Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-17 Cont ID  
Sent By dbattles Date 2019-05-17 Time 15:51 Rev Time 0.00
Received By dbattles Date 2019-05-17 Time 12:50 Sent To  
Notes
2019-05-17 15:54:43****CORRECTIONS****
 W.P.B. PERMIT: 19040727
 REVIEWED: MAY 17, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) 107.2.5 FBC[AMENDED] DEMOLITION PLAN.
 - PROVIDE DEMOLITION PLAN TO SHOW EXISTING AREA TO BE
 REMOVED.
  
 2) 109.3 FBC[AMENDED] PROVIDE COPY OF PROPOSAL WITH
 CONTRACTOR TO SHOW WORK VALUE EQUAL TO THE AMOUNT SHOWN
 ON PERMIT APPLICATION, OR ADJUST VALUE TO MATCH ACTUAL
 COST OF WORK. PLEASE ADJUST FEE AT FRONT DESK AND PAY
 ADJUSTED PERMIT REVIEW FEE AT TIME OF RE-SUBMITTAL.
 - VALUE TO BE BASED ON COST OF CONSTRUCTION AS IF BEING
 DONE BY CONTRACTOR. ALTHOUGH THIS IS OWNER BUILDER THE
 COST OF 4000.00 DOLLARS SEEMS LOW FOR ADDITION WITH
 MULTIPLE TRADES. PLEASE PROVIDE A COST BREAKDOWN FOR
 THE ADDITION BASED ON CURRENT CONSTRUCTION INDUSTRY
 STANDARDS.
  
 3) 481.221(2)?SEALS; DISPLAY OF CERTIFICATE NUMBER
 - PLANS NEED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OF RECORD FROM REGINALD ACOX & ASSOCIATES. IF THAT IS
 NOT THE COMPANY THAT PRODUCED THE DRAWINGS FOR THIS
 ADDITION PLEASE REMOVE THEIR TITLE BLOCK AND HAVE THE
 RESPONSIBLE PARTY PUT THEIR NAME AND SIGNATURE ON THE
 PLANS.
  
 4) 1101.1 ADDITION VS. LEVEL 2 ALTERARTION
 - THIS WOULD BE CLASSIFIED AS AN ADDITION INSTEAD OF A
 LEVEL 2 ALTERATION. PROVIDE EXISTING UNDER AIR AREA,
 ADDITION (PROVIDED) AND NEW TOTAL.
  
 5) 103.1.1.2 FBC[RE] THE BUILDINGS OWNER, THE OWNERS
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNATED
 BY THE OWNER SHALL CERTIFY THAT THE BUILDING IS IN
 COMPLIANCE WITH THE CODE, AS PER SECTION 553.907,
 FLORIDA STATUTES, PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION OR RENOVATION. 553.907, FLORIDA
 STATUTES.
 - PLEASE HAVE THE OWNER SIGN THE ENERGY CALCULATIONS.
  
 6) 401.3 FBC[RE] PROVIDE ENERGY PERFORMANCE LEVEL
 (EPL)DISPLAY CARD WITH THE ENEGRY CALCULATIONS TO SHOW
 ESTIMATED ENERGY PERFORMANCE LEVEL. THIS CARD IS TO BE
 SIGNED BY BUILDER AND AVAILABLE FOR INSPECTOR TO REVIEW
 FOR BUILDING FINAL.
 - ADD EPL CARD TO ENERGY CALCULATION SUBMITTAL. THIS IS
 IN THE MANDATORY CATEGORY FOR ALL COMPLIANCE TYPES.
  
 7) 318 FBC[R] INDICATE THE MEANS OF TERMITE PROTECTION
 PROPOSED AND REFERENCE SECTION R308 FOR STANDARDS.
 - HOW WILL TERMITE PROTECTION BE PROVIDED AT EXISTING
 SLAB?
  
 8) 403.4 FBC[R] EXTERIOR FOOTINGS SHALL BE PLACED NOT
 LESS THAN 12 INCHES BELOW THE UNDISTURBED GROUND
 SURFACE. WHERE APPLICABLE, THE DEPTH OF FOOTINGS SHALL
 ALSO CONFORM TO SECTIONS R403.1.4.1 THROUGH R403.1.4.2.
 - PROVIDE DIMENSIONS OF EXISTING FOOTER.
  
