Plan Review Details - Permit 19040663
Plan Review Stops For Permit 19040663
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-07-05 Cont ID  
Sent By cthroop Date 2019-07-05 Time 08:01 Rev Time 0.00
Received By cthroop Date 2019-06-25 Time 10:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-06-10 Cont ID  
Sent By jgomez Date 2019-06-10 Time 18:23 Rev Time 0.00
Received By jgomez Date 2019-06-10 Time 09:31 Sent To  
Notes
2019-06-10 09:57:48SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
  
 NOTE:
 PLANS THAT WERE REVIEWED THE FIRST TIME WERE NOT
 RE-SUBMITTED. THIS MAKES THE REVIEW MORE DIFFICULT
 BECAUSE THERE IS NO REFERENCE OF WHAT WAS REVIEWED. IN
 THE FUTURE PLEASE SUBMIT THE PLANS THAT WERE REVIEWED
 TO HELP EXPEDITE THE REVIEW PROCESS. THANK YOU.
  
  
  
 1) OK.
  
 ORIGINAL COMMENT:
 2) THE COVERSHEET UNDER THE HEADING OCCUPANCY LOADS
 STATES THE CUSTOMER AREA AS BASED ON STANDING
 UNCONCENTRATED TABLES AND CHAIRS @ 15 SQ. FT. PER
 OCCUPANT. PLEASE REVIEW THE 2017 FBC-B
 TABLE 1004.1.2.
 ASSEMBLY WITHOUT FIXED SEATS
 CONCENTRATED (CHAIRS ONLY- NOT FIXED 7 NET
 STANDING SPACE 5 NET
 UNCONCENTRATED (TABLES & CHAIRS) 15 NET
  
 YOU NEED TO DECIDE IF YOU ARE TAKING THE SQUARE FEET AT
 STANDING 441/5= 89 OCCUPANTS REQUIRING 2 EXITS.
 OR
 IF YOU ARE TAKING THE UNCONCENTRATED (TABLES & CHAIRS)
 @ 15 NET. 441/15=30 OCCUPANTS.
  
 RESPONSEE:
 REVISED CALCULATIONS SHOW 10 PEOPLE AS THE TOTAL NUMBER
 OF PEOPLE. THIS IS INCORRECT. THE OCCUPANT LOAD IS
 BASED ON THE ACTUAL FUNCTION OF EACH SPACE AS REQUIRED
 BY TABLE 1004.1.2 FBC-BUILDING. PROVIDE THE OCCUPANT
 LOAD OF EACH ROOM OR AREA AS REQUIRED BY SEC.
 1004.1.1.1 FBC-BUILDING, THEN ADD THEM UP AND PROVIDE
 THE TOTAL OCCUPANT LOAD.
 NOTE: THE BUSINESS CLASSIFICATION IS JUST FOR THE
 OCCUPANCY CLASSIFICATION SINCE THIS IS AN SMALL
 ASSEMBLY GROUP WITH AN OCCUPANT LOAD OF LESS THAN 50
 PEOPLE. OCCUPANT LOAD IS ALWAYS CALCULATED USING TABLE
 1004.1.2.
  
 ORIGINAL COMMENT:
 3) PLEASE NOTE ON THE COVER SHEET THE DESIGNER OF
 RECORD HAS THE NUMBER OF EXITS REQUIRED AS 1 BUT 2
 PROVIDED AND THE MAXIMUM TRAVEL DISTANCE OF 27 FEET 6
 INCHES. IF THE TRAVEL DISTANCE IS GOING TO BE TAKEN
 FROM THE MIDDLE OF THE FLOOR REQUIRING THE 2 EXITS,
 THEN SHOW COMPLIANCE WITH:
 2017 ACCESS. CODE 206.4.1 PUBLIC ENTRANCES. IN ADDITION
 TO ENTRANCES REQUIRED BY 206.4.2 THROUGH 206.4.9, AT
 LEAST 60 PERCENT OF ALL PUBLIC ENTRANCES SHALL COMPLY
 WITH 404.
  
 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF
 EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
  
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
 THERE IS AT LEAST A 6 INCH DROP OUT THE BACK DOOR TO
 THE COURTYARD DECK MAKING IT NOT ABLE TO BE AN
 ACCESSIBLE MEANS OF EGRESS.
  
 RESPONSE:
 A)THE MEASUREMENT OF THE TRAVEL DISTANCE IS TAKEN FROM
 THE MOST REMOTE POINT TO THE ENTRANCE TO AN EXIT. SEE
 SEC. 1017.3 FBC-BUILDING. LIFE SAFETY PLAN ON SHEET A-1
 SHOWS THE DISTANCE FROM THE REAR DOOR TO THE ENTRY
 DOOR. CLARIFY WHY MEASURING THE DISTANCE FROM ONE DOOR
 TO THE OTHER. IT LOOKS LIKE THE MOST REMOTE POINT WOULD
 BE THE FREEZER. REVISE AS REQUIRED.
  
