Plan Review Details - Permit 19041040
Plan Review Stops For Permit 19041040
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-05-06 Cont ID  
Sent By jwitmer Date 2019-05-06 Time 11:55 Rev Time 0.00
Received By jwitmer Date 2019-05-06 Time 07:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-05-28 Cont ID  
Sent By fgiaquin Date 2019-05-28 Time 07:00 Rev Time 0.00
Received By fgiaquin Date 2019-05-28 Time 06:55 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-14 Cont ID  
Sent By fgiaquin Date 2019-05-14 Time 06:52 Rev Time 0.00
Received By fgiaquin Date 2019-05-14 Time 06:42 Sent To I
Notes
2019-05-14 06:52:50ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHOW ALL ELECTRICAL WORK TO BE PERFORMED ON THE
 SUBMITTED PLANS. A NOTE STATING "KITCHEN COUNTERTOP
 RECEPTACLES WILL BE PER CODE" WILL NOT SUFFICE. FBC
 107.2.1 NEC 210.52
  
 2. KITCHEN COUNTERTOP RECEPTACLES SPACING IS NOT CODE
 COMPLIANT.PLEASE PROVIDE CORRECTION. NEC 210.52C
  
 3. PLAN PROVIDED IS A COPY. PLANS SUBMITTED MUST HAVE
 ORIGINAL SIGNATURES ON PLAN. ELECTRICAL PLAN IS
 REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR THE
 DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC
 107.2.1, 107.3.5.1.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-04-26 Cont ID  
Sent By scaldero Date 2019-04-26 Time 09:38 Rev Time 0.00
Received By scaldero Date 2019-04-26 Time 09:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-28 Cont ID  
Sent By fgiaquin Date 2019-05-28 Time 07:00 Rev Time 0.00
Received By fgiaquin Date 2019-05-21 Time 13:46 Sent To  
Notes
2019-05-22 13:47:01RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-14 Cont ID  
Sent By fgiaquin Date 2019-05-14 Time 06:53 Rev Time 0.00
Received By fgiaquin Date 2019-04-19 Time 13:29 Sent To  
Notes
2019-04-22 13:29:45B20

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-04-29 Cont ID  
Sent By thunt Date 2019-04-29 Time 15:52 Rev Time 0.00
Received By thunt Date 2019-04-29 Time 15:52 Sent To  
Notes
***NONE***