Plan Review Stops For Permit 19040741 |
Review Stop |
G |
GAS REVIEW |
Rev No |
4 |
Status |
P |
Date |
2019-08-05 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-08-05 |
Time |
09:16 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-08-05 |
Time |
09:16 |
Sent To |
I |
|
Notes |
2019-08-03 07:10:44 | CONTACTED CONTRACTOR AWAITING RESPONSE |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
F |
Date |
2019-07-12 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-07-12 |
Time |
06:45 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-07-11 |
Time |
06:39 |
Sent To |
|
|
Notes |
2019-07-12 06:44:43 | 1) THE PLANS INDICATE AN EXISTING GAS METER AND CITY | | RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS ADDRESS. | | THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED | | INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE | | EXISTING SYSTEM IS PROPERLY SIZED. SUBMIT A GAS PIPING | | RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING | | APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE | | SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE | | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT | | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF | | THE SECTION. I HAVE INCLUDED A COPY OF THE MOST RECENT | | GAS DRAWING ON FILE IN THE APPLICATION PACKAGE TO BE | | USED AS REFERENCE ONLY. FGC SECS. 401.4, 401.8, 402.1, | | 402.2, 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, | | G2413.2, G2413.3. WPB AMEND. TO FBC SEC. 107.1.3RD | | REQUEST. | | 2) SHOW THE SIZES AND TYPE OF PIPE MATERIAL BEING | | INSTALLED FOR THE RANGE AND THE TANKLESS WATER HEATER. | | WPB AMEND. TO FBC SEC. 107.2.1. 3RD REQUEST. | | PLEASE CALL THIS REVIEWER TO REVIEW THESE COMMENTS | | PRIOR TO RESUBMITTAL. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2019-07-08 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-07-08 |
Time |
06:20 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-07-08 |
Time |
05:31 |
Sent To |
|
|
Notes |
2019-07-08 06:19:22 | 1) THERE ARE FOUR GAS RISER DIAGRAMS IN THIS SUBMITTAL | | PACKAGE AND I HAVE NO IDEA WHICH ONE IS TO BE USED. ALL | | DOCUMENTS NOT TO BE USED ARE TO BE REMOVED FROM THE | | SUBMITTAL PACKAGE AND TWO COMPLETE SETS OF PLANS ARE TO | | BE SUBMITTED FOR REVIEW AND APPROVAL. THIS SUBMITTAL IS | | DISORGANIZED AND CONFUSING AND A THOROUGH REVIEW COULD | | NOT BE PERFORMED. | | 2) THE PLANS INDICATE AN EXISTING GAS METER AND CITY | | RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS ADDRESS. | | THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED | | INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE | | EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE | | EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE | | OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM | | THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD | | OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO | | EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH | | OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE | | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE | | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE | | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE | | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. | | FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR | | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. WPB | | AMEND. TO FBC SEC. 107.1.2ND REQUEST. | | 3) SHOW THE SIZES AND TYPE OF PIPE MATERIAL BEING | | INSTALLED FOR THE RANGE AND THE TANKLESS WATER HEATER. | | WPB AMEND. TO FBC SEC. 107.2.1. 2ND REQUEST. | | 4) THE GAS DRAWING REFERENCES A TABLE FOR CSST BUT | | THERE IS NO CSST SHOWN ON THE GAS DRAWING. CLARIFY. 2ND | | REQUEST. | | | | ***NOTE: A COMPREHENSIVE REVIEW COULD NOT BE DONE AT | | THIS TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2019-04-16 |
|
|
Cont ID |
|
Sent By |
thunt |
Date |
2019-04-16 |
Time |
16:53 |
Rev Time |
0.00 |
Received By |
thunt |
Date |
2019-04-16 |
Time |
16:53 |
Sent To |
|
|
Notes |
2019-04-16 16:53:51 | GAS 1ST REVIEW**DENIED** | | | | 1) ) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU | | LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE | | TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING | | SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING | | SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING | | SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS | | THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH | | APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH | | APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF | | PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE | | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE | | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE | | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE | | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. | | FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR | | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. CITY | | RECORDS ( 05010245) SHOWS FIRE PIT 50K, POOL HEATER AS | | 400K, FUTURE BBQ 50K. PROVIDE PLAN SHOWING ALL FIXTURE | | LOAD ON GAS SYSTEM. | | | | 2) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE | | LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION | | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN | | RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER | | HEATER SHALL COMPLY WITH THE MANUFACTURER'S | | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND | | DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. | | | | 3) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL | | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE | | CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR | | EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1. | | | | 4) SUBMIT INSTALLATION MANUAL SHOWING THE INSTALLATION | | REQUIREMENTS FROM ANY DOOR OR WINDOW. FBC 107.3.5 | | | | 5) YOUR PLAN SHOWINF A SIZING TABLE FOR CSST BUT NO | | CSST PIPING IS SHOWN ON PLAN. PLEASE CLARIFY. FBC | | 107.2.1 | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | TIM HUNT | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | CITY OF WEST PALM BEACH | | 561-248-2703 | | [email protected] | | [email protected] | | | | | | | | | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2019-08-05 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-08-05 |
Time |
09:17 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-07-19 |
Time |
13:03 |
Sent To |
|
|
Notes |
2019-07-22 13:03:10 | RESUB ROUTED TO TKLARGE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2019-07-12 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-07-12 |
Time |
06:45 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-07-08 |
Time |
14:31 |
Sent To |
|
|
Notes |
2019-07-09 14:31:40 | RESUB ROUTED TO TKLARGE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2019-07-08 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-07-08 |
Time |
06:47 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-07-02 |
Time |
15:03 |
Sent To |
|
|
Notes |
2019-07-03 15:04:00 | RESUB ROUTED TO THUNT |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2019-04-16 |
|
|
Cont ID |
|
Sent By |
thunt |
Date |
2019-04-16 |
Time |
16:59 |
Rev Time |
0.00 |
Received By |
thunt |
Date |
2019-04-15 |
Time |
11:20 |
Sent To |
|
|
Notes |
2019-04-16 11:20:34 | PLUMN <5K |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2019-08-05 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-08-05 |
Time |
09:16 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-08-02 |
Time |
08:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2019-07-12 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-07-12 |
Time |
06:45 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-07-12 |
Time |
06:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2019-07-08 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-07-08 |
Time |
06:38 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-07-08 |
Time |
06:20 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2019-04-16 |
|
|
Cont ID |
|
Sent By |
thunt |
Date |
2019-04-16 |
Time |
16:54 |
Rev Time |
0.00 |
Received By |
thunt |
Date |
2019-04-16 |
Time |
16:54 |
Sent To |
|
|
Notes |
2019-04-16 16:59:09 | PLUMBING 1ST REVIEW**DENIED** | | | | 1) PROVIDE LOCATION OF EXISTING TANK WATER HEATER AND | | PROVIDE WATER PIPE FLAT DRAWING . WHAT IS BEING DONE | | WITH THE EXISTING VENT? FBC 107.3.5 | | | | 2) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE | | LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION | | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN | | RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER | | HEATER SHALL COMPLY WITH THE MANUFACTURER'S | | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND | | DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | TIM HUNT | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | CITY OF WEST PALM BEACH | | 561-248-2703 | | [email protected] | | [email protected] | | | | |
|
|