 B) REVISE THE EGRESS WIDTH INFORMATION SHOWN ON SHEET
 CVR:
 (1)REVISE THE NUMBER OF OCCUPANTS. SEE RESPONSE TO
 COMMENT #2 ABOVE AND REVISE THE EGRESS WIDTH PROVIDED.
 36" PROVIDED IS INCORRECT. THE WIDTH PROVIDED IS THE
 CLEAR WIDTH OPENING NOT THE SIZE OF THE DOOR. SEE SEC.
 1010.1.1 FBC-BUILDING FOR PROPER WAY OF DIMENSIONING
 THE CLEAR WIDTH AND REVISE AS REQUIRED. TYPICALLY A 36"
 DOOR WOULD PROVIDE 32" CLEAR WIDTH OPENING. NOTE:
 PROVIDE THE SIZE OF THE EXISTING DOORS. DORO SCHEDULE
 DOESN'T SPECIFY THE SIZE OF THE EXISTING DOORS. THIS
 INFORMATION IS REQUIRED.
  
 (1)THERE IS NOT TABLE 1005.1 IN TH FBC-BUILDING CODE.
  
  
 4) OK. ARCHITECT'S RESPONSE LETTER STATES THAT " THE
 TENANT DOES NOT INTEND TO USE THE COURTYARD FOR
 SEASONAL SEATING".
  
 4A) OK.
  
 4B) OK.
  
 4C) OK.
  
 4D)OK.
  
 ORIGINAL COMMENT:
 4D)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 RESPONSE:
 KNEE AND TOE CLEARANCES WERE NOT PROVIDED. THERE ARE NO
 DETAILS FOR FRONT COUNTER AND PICK UP COUNTER BY THE
 PREP/SERV AREA.
 ALSO, CLARIFY WHERE DOES RECEPTION COUNTER ADA DETAIL
 5/A-2 APPLIES TO?. SEC. 107.2.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 4D)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 RESPONS:
 THE HEIGHT OF THE PICK UP COUNTER DOESN'T COMPLY.
 REVISE AS REQUIRED.
 ALSO, CLARIFY WHERE DOES RECEPTION COUNTER ADA DETAIL
 5/A-2 APPLIES TO?. SEC. 107.2.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 5) THE VALUE FOR THIS PERMIT IS EXTREMELY LOW
 CONSIDERING ALL OF THE KITCHEN EQUIPMENT THAT IS GOING
 INTO THIS SPACE AND THE REQUIRED GREASE TRAP. 109.3*
 BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 RESPONSE:
 PLEASE PROVIDE THE ITEMIZED LIST REQUESTED BY THE
 PREVIOUS PLANS EXAMINER. INLCUDE THE DESIGN
 PROFESSIONAL FEES.
  
  
 ORIGINAL COMMENT:
 6) PLEASE PROVIDE THE DIMENSION OF THE EXISTING
 RESTROOM TO SEE IF THE RESTROOM COMPLIES WITH THE 2017
 FBC-ACCESSIBILITY CODE? 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 RESPONSE:
 ARCHITECT'S RESPONSE LETTER STATES THAT THE RESTROOM
 DESIGN HAS BEEN REVISED TO CONFORM TO THE 2017
 FBC-ACCESSIBILITY CODE".
 FLOOR PLANS WERE REVISED BUT IS NOT CLEAR WHAT WALLS
 ARE NEW AND WHAT WALLS ARE EXISTING. PLEASE COORDINATE
 WITH THE WALL PLAN LEGEND AND REVISE ACCORDINGLY TO
 AVOID CONFUSION. SEC. 107.2.1 CITY AMENDMENTS.
  
  
 7) OK.
  
 ORIGINAL COMMENT:
 8) SHEET A-1 SHOWS UNDER THE STAIR STORAGE. PLEASE SHOW
 HOW COMPLIANCE WITH THE 2017 FBC-B SECTION
 1011.7.3 ENCLOSURES UNDER INTERIOR STAIRWAYS. THE WALLS
 AND SOFFITS WITHIN ENCLOSED USABLE SPACES UNDER
 ENCLOSED AND UNENCLOSED STAIRWAYS SHALL BE PROTECTED BY
 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION OR THE
 FIRE-RESISTANCE RATING OF THE STAIRWAY ENCLOSURE,
 WHICHEVER IS GREATER.
  
