Plan Review Details - Permit 19040567
Plan Review Stops For Permit 19040567
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-19 Cont ID  
Sent By lcrespo Date 2019-04-19 Time 14:21 Rev Time 0.00
Received By lcrespo Date 2019-04-19 Time 14:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-15 Cont ID  
Sent By lcrespo Date 2019-04-15 Time 07:23 Rev Time 0.00
Received By lcrespo Date 2019-04-15 Time 07:02 Sent To  
Notes
2019-04-12 13:35:55PLUMB <5K

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-04-19 Cont ID  
Sent By lcrespo Date 2019-04-19 Time 14:20 Rev Time 0.00
Received By lcrespo Date 2019-04-19 Time 14:20 Sent To  
Notes
2019-04-19 14:23:5704/18/19 REVIEWED FOR CODE COMPLIANCE
 (PLUMBING/BACKFLOW)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  
 04/15/2019 1ST PLUMBING/BACKFLOW REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THIS PRESSURE VACUUM BREAKER MODEL 800M4FR IS NOT A
 LEAD-FREE DEVICE WHICH IS REQUIRED BY THE CITY OF WEST
 PALM BEACH UTILITY DEPARTMENT. YOU CAN REFER TO THEIR
 CROSS CONNECTION MANUAL IN THE CITY WEB SITE HTTP://WPB
 .ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLICATIONS/BA
 CKFLOW-CROSS-CONNECTION-CONTROL-MANUAL FOR MORE
 INFORMATION. THE LF800M4QT MODEL IS A LEAD FREE DEVICE
 SO PLEASE RESUBMIT SPECS FOR IT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-15 Cont ID  
Sent By lcrespo Date 2019-04-15 Time 07:23 Rev Time 0.00
Received By lcrespo Date 2019-04-15 Time 07:23 Sent To  
Notes
2019-04-18 13:46:48 
  
2019-04-15 07:23:4404/15/2019 1ST PLUMBING/BACKFLOW REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THIS PRESSURE VACUUM BREAKER MODEL 800M4FR IS NOT A
 LEAD-FREE DEVICE WHICH IS REQUIRED BY THE CITY OF WEST
 PALM BEACH UTILITY DEPARTMENT. YOU CAN REFER TO THEIR
 CROSS CONNECTION MANUAL IN THE CITY WEB SITE HTTP://WPB
 .ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLICATIONS/BA
 CKFLOW-CROSS-CONNECTION-CONTROL-MANUAL FOR MORE
 INFORMATION. THE LF800M4QT MODEL IS A LEAD FREE DEVICE
 SO PLEASE RESUBMIT SPECS FOR IT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  