 9) 506.2.3 FBC[R] VAPOR RETARDER. A 6-MIL (0.006 INCH;
 152 ?M) POLYETHYLENE OR APPROVED VAPOR RETARDER WITH
 JOINTS LAPPED NOT LESS THAN 6 INCHES (152 MM) SHALL BE
 PLACED BETWEEN THE CONCRETE FLOOR SLAB AND THE BASE
 COURSE OR THE PREPARED SUBGRADE WHERE NO BASE COURSE
 EXISTS.
 - HOW WILL A VAPOR BARRIER BE INSTALLED AT EXISTING
 SLAB.
  
 10) 403.1.6 FBC[R] FOUNDATION ANCHORAGE. WOOD SILL
 PLATES AND WOOD WALLS SUPPORTED DIRECTLY ON CONTINUOUS
 FOUNDATIONS SHALL BE ANCHORED TO THE FOUNDATION IN
 ACCORDANCE WITH THIS SECTION. COLD-FORMED STEEL FRAMING
 SHALL BE ANCHORED DIRECTLY TO THE FOUNDATION OR
 FASTENED TO WOOD SILL PLATES ANCHORED TO THE
 FOUNDATION. ANCHORAGE OF COLD-FORMED STEEL FRAMING AND
 SILL PLATES SUPPORTING COLD-FORMED STEEL FRAMING SHALL
 BE IN ACCORDANCE WITH THIS SECTION AND SECTION R505.3.1
 OR R603.3.1. WOOD SOLE PLATES AT ALL EXTERIOR WALLS ON
 MONOLITHIC SLABS, WOOD SOLE PLATES OF BRACED WALL
 PANELS AT BUILDING INTERIORS ON MONOLITHIC SLABS AND
 ALL WOOD SILL PLATES SHALL BE ANCHORED TO THE
 FOUNDATION WITH MINIMUM 1/2-INCHDIAMETER (12.7 MM)
 ANCHOR BOLTS SPACED A MAXIMUM OF 6 FEET (1829 MM) ON
 CENTER OR APPROVED ANCHORS OR ANCHOR STRAPS SPACED AS
 REQUIRED TO PROVIDE EQUIVALENT ANCHORAGE TO
 1/2-INCH-DIAMETER (12.7 MM) ANCHOR BOLTS. BOLTS SHALL
 EXTEND A MINIMUM OF 7 INCHES (178 MM) INTO CONCRETE OR
 GROUTED CELLS OF CONCRETE MASONRY UNITS. THE BOLTS
 SHALL BE LOCATED IN THE MIDDLE THIRD OF THE WIDTH OF
 THE PLATE. A NUT AND WASHER SHALL BE TIGHTENED ON EACH
 ANCHOR BOLT. THERE SHALL BE A MINIMUM OF TWO BOLTS PER
 PLATE SECTION WITH ONE BOLT LOCATED NOT MORE THAN 12
 INCHES (305 MM) OR LESS THAN SEVEN BOLT DIAMETERS FROM
 EACH END OF THE PLATE SECTION. INTERIOR BEARING WALL
 SOLE PLATES ON MONOLITHIC SLAB FOUNDATION THAT ARE NOT
 PART OF A BRACED WALL PANEL SHALL BE POSITIVELY
 ANCHORED WITH APPROVED FASTENERS. SILL PLATES AND SOLE
 PLATES SHALL BE PROTECTED AGAINST DECAY AND TERMITES
 WHERE REQUIRED BY SECTIONS R317 AND R318. EXCEPTIONS:
 - SHEET A-2 SHOW DOUBLE SILL CONNECTED WITH 5 INCH
 TAPCONS. AFTER 3 INCHES OF WOOD THAT WOULD BE 1 1/2
 EMBEDMENT INTO 4 IN SLAB THAT SITS ON TOP OF EXISTING
 FOOTER. FBC 403.1.6 CALLS FOR 7 INCHES OF EMBEDMENT OF
 1/2 INCH ANCHOR BOLT 6' O.C. THIS WOULD HELP TIE
 EXISTING SLAB, NEW 4 INCH SLAB AND SILL PLATE. PLEASE
 SPECIFY ANCHOR BOLT TO MEET 403.1.6.
  
 11) 806 FBC[R] SUPPLY VENTING CALCULATIONS FOR THE
 ATTIC AND HOW THE AREA OF VENTING WILL BE ACHIEVED, OR
 FOLLOW R805.5 FOR UNVENTED.
 - ARE THE ROOF JOISTS VENTED?
  