 RESPONSE:
 DETAIL PROVIDED ON SHEET A-1 DOESN'T SEEM TO APPLY TO
 THE EXISTING CONDITIONS. PROVIDE DETAIL THAT MATCHES
 EXISTING CONDITIONS. SEC. 107.2.1 CITY AMENDMENTS.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. SUBMIT OLD DRAWINGS FOR REFERENCE. (PLEASE
 DON'T STAPLE OLD DRAWINGS TO RESUBMITTED PACKAGE). A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 10- A NEW CERTIFICATE OF OCCUPANCY WILL BE REQUIRED
 AFTER COMPLETION OF WORK.
 SEC. 1001.2 FBC-EXISTING BUILDING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-30 Cont ID  
Sent By jwitmer Date 2019-04-30 Time 12:35 Rev Time 0.00
Received By jwitmer Date 2019-04-30 Time 09:46 Sent To  
Notes
2019-04-30 12:34:582017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19040663
 ADD: 513 CLEMATIS ST. / SUITE: 103
 CONT: TBD/ TO BE DETERMINED
 TEL: 314-397-9047
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. APRIL 20/ 2019
 ACTION: DENIED
  
 1) THIS REVIEW, BUILDING WILL BE REVIEWING THIS TENANT
 SPACE AS A BUSINESS OCCUPANCY. THE USE BEFORE PERMITTED
 AS A BUSINESS OCCUPANCY (13070239/ 2010 FBC-B 303.1
 EXCEPT. 2) OCCUPANT LOAD LESS THAN 50. SHEET A-1 UNDER
 EGRESS AND LIFE SAFETY NOTES INDICATES A MERCANTILE
 OCCUPANCY WHERE A ON THIS SAME PAGE THE FLAME SPREAD
 RATINGS ARE TAKEN FOR A BUSINESS OCCUPANCY. DISCREPANCY
 IN THE OCCUPANCY TYPE?
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) THE COVERSHEET UNDER THE HEADING OCCUPANCY LOADS
 STATES THE CUSTOMER AREA AS BASED ON STANDING
 UNCONCENTRATED TABLES AND CHAIRS @ 15 SQ. FT. PER
 OCCUPANT. PLEASE REVIEW THE 2017 FBC-B
 TABLE 1004.1.2.
 ASSEMBLY WITHOUT FIXED SEATS
 CONCENTRATED (CHAIRS ONLY- NOT FIXED 7 NET
 STANDING SPACE 5 NET
 UNCONCENTRATED (TABLES & CHAIRS) 15 NET
  
 YOU NEED TO DECIDE IF YOU ARE TAKING THE SQUARE FEET AT
 STANDING 441/5= 89 OCCUPANTS REQUIRING 2 EXITS.
 OR
 IF YOU ARE TAKING THE UNCONCENTRATED (TABLES & CHAIRS)
 @ 15 NET. 441/15=30 OCCUPANTS
  
 3) PLEASE NOTE ON THE COVER SHEET THE DESIGNER OF
 RECORD HAS THE NUMBER OF EXITS REQUIRED AS 1 BUT 2
 PROVIDED AND THE MAXIMUM TRAVEL DISTANCE OF 27 FEET 6
 INCHES. IF THE TRAVEL DISTANCE IS GOING TO BE TAKEN
 FROM THE MIDDLE OF THE FLOOR REQUIRING THE 2 EXITS,
 THEN SHOW COMPLIANCE WITH:
 2017 ACCESS. CODE 206.4.1 PUBLIC ENTRANCES. IN ADDITION
 TO ENTRANCES REQUIRED BY 206.4.2 THROUGH 206.4.9, AT
 LEAST 60 PERCENT OF ALL PUBLIC ENTRANCES SHALL COMPLY
 WITH 404.
  
 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF
 EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
  
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
 THERE IS AT LEAST A 6 INCH DROP OUT THE BACK DOOR TO
 THE COURTYARD DECK MAKING IT NOT ABLE TO BE AN
 ACCESSIBLE MEANS OF EGRESS.
  
 4) IF THE TENANT INTENDS TO USE THE COURTYARD AREA FOR
 SEASONAL SEATING, THEN THE BACK DOOR WILL NEED TO HAVE
 AN UPPER LANDING AND AN ACCESSIBLE RAMP TO THE
 COURTYARD AREA. HANDRAILS MAYBE REQUIRED ON THE
 DIFFERENCE IN GRADE.
 4A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 4B) 226.2 DISPERSION. DINING SURFACES REQUIRED TO
 COMPLY WITH 902 SHALL BE DISPERSED THROUGHOUT THE SPACE
 OR FACILITY CONTAINING DINING SURFACES AND WORK
 SURFACES.
  
