By gjohnson Date 2019-06-04 Time 11:36 Rev Time 0.00
Received By gjohnson Date 2019-06-04 Time 10:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-05-02 Cont ID  
Sent By gjohnson Date 2019-05-02 Time 15:18 Rev Time 0.00
Received By gjohnson Date 2019-05-02 Time 12:41 Sent To  
Notes
2019-05-02 15:37:161ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 MED GAS COMMENTS:
  
 1. PLEASE PLACE NOTE ON PLAN THE CONTRACTOR AND ANYONE
 INSTALLING MED GAS PIPING SHALL BE MED GAS CERTIFIED.
 INSTALLERS SHALL PROVIDED PROOF FOR PERMIT ISSUE AND ON
 JOBSITE FOR INSPECTORS APPROVAL . PER FAC 61G4-15.031
  
 2. PLEASE PROVIDE PIPING DETAIL FOR NEW ZONE VALVES.
 PER WPB AMEND TO FBC 107.2.1
  
 3. PROVIDE AMOUNT OF NITROGEN AND NITROUS OXIDE BEING
 STORED. PER WPB AMEND TO FBC 107.2.1
  
 4. PROVIDE DETAIL FOR CONNECTION OF THE TANK CHAINS.
 PER WPB AMEND TO FBC 107.2.1
  
 5. PROVIDE MANUFACTURE SPECIFICATION AND INSTILLATION
 GUIDE FOR THE MED GAS EQUIPMENT. PER WPB AMEND TO FBC
 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-06-03 Cont ID  
Sent By shill Date 2019-06-03 Time 08:36 Rev Time 0.00
Received By shill Date 2019-06-03 Time 08:36 Sent To  
Notes
2019-05-28 10:12:53OK - BUILDING SHEETS AND PRODUCT APPROVALS

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-05-16 Cont ID  
Sent By jpearson Date 2019-05-16 Time 08:43 Rev Time 0.00
Received By jpearson Date 2019-05-16 Time 08:43 Sent To  
Notes
2019-04-30 10:00:30UPLOAD TWO WINDOW SUBMITTAL FILES WITH DIGITAL
 SIGNATURE OF EOR INTO SUPPORTING DOCUMENTS.
  
 A-SHEETS AND SP1.1 ARE - OK
 CHECKED BY DB ON 4-30-19

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By pgreilic Date 2019-05-06 Time   Rev Time 0.00
Received By pgreilic Date 2019-05-06 Time 15:00 Sent To  
Notes
2019-05-06 15:00:24PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]