Plan Review Details - Permit 19041024
Plan Review Stops For Permit 19041024
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-05-18 Cont ID  
Sent By pvalenti Date 2019-05-18 Time 10:06 Rev Time 0.00
Received By pvalenti Date 2019-05-18 Time 10:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-05-10 Cont ID  
Sent By pvalenti Date 2019-05-10 Time 11:26 Rev Time 0.00
Received By pvalenti Date 2019-05-10 Time 11:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-05-17 Cont ID  
Sent By jpearson Date 2019-05-17 Time 15:31 Rev Time 0.00
Received By jpearson Date 2019-05-17 Time 15:31 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-05-07 Cont ID  
Sent By jpearson Date 2019-05-07 Time 11:06 Rev Time 0.00
Received By jpearson Date 2019-05-07 Time 11:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-18 Cont ID  
Sent By pvalenti Date 2019-05-18 Time 10:06 Rev Time 0.00
Received By pvalenti Date 2019-05-15 Time 14:29 Sent To  
Notes
2019-05-16 14:29:32RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-10 Cont ID  
Sent By pvalenti Date 2019-05-10 Time 11:27 Rev Time 0.00
Received By pvalenti Date 2019-04-19 Time 13:23 Sent To  
Notes
2019-04-22 13:23:24R34

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-05-16 Cont ID  
Sent By thunt Date 2019-05-16 Time 16:47 Rev Time 0.00
Received By thunt Date 2019-05-16 Time 16:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-24 Cont ID  
Sent By thunt Date 2019-04-24 Time 18:52 Rev Time 0.00
Received By thunt Date 2019-04-24 Time 18:52 Sent To  
Notes
2019-04-24 18:51:56PLUMBING 1ST REVIEW**DENIED**A SUB PLUMBING PERMIT IS
 REQUIRED
  
 1) VALUE SEEMS LOW. PROVIDE A SIGNED BONA FIDE
 CONTRACT.109.3 BUILDING PERMIT VALUATIONS. IF, IN THE
 OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION
 OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
  
 2) PROVIDE AN EXISTING FLOOR PLAN. IS THE SHOWER
 REPLACING A TUB OR SHOWER? PLEASE CLARIFY. FBC 107.2.1
  
 3) PROVIDE BATHROOM DIMENSIONS SHOWING FIXTURES WILL
 COMPLY WITH MIN REQUIRED DIMENSIONS AS CALLED OUT IN
 FBC-R P 2705.1 (5)
  
 4) PROVIDE SHOWER PAN DETAIL SHOWING MATERIAL BEING
 USED AND PREPITCH. IF FLOORING IS RECESS IS IT
 INTEGRALLY POURED? FBC-R P2709.1
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  
  
  
  
  
  