 4C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 4D) 902.1 .DINING SURFACES SHALL COMPLY WITH 902.2 AND
 902.3. ADVISORY 902.1 GENERAL. DINING SURFACES INCLUDE,
 BUT ARE NOT LIMITED TO, BARS, TABLES, LUNCH COUNTERS,
 AND BOOTHS
  
 4D)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 4D)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5) THE VALUE FOR THIS PERMIT IS EXTREMELY LOW
 CONSIDERING ALL OF THE KITCHEN EQUIPMENT THAT IS GOING
 INTO THIS SPACE AND THE REQUIRED GREASE TRAP. 109.3*
 BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 6) PLEASE PROVIDE THE DIMENSION OF THE EXISTING
 RESTROOM TO SEE IF THE RESTROOM COMPLIES WITH THE 2017
 FBC-ACCESSIBILITY CODE? 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 7) PLEASE PROVIDE COMPLIANCE WITH THE 2017
 FBC-ACCESSIBILITY CODE SECTION:
 202.4.1 DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA.
  
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY. WHEN THE COST OF ALTERATIONS
 NECESSARY TO MAKE THE PATH OF TRAVEL TO THE ALTERED
 AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO THE COST
 OF THE OVERALL ALTERATION, THE PATH OF TRAVEL SHALL BE
 MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE MADE
 ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE COSTS. IN
 CHOOSING WHICH ACCESSIBLE ELEMENTS TO PROVIDE, PRIORITY
 SHOULD BE GIVEN TO THOSE ELEMENTS THAT WILL PROVIDE THE
 GREATEST ACCESS, IN THE FOLLOWING ORDER: (I) AN
 ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (III) AT LEAST ONE ACCESSIBLE RESTROOM
 FOR EACH SEX OR A SINGLE UNISEX RESTROOM; (IV)
 ACCESSIBLE TELEPHONES; (V) ACCESSIBLE DRINKING
 FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 EITHER THE DESIGNER OF RECORD OR CONTRACTOR ON THEIR
 LETTERHEAD CAN SHOW WHERE 0.20 % OF THE VALUE OF THE
 PROJECT, THIS ENCLUDESDESIGN FEES, IS GOING TO MAKE
 THIS UNIT ACCESSIBLE.
  
 8) SHEET A-1 SHOWS UNDER THE STAIR STORAGE. PLEASE SHOW
 HOW COMPLIANCE WITH THE 2017 FBC-B SECTION
 1011.7.3 ENCLOSURES UNDER INTERIOR STAIRWAYS. THE WALLS
 AND SOFFITS WITHIN ENCLOSED USABLE SPACES UNDER
 ENCLOSED AND UNENCLOSED STAIRWAYS SHALL BE PROTECTED BY
 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION OR THE
 FIRE-RESISTANCE RATING OF THE STAIRWAY ENCLOSURE,
 WHICHEVER IS GREATER.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-07-12 Cont ID  
Sent By jpearson Date 2019-07-12 Time 08:19 Rev Time 0.00
Received By jpearson Date 2019-07-12 Time 07:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-05-31 Cont ID  
Sent By ppetty Date 2019-05-31 Time 11:10 Rev Time 0.00
Received By ppetty Date 2019-05-31 Time 11:10 Sent To  
Notes
2019-05-31 11:10:43CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30
 2. PROVIDE ACCURATE LOAD CALCULATION FOR COMMERCIAL
 SERVICE INCLUDING ALL LOADS. NEC 220; WPB FBC 107.2.1
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
 10. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-05-07 Cont ID  
Sent By jpearson Date 2019-05-07 Time 15:55 Rev Time 0.00
Received By jpearson Date 2019-05-07 Time 14:27 Sent To  
Notes
2019-05-07 15:54:57CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30
 2. PROVIDE ACCURATE LOAD CALCULATION FOR COMMERCIAL
 SERVICE INCLUDING ALL LOADS. NEC 220; WPB FBC 107.2.1
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
 4. PROVIDE GFCI PROTECTION FOR ALL RECEPTACLES IN FOOD
 PREP / KITCHEN AREAS. NEC 210.8
 5. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC EC C405.2
 6. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 7. NOTE 1 STATES THE 2010 FBC AS BASIS OF DESIGN.
 PROVIDE CORRECTION. FBC PREFACE
 8. SOME OF THE ELECTRICAL NOTES ARE THOSE USED FOR
 RESIDENTIAL APPLICATIONS. REMOVE ANY NOTES NOT
 PERTAINING TO THIS JOB. WPB FBC 107.2.1
 9. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 10. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-07-08 Cont ID  
Sent By pleduc Date 2019-07-08 Time   Rev Time 0.00
Received By pleduc Date 2019-07-08 Time 14:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-05-23 Cont ID  
Sent By pleduc Date 2019-05-23 Time   Rev Time 0.00
Received By pleduc Date 2019-05-23 Time 14:53 Sent To  
Notes
2019-05-23 15:30:565/23/19
  
 IN A EFFORT TO MOVE THIS PROJECT FORWARD THE FOLLOWING
 WAS PROVIOSED
  
  
 1) SHEET CVR - YOUR OCCUPANCY CLASSIFICATION WAS
 MODIFIED AND LOADS RECLACULATED PER THE FLORIDA FIRE
 PREVENTION CODE.
  
