Plan Review Details - Permit 19040741
Plan Review Stops For Permit 19040741
Review Stop G GAS REVIEW
Rev No 4 Status P Date 2019-08-05 Cont ID  
Sent By tklarge Date 2019-08-05 Time 09:16 Rev Time 0.00
Received By tklarge Date 2019-08-05 Time 09:16 Sent To I
Notes
2019-08-03 07:10:44CONTACTED CONTRACTOR AWAITING RESPONSE

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2019-07-12 Cont ID  
Sent By tklarge Date 2019-07-12 Time 06:45 Rev Time 0.00
Received By tklarge Date 2019-07-11 Time 06:39 Sent To  
Notes
2019-07-12 06:44:431) THE PLANS INDICATE AN EXISTING GAS METER AND CITY
 RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS ADDRESS.
 THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED
 INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE
 EXISTING SYSTEM IS PROPERLY SIZED. SUBMIT A GAS PIPING
 RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. I HAVE INCLUDED A COPY OF THE MOST RECENT
 GAS DRAWING ON FILE IN THE APPLICATION PACKAGE TO BE
 USED AS REFERENCE ONLY. FGC SECS. 401.4, 401.8, 402.1,
 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3. WPB AMEND. TO FBC SEC. 107.1.3RD
 REQUEST.
 2) SHOW THE SIZES AND TYPE OF PIPE MATERIAL BEING
 INSTALLED FOR THE RANGE AND THE TANKLESS WATER HEATER.
 WPB AMEND. TO FBC SEC. 107.2.1. 3RD REQUEST.
 PLEASE CALL THIS REVIEWER TO REVIEW THESE COMMENTS
 PRIOR TO RESUBMITTAL.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-07-08 Cont ID  
Sent By tklarge Date 2019-07-08 Time 06:20 Rev Time 0.00
Received By tklarge Date 2019-07-08 Time 05:31 Sent To  
Notes
2019-07-08 06:19:221) THERE ARE FOUR GAS RISER DIAGRAMS IN THIS SUBMITTAL
 PACKAGE AND I HAVE NO IDEA WHICH ONE IS TO BE USED. ALL
 DOCUMENTS NOT TO BE USED ARE TO BE REMOVED FROM THE
 SUBMITTAL PACKAGE AND TWO COMPLETE SETS OF PLANS ARE TO
 BE SUBMITTED FOR REVIEW AND APPROVAL. THIS SUBMITTAL IS
 DISORGANIZED AND CONFUSING AND A THOROUGH REVIEW COULD
 NOT BE PERFORMED.
 2) THE PLANS INDICATE AN EXISTING GAS METER AND CITY
 RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS ADDRESS.
 THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED
 INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE
 EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE
 EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM
 THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD
 OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO
 EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH
 OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. WPB
 AMEND. TO FBC SEC. 107.1.2ND REQUEST.
 3) SHOW THE SIZES AND TYPE OF PIPE MATERIAL BEING
 INSTALLED FOR THE RANGE AND THE TANKLESS WATER HEATER.
 WPB AMEND. TO FBC SEC. 107.2.1. 2ND REQUEST.
 4) THE GAS DRAWING REFERENCES A TABLE FOR CSST BUT
 THERE IS NO CSST SHOWN ON THE GAS DRAWING. CLARIFY. 2ND
 REQUEST.
  
 ***NOTE: A COMPREHENSIVE REVIEW COULD NOT BE DONE AT
 THIS TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-04-16 Cont ID  
Sent By thunt Date 2019-04-16 Time 16:53 Rev Time 0.00
Received By thunt Date 2019-04-16 Time 16:53 Sent To  
Notes
2019-04-16 16:53:51GAS 1ST REVIEW**DENIED**
  
 1) ) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. CITY
 RECORDS ( 05010245) SHOWS FIRE PIT 50K, POOL HEATER AS
 400K, FUTURE BBQ 50K. PROVIDE PLAN SHOWING ALL FIXTURE
 LOAD ON GAS SYSTEM.
  
 2) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
  
 3) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 4) SUBMIT INSTALLATION MANUAL SHOWING THE INSTALLATION
 REQUIREMENTS FROM ANY DOOR OR WINDOW. FBC 107.3.5
  
 5) YOUR PLAN SHOWINF A SIZING TABLE FOR CSST BUT NO
 CSST PIPING IS SHOWN ON PLAN. PLEASE CLARIFY. FBC
 107.2.1
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-08-05 Cont ID  
Sent By tklarge Date 2019-08-05 Time 09:17 Rev Time 0.00
Received By tklarge Date 2019-07-19 Time 13:03 Sent To  
Notes
2019-07-22 13:03:10RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-07-12 Cont ID  
Sent By tklarge Date 2019-07-12 Time 06:45 Rev Time 0.00
Received By tklarge Date 2019-07-08 Time 14:31 Sent To  
Notes
2019-07-09 14:31:40RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-08 Cont ID  
Sent By tklarge Date 2019-07-08 Time 06:47 Rev Time 0.00
Received By tklarge Date 2019-07-02 Time 15:03 Sent To  
Notes
2019-07-03 15:04:00RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-16 Cont ID  
Sent By thunt Date 2019-04-16 Time 16:59 Rev Time 0.00
Received By thunt Date 2019-04-15 Time 11:20 Sent To  
Notes
2019-04-16 11:20:34PLUMN <5K

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-08-05 Cont ID  
Sent By tklarge Date 2019-08-05 Time 09:16 Rev Time 0.00
Received By tklarge Date 2019-08-02 Time 08:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-07-12 Cont ID  
Sent By tklarge Date 2019-07-12 Time 06:45 Rev Time 0.00
Received By tklarge Date 2019-07-12 Time 06:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-07-08 Cont ID  
Sent By tklarge Date 2019-07-08 Time 06:38 Rev Time 0.00
Received By tklarge Date 2019-07-08 Time 06:20 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-16 Cont ID  
Sent By thunt Date 2019-04-16 Time 16:54 Rev Time 0.00
Received By thunt Date 2019-04-16 Time 16:54 Sent To  
Notes
2019-04-16 16:59:09PLUMBING 1ST REVIEW**DENIED**
  
 1) PROVIDE LOCATION OF EXISTING TANK WATER HEATER AND
 PROVIDE WATER PIPE FLAT DRAWING . WHAT IS BEING DONE
 WITH THE EXISTING VENT? FBC 107.3.5
  
 2) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
  
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR