Plan Review Details - Permit 19040963
Plan Review Stops For Permit 19040963
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2019-04-26 Cont ID  
Sent By jleahy Date 2019-04-26 Time 14:31 Rev Time 0.00
Received By jleahy Date 2019-04-26 Time 14:31 Sent To  
Notes
2019-04-26 14:38:32SLAB WAS APPROVED ON ANOTHER PERMIT JLEAHY

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-24 Cont ID  
Sent By jleahy Date 2019-04-24 Time 15:34 Rev Time 0.00
Received By jleahy Date 2019-04-24 Time 15:34 Sent To  
Notes
2019-04-24 15:37:01 
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO SLAB DETAIL SHOWN, SUBMIT SLAB DETAIL FOR REVIEW.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-05-08 Cont ID  
Sent By jleahy Date 2019-05-08 Time 10:40 Rev Time 0.00
Received By jleahy Date 2019-05-08 Time 10:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-04-26 Cont ID  
Sent By jleahy Date 2019-04-26 Time 15:19 Rev Time 0.00
Received By jleahy Date 2019-04-26 Time 15:19 Sent To  
Notes
2019-04-26 15:20:18NEED TO AJUST THE VALUE OF THE GENERATOR IN ORDER TO
 GET PERMIT. JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-24 Cont ID  
Sent By jleahy Date 2019-04-24 Time 15:34 Rev Time 0.00
Received By jleahy Date 2019-04-24 Time 15:34 Sent To  
Notes
2019-04-24 15:38:48ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 VALUE FOR 60KW GENERATOR TO LOW SUBMIT A SIGNED
 CONTRACT FOR THE COMPLETE VALUE OF WORK SHOWN.
  
 SLAB DETAIL MISSING
  
 SUBMIT RISER DIAGRAM SHOWING LOCATION OF TRANSFER
 SWITCH AND SERVICE.

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2019-05-07 Cont ID  
Sent By thunt Date 2019-05-07 Time 14:04 Rev Time 0.00
Received By thunt Date 2019-05-07 Time 14:04 Sent To  
Notes
2019-05-07 14:05:19GAS PERMITTED UNDER PERMIT # 19050135

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-04-24 Cont ID  
Sent By thunt Date 2019-04-24 Time 14:17 Rev Time 0.00
Received By thunt Date 2019-04-24 Time 14:17 Sent To  
Notes
2019-04-24 14:17:42GAS 1ST REVIEW**DENIED**
  
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT IS REQUIRED FOR A
 CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE
 COMPLETE PLANS THAT REFLECT THE ENTIRE SCOPE OF GAS
 WORK TO BE DONE. WPB AMEND. TO FBC SEC.107.2.1.
  
 1) THE PIPING INTENDED FOR THE GENERATOR INSTALLED
 UNDER PERMIT#18081434 WAS ONLY SIZED FOR 790,000 BTU'S.
 YOU GENERATOR BASED ON THE SPEC SUPPLIED IS 890,000
 BTU'S. YOU MUST SUBMIT A COMPLETE GAS PLAN SHOWING HOW
 THIS EXTRA LOAD ON THE EXISTING SYSTEM IS GOING TO BE
 HANDLED TO INLCUDE. FBC 107.3.5
  
 2) VALUE SEEMS LOW. PROVIDE A SIGN BONA FIDE
 CONTRACT.109.3 BUILDING PERMIT VALUATIONS. IF, IN THE
 OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION
 OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
  
 3) PLAN SHOW GENERATOR TO BE INSTALLED UNDER A COVERED
 CONC. PLEASE CLARIFY. SUBMIT TWO COPIES OF A HOUSE PLAN
 SHOWING THE LOCATION OF THE GENERATORR AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE GENERATORR. THE LOCATION OF THE
 GENERATORSHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-24 Cont ID  
Sent By jleahy Date 2019-04-24 Time 15:39 Rev Time 0.00
Received By jleahy Date 2019-04-18 Time 13:15 Sent To  
Notes
2019-04-19 13:16:09ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2019-04-23 Cont ID  
Sent By mcruz Date 2019-04-23 Time 16:43 Rev Time 0.00
Received By mcruz Date 2019-04-23 Time 16:41 Sent To  
Notes
***NONE***