 USING A BUSINESS OCCUPANCY CALCULATION OF 10 FOR THIS
 ENTIRE SPACE IS AN INCORRECT APPLICATION OF THE CODE.
  
 THIS IS AN ASSEMBLY OCCUPANCY WITH LESS THAN 50 PERSON,
 AND THUSLY MERCANTILE PER THE FFPC.
  
 THE OCCUPANCY LOAD CALCULATION; HOWEVER, DOES NOT
 CHANGE FOR THE ASSEMBLY SPACE.
  
 YOU WERE GIVEN CREDIT FOR BUSINESS, KITCHEN AND STORAGE
 USE FORMULAS IN THOSE OTHER APPLICABLE AREAS .
  
 YOUR TOTAL OCCUPANCY LOAD IS 31.
  
  
 2) SHOULD YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE
 CONTACT MY OFFICE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-05-01 Cont ID  
Sent By pleduc Date 2019-05-01 Time   Rev Time 0.00
Received By pleduc Date 2019-05-01 Time 14:03 Sent To  
Notes
2019-05-01 14:20:08THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET CVR & A 1 - THERE IS AN INDICATION OF ONE EXIT
 REQUIRED AND TWO PROVIDED. SHEET A 1 INDICATES THAT THE
 BATHROOM AND OFFICE DOORS OPEN INTO THE EXIT CORRIDOR
 ENCROACHING INTO THE REQUIRED EGRESS WIDTH.
  
 PER NFPA 101, CH 7, MEANS OF EGRESS
  
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR
 LEAF IS FULLY OPEN.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 2) SHEET E 1 & A 1 - THERE ARE NO INDICTIONS, EXISTING
 OR PROPOSED, OF EXITS SIGNS OVER THE EXIT DOORS.
  
 PER NFPA 101 CH 7, MEANS OF EGRESS
  
 7.10 MARKING OF MEANS OF EGRESS.
 7.10.1 GENERAL.
 7.10.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE
 MARKED IN
 ACCORDANCE WITH SECTION 7.10 WHERE REQUIRED IN CHAPTERS
 11
 THROUGH 43.
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS.
  
 PER NFPA 101, NEW MERCANTILE OCCUPANCIES
  
 36.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL
 BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8.
  
 7.8 ILLUMINATION OF MEANS OF EGRESS.
 7.8.1 GENERAL.
 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN
 ACCORDANCE WITH SECTION 7.8 FOR EVERY BUILDING AND
 STRUCTURE WHERE
 REQUIRED IN CHAPTERS 11 THROUGH 43. FOR THE PURPOSES OF
 THIS
 REQUIREMENT, EXIT ACCESS SHALL INCLUDE ONLY DESIGNATED
 STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING
 TO AN EXIT. FOR THE
 PURPOSES OF THIS REQUIREMENT, EXIT DISCHARGE SHALL
 INCLUDE ONLY
 DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS,
 ESCALATORS, WALKWAYS, AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY.
 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 CONTINUOUS DURING THE
 TIME THAT THE CONDITIONS OF OCCUPANCY REQUIRE THAT THE
 MEANS OF EGRESS
 BE AVAILABLE FOR USE, UNLESS OTHERWISE PROVIDED IN
 7.8.1.2.2.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 3) SHEET A 1 - THERE IS AN INCORRECT REFERENCE, 2014,
 OF NFPA. IS THIS REFERENCE A GENERAL REFERENCE OR
 SPECIFIC ONE?
  
 THE CURRENT EDITION OF NFPA 1 PER THE FLORIDA FIRE
 PREVENTION CODE IS 2015.
  
 PLEASE REVIEW ANC CLARIFY AND/OR CORRECT.
  
