2019-04-19 14:23:57 | 04/18/19 REVIEWED FOR CODE COMPLIANCE |
| (PLUMBING/BACKFLOW) |
| |
| BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE |
| COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN |
| PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM |
| THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND |
| NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF |
| PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY |
| ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM |
| REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES |
| / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO |
| AVOID VOIDING OF THE PERMIT. |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER |
| |
| 04/15/2019 1ST PLUMBING/BACKFLOW REVIEW **DENIED** WITH |
| COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. THIS PRESSURE VACUUM BREAKER MODEL 800M4FR IS NOT A |
| LEAD-FREE DEVICE WHICH IS REQUIRED BY THE CITY OF WEST |
| PALM BEACH UTILITY DEPARTMENT. YOU CAN REFER TO THEIR |
| CROSS CONNECTION MANUAL IN THE CITY WEB SITE HTTP://WPB |
| .ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLICATIONS/BA |
| CKFLOW-CROSS-CONNECTION-CONTROL-MANUAL FOR MORE |
| INFORMATION. THE LF800M4QT MODEL IS A LEAD FREE DEVICE |
| SO PLEASE RESUBMIT SPECS FOR IT. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| LUIS A. CRESPO |
| PLUMBING INSPECTOR / |
| PLUMBING PLAN REVIEW |
| AVAILABLE FROM 1:00 PM TO 4:00 PM |
| [email protected] |
| 561-805-6720 |
| |