 12) 806.5 FBC[R] UNVENTED ATTIC AND UNVENTED ENCLOSED
 RAFTER ASSEMBLIES. 5.1.2. WHERE AIR-PERMEABLE
 INSULATION IS PROVIDED INSIDE THE BUILDING THERMAL
 ENVELOPE, IT SHALL BE INSTALLED IN ACCORDANCE WITH
 SECTION 5.1.1. IN ADDITION TO THE AIR-PERMEABLE
 INSULATION INSTALLED DIRECTLY BELOW THE STRUCTURAL
 SHEATHING, RIGID BOARD OR SHEET INSULATION SHALL BE
 INSTALLED DIRECTLY ABOVE THE STRUCTURAL ROOF SHEATHING
 IN ACCORDANCE WITH THE R-VALUES IN TABLE R806.5 FOR
 CONDENSATION CONTROL.
 - REVIEW THIS SECTION IF UNVENTED AT CEILING JOISTS.
  
 13) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT (P.A.)
 APPROVALS FOR SLIDING GLASS DOOR. IF NON IMPACT PROVIDE
 P.A. FOR SHUTTER PROTECTION
  
 14) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS
 FOR ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM
 DEFERED.
 - IF DEFERRED THE PRODUCT APPROVAL FOR FLAT ROOF WILL
 NEED TO BE SUBMITTED WITH ROOFING SUB PERMIT.
  
 15) 703.7.2.1 FBC[R] WEEP SCREEDS. A MINIMUM 0.019-INCH
 (0.5 MM) (NO. 26 GALVANIZED SHEET GAGE),
 CORROSION-RESISTANT WEEP SCREED OR PLASTIC WEEP SCREED,
 WITH A MINIMUM VERTICAL ATTACHMENT FLANGE OF 31/2
 INCHES (89 MM) SHALL BE PROVIDED AT OR BELOW THE
 FOUNDATION PLATE LINE ON EXTERIOR STUD WALLS IN
 ACCORDANCE WITH ASTM C926. THE WEEP SCREED SHALL BE
 PLACED NOT LESS THAN 4 INCHES (102 MM) ABOVE THE EARTH
 OR 2 INCHES (51 MM) ABOVE PAVED AREAS AND SHALL BE OF A
 TYPE THAT WILL ALLOW TRAPPED WATER TO DRAIN TO THE
 EXTERIOR OF THE BUILDING. THE WEATHER-RESISTANT BARRIER
 SHALL LAP THE ATTACHMENT FLANGE. THE EXTERIOR LATH
 SHALL COVER AND TERMINATE ON THE ATTACHMENT FLANGE OF
 THE WEEP SCREED.
  
 16) 703.7.3 FBC[R] WATER-RESISTIVE BARRIERS.
 WATER-RESISTIVE BARRIERS SHALL BE INSTALLED AS REQUIRED
 IN SECTION R703.2 AND,
 - THIS CALLS FOR 15 # FELT OVER THE PLYWOOD.
  
 17) 703.2 FBC[R] WATER-RESISTIVE BARRIER. ONE LAYER OF
 NO. 15 ASPHALT FELT, FREE FROM HOLES AND BREAKS,
 COMPLYING WITH ASTM D226 FOR TYPE 1 FELT OR OTHER
 APPROVED WATER-RESISTIVE BARRIER SHALL BE APPLIED OVER
 STUDS OR SHEATHING OF ALL EXTERIOR WALLS.
 - THE SECOND LAYER CAN BE THE PAPER BACK LATH .
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-05-09 Cont ID  
Sent By ppetty Date 2019-05-09 Time 09:29 Rev Time 0.00
Received By ppetty Date 2019-05-09 Time 09:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-17 Cont ID  
Sent By dbattles Date 2019-05-17 Time 15:54 Rev Time 0.00
Received By dbattles Date 2019-04-15 Time 11:33 Sent To  
Notes
2019-04-16 11:33:14R08

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-05-17 Cont ID  
Sent By dbattles Date 2019-05-17 Time 13:46 Rev Time 0.00
Received By dbattles Date 2019-05-17 Time 13:46 Sent To  
Notes
2019-05-17 13:46:49109 FBC[AMENDED] PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. ?CALL (561) 233-5025. ?UPON APPROVAL, YOU
 MAY CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. ?PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-05-15 Cont ID  
Sent By cmontell Date 2019-05-15 Time 13:37 Rev Time 0.00
Received By cmontell Date 2019-05-15 Time 13:37 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-05-17 Cont ID  
Sent By dbattles Date 2019-05-17 Time 13:47 Rev Time 0.00
Received By dbattles Date 2019-05-17 Time 13:47 Sent To  
Notes
2019-05-17 13:47:30SEE BUILDING REVIEW COMMENTS.