  
  
 4) SHEET CVR - THE IS AN INDICATION UNDER CODE RESEACH:
 OCCUPANCY, OF BUSINESS (B GROUP)
  
 PER THE FLORIDA FIRE PREVENTION CODE THIS WOULD BE
 CONSIDERED A MERCANTILE OCCUPANCY;(ASSEMBLY LESS THAN
 50)
  
 PLEASE REVIEW AND PROVIDE A CARRECTIVE NOTE FOR THE
 FFPC AND ENSURE COMPLIANCE.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 3 Status N Date 2019-07-12 Cont ID  
Sent By fmittner Date 2019-07-12 Time 16:24 Rev Time 0.00
Received By fmittner Date 2019-07-12 Time 16:24 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-06-04 Cont ID  
Sent By fmittner Date 2019-06-04 Time 11:30 Rev Time 0.00
Received By fmittner Date 2019-06-04 Time 11:30 Sent To P
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-05-09 Cont ID  
Sent By fmittner Date 2019-05-09 Time 09:26 Rev Time 0.00
Received By fmittner Date 2019-05-09 Time 09:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-07-15 Time   Rev Time 0.00
Received By lmarchan Date 2019-06-20 Time 12:56 Sent To  
Notes
2019-06-24 12:56:49B27

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-13 Cont ID  
Sent By lmarchan Date 2019-06-13 Time 10:29 Rev Time 0.00
Received By lmarchan Date 2019-05-21 Time 14:06 Sent To  
Notes
2019-05-22 14:06:59B14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-09 Cont ID  
Sent By cpuell Date 2019-05-09 Time 10:17 Rev Time 0.00
Received By cpuell Date 2019-04-15 Time 14:11 Sent To  
Notes
2019-04-15 14:11:26B25

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-04-30 Cont ID  
Sent By jwitmer Date 2019-04-30 Time 12:32 Rev Time 0.00
Received By jwitmer Date 2019-04-30 Time 09:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-07-15 Cont ID  
Sent By ccole Date 2019-07-15 Time 10:52 Rev Time 0.00
Received By ccole Date 2019-07-10 Time 10:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-06-11 Cont ID  
Sent By ccole Date 2019-06-11 Time 11:48 Rev Time 0.00
Received By ccole Date 2019-06-11 Time 11:42 Sent To  
Notes
2019-06-11 12:04:061ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19040663
 6/11/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SEPARATE PERMITS ARE REQUIRED FOR THE WALK-IN
 FREEZER AND ANY PROPOSED KITCHEN EXHAUST HOODS AND FIRE
 SUPPRESSION SYSTEMS- SECTION 107.2.1 WPB. PLEASE PLACE
 A NOTE ON THE PLAN ACCORDINGLY.
  
 2) ALTHOUGH THE PLAN INDICATES NO MECHANICAL WORK,
 THERE IS A REQUIREMENT TO VERIFY ADEQUATE VENTILATION
 IS BEING PROVIDED TO THE NEW SPACES. PLEASE REFER TO
 SECTION 809.2 FBC-17 EXISTING BUILDING CODE AND PROVIDE
 MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS AND
 SPACES PER TABLE 403.3.1.1 FBC-17 MECHANICAL. PROVIDE A
 SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED CFMS
 OF OUTDOOR AIR.
  
 3) COOKING KITCHENS REQUIRE AN EXHAUST SYSTEM SIZED AT
 A RATE 0.7 CFMS PER SQUARE FT, AND RECIRCULATION OF AIR
 FROM THE KITCHEN TO OTHER ROOMS AND SPACES IS
 PROHIBITED- SEE TABLE 403.1.1 FBC M FOOTNOTE B. PLEASE
 CLARIFY IF ANY ELECTRIC OR GAS-FIRED COOKING
 APPLLIANCES ARE TO BE INSTALLED AND PROVIDE AN
 EQUIPMENT SCHEDULE AND PLAN IF APPLICABLE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-07-11 Cont ID  
Sent By gjohnson Date 2019-07-11 Time 14:37 Rev Time 0.00
Received By gjohnson Date 2019-07-11 Time 08:51 Sent To  
Notes
2019-07-11 14:46:04PROVISO PLANS REDLINED.
  
 1) EACH BUILDING DRAIN REQUIRES 1 VENT THAT EXTENDS TO
 THE OUTDOORS. THE DIPPING WELL, HAND SINK, AND THE ICE
 CUBE DRAIN ALL SHOW AAV VENTS. PROVIDE 1 THAT VENTS TO
 THE OUTDOORS ON THIS BUILDING DRAIN. FBC P 904.1. THE
 ONLY VENT THAT EXTENDS IS ON THE INLET SIDE OFT HE
 GREASE INTERCEPTOR.
  
 3) PROVIDE SHUT OFF VALVES AT THE TOP OF EVERY WATER
 DOWN FEED PIPE. FBC P 606.1 (5). ACCESS PANEL TO THESE
 VALVES SHALL BE PROVIDE. FBC P606.3
  
 4) PROVIDE BATHROOM ACCESSIBILITY DETAILS FOR THE GRAB
 BARS AND THE TOILET PAPER HOLDER. FBC-ACC 604.5.1,
 604.5.2, 604.7, 603.3, 604.2, 604.6, 604.4, 606.3,
 609.4
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2019-07-08 Cont ID  
Sent By thunt Date 2019-07-08 Time 12:07 Rev Time 0.00
Received By thunt Date 2019-07-08 Time 09:09 Sent To  
Notes
2019-07-08 12:07:02PLUMBING 3RD REVIEW**DENIED**
  
 1) EACH BUILDING DRAIN REQUIRES 1 VENT THAT EXTENDS TO
 THE OUTDOORS. THE DIPPING WELL, HAND SINK, AND THE ICE
 CUBE DRAIN ALL SHOW AAV VENTS. PROVIDE 1 THAT VENTS TO
 THE OUTDOORS ON THIS BUILDING DRAIN. FBC P 904.1. THE
 ONLY VENT THAT EXTENDS IS ON THE INLET SIDE OFT HE
 GREASE INTERCEPTOR.
  
 2) SHT. P1 PLUMBING ISOMETRIC THE TOILET IS MISSING
 FROM THE DRAWING. FBC 107.3.5
  
 3) PROVIDE SHUT OFF VALVES AT THE TOP OF EVERY WATER
 DOWN FEED PIPE. FBC P 606.1 (5). ACCESS PANEL TO THESE
 VALVES SHALL BE PROVIDE. FBC P606.3
  
 4) PROVIDE BATHROOM ACCESSIBILITY DETAILS FOR THE GRAB
 BARS AND THE TOILET PAPER HOLDER. FBC-ACC 604.5.1,
 604.5.2, 604.7
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-06-12 Cont ID  
Sent By gjohnson Date 2019-06-12 Time 09:18 Rev Time 0.00
Received By gjohnson Date 2019-06-06 Time 11:29 Sent To  
Notes
2019-06-12 09:19:17 
 2ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. YOUR SIZING CALCULATION FOR YOUR GREASE INTERCEPTOR
 IS INACCURATE THIS FORMULA IS MEANT TO BE USED FOR
 LARGER SIT DOWN RESTAURANTS AND IT IS ONLY LISTING 1
 SEAT AND THE PLAN SHOWS 4, YOU NEED TO USE THE
 CALCULATIONS THE USE THE VOLUME OF THE SINKS TO
 DETERMINE THE GPM ALSO KNOWN AS THE PDI METHOD. IN
 ORDER TO APPROVE THIS INTERCEPTOR YOU SHALL PROVIDE
 SIZING CALCULATIONS FROM THE MANUFACTURE THEY CAN BE
 EASILY FOUND ON THE MANUFACTURE,S WEB SITE. PER FBC PL
 1003.2 AND WPB AMEND TO FBC 107.2.1
  
 2. YOU PROVIDED MANUFACTURE SPECIFICATIONS BUT YOU DID
 NOT LIST THE MODEL THAT YOU WILL BE USING PLEASE MARK
 THE MODEL ON THE SPECS AND PROVIDE MANUFACTURE
 INSTALLATION GUIDE. WPB AMEND TO FBC 107.2.1
  
 3. YOUR SANITARY ISOMETRIC IS NOTING STUDOR VENTS ON
 ALL OF THE VENT STACKS AT LEAST ONE OF THE VENTS SHALL
 DISCHARGE TO THE EXTERIOR OF THE BUILDING.PER FBC PL
 904.1
  
 4. THE ICE MACHINE REQUIRES A AIR HAMMER ARRESTOR
 LOCATE AT THE APPLIANCE.PER FBC PL 604.9
  
 5. SHUT OFF VALVES ARE REQUIRED AT ALL DROPS ON THE HOT
 AND COLD WATER SYSTEM PLEASE SHOW ON ISOMETRIC . PER
 FBC PL 606.1(5)
  
 6. PLEASE NOTE ON THE PLAN THE EXISTING FLOOR DRAIN
 SHALL HAVE A TRAP PRIMER.FBC PL 1002.4.1
  
 7. THE 3 COMP SINK AND THE PREP SINK SHALL BE INDIRECT
 WASTE PLEASE NOT ON PLAN. PER FBC PL 802.1.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-25 Cont ID  
Sent By gjohnson Date 2019-04-25 Time 12:11 Rev Time 0.00
Received By gjohnson Date 2019-04-25 Time 09:02 Sent To  
Notes
2019-04-25 12:12:261ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE PREVIOUS OCCUPANCY OF THE THIS SPACE WAS A
 MERCANTILE WHICH WOULD MAKE THIS A CHANGE OF OCCUPANCY
 NOT LEVEL 2 ALTERATION. PER BUSINESS LICENSE RECORD OF
 PROPERTY. SHALL COMPLY WITH FBC EX 506.1 AND CH 10
  
 2. THE COVER SHEET STATES AS BUSINESS OCCUPANCY SHT A-1
 UNDER LIFE SAFETY NOTES LIST IT AS MERCANTILE PLEASE
 CLARIFY. THIS IS AN ASSEMBLY THAT IS CLASSIFIED AS A
 BUSINESS PER FBC 303.1.1 SMALL BUILDINGS AND TENANT
 SPACES. A BUILDING OR TENANT SPACE USED FOR ASSEMBLY
 PURPOSES WITH AN OCCUPANT LOAD OF LESS THAN 50 PERSONS
 SHALL BE CLASSIFIED AS A GROUP B OCCUPANCY.
  
 3. TWO BATHROOMS ARE REQUIRED PER FBC PL 403.2 SEPARATE
 FACILITIES. WHERE PLUMBING FIXTURES ARE REQUIRED,
 SEPARATE FACILITIES SHALL BE PROVIDED FOR EACH SEX. PER
 FBC EX 1010.1
  
 4. IS THE EXISTING BATHROOM FULLY ACCESSIBLE PER 2017
 FBC ACC 6TH EDITION PLEASE SHOW LEVEL OF ACCESSIBILITY
 SUCH AS GRAB BARS TOILET AND LAVATORY AND CLEAR FLOOR
 SPACE FOR THE FIXTURES. PER WPB AMEND TO FBC 107.2.1. A
 MINIMUM OF 20% OF THE TOTAL COST OF THE JOB SHALL BE
 USED TO BRING UP THE LEVEL OF ACCESSIBILITY OF THE
 SPACE. PER FBC ACC 202.4, 202.4.1
  
 5.EVEN THOUGH THERE MAY NOT BE COCKING BEING DONE ANY
 TIME FOOD OR DRINKS ARE BEING MADE THAT COULD PRODUCE
 ANY TYPE OF GREASE SUCH AS DIARY , NUT BUTTERS A GREASE
 TRAP IS REQUIRED FOR ANY TYPE OF KITCHEN THERE ARE NO
 EXEMPTIONS. PER FBC PL 1003.1 AND WPB UTILITIES
 DEPARTMENT FOG PROGRAM
  
 6. PLEASE PROVIDE A WATER ISOMETRIC DRAWING. PER FBC PL
 107.3.5.1.3
  
 7. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC 416.5
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 2 Status P Date 2019-07-08 Cont ID  
Sent By thunt Date 2019-07-08 Time 12:07 Rev Time 0.00
Received By thunt Date 2019-07-08 Time 12:07 Sent To  
Notes
***NONE***

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status F Date 2019-06-12 Cont ID  
Sent By gjohnson Date 2019-06-12 Time 09:20 Rev Time 0.00
Received By gjohnson Date 2019-06-12 Time 09:20 Sent To  
Notes
2019-06-12 09:22:352NDREVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. YOUR SIZING CALCULATION FOR YOUR GREASE INTERCEPTOR
 IS INACCURATE THIS FORMULA IS MEANT TO BE USED FOR
 LARGER SIT DOWN RESTAURANTS AND IT IS ONLY LISTING 1
 SEAT AND THE PLAN SHOWS 4, YOU NEED TO USE THE
 CALCULATIONS THE USE THE VOLUME OF THE SINKS TO
 DETERMINE THE GPM ALSO KNOWN AS THE PDI METHOD. IN
 ORDER TO APPROVE THIS INTERCEPTOR YOU SHALL PROVIDE
 SIZING CALCULATIONS FROM THE MANUFACTURE THEY CAN BE
 EASILY FOUND ON THE MANUFACTURE,S WEB SITE. PER FBC PL
 1003.2 AND WPB AMEND TO FBC 107.2.1
  
 2. YOU PROVIDED MANUFACTURE SPECIFICATIONS BUT YOU DID
 NOT LIST THE MODEL THAT YOU WILL BE USING PLEASE MARK
 THE MODEL ON THE SPECS AND PROVIDE MANUFACTURE
 INSTALLATION GUIDE. WPB AMEND TO FBC 107.2.1
  
 3. PLEASE NOTE ON THE PLAN A SEPARATE PERMIT IS
 REQUIRED FOR THE GREASE INTERCEPTOR. PER WPB UTILITIES
 DEPT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2019-07-15 Cont ID  
Sent By llouie Date 2019-07-15 Time   Rev Time 0.00
Received By llouie Date 2019-07-15 Time   Sent To  
Notes
2019-07-15 11:31:02APPROVAL STAMPED ON 7/12/19 BY AAPONTE.

Review Stop Z ZONING
Rev No 1 Status P Date 2019-06-12 Cont ID  
Sent By aaponte Date 2019-06-12 Time 14:43 Rev Time 0.00
Received By aaponte Date 2019-06-12 Time 14:43 Sent To  
Notes
***NONE***