2019-08-12 11:49:53 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19040448 |
| ADD: 2700 S AUSTRALIAN AVE. |
| CONT: AUTOBUILDERS GENERAL CONT. SVCS. INC. |
| TEL: 561-622-3515 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| 2ND REVIEW |
| DATE: MONDAY, AUGUST 12TH/2019 |
| ACTION: DENIED |
| |
| NOTICE: *************** 4X FEE / NOTICE!!!!! FLORIDA |
| STATUTE 553.80(2)(B) ****************** |
| WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| |
| 1) SHEET 002-G-101 THE LIFE SAFETY PLAN: |
| 1A).2ND REQUEST. UNDER THE HEADING BUILDING CODE |
| SUMMARY THE PROPOSED USE IS LISTED AS BUSINESS (B) AND |
| STORAGE (S1). PLEASE NOTE THAT THE SERVICE SHOP IS |
| LISTED AS A S1 OCCUPANCY. FOR MOTOR VEHICLE REPAIR |
| GARAGES COMPLYING WITH THE MAXIMUM ALLOWABLE QUANTITIES |
| OF HAZARDOUS MATERIALS LISTED IN TABLE 307.1(1). |
| PLEASE SUBMIT A LIST OF HAZARDOUS MATERIALS AND |
| ALLOWABLE QUANTITIES PER THE 2017 FBC-B TABLE 307.1(1). |
| |
| 1B) 2N REQUEST. UNDER THE HEADING OF BUILDING DATA THE |
| PLANS ARE INDICATED THEY ARE DESIGNED UNDER THE 2014 |
| FBC. PLEASE NOTE THAT THE 2017 FBC-B WAS ADOPTED |
| STATEWIDE ON DEC. 31/ 2017. PLEASE UPDATE PLANS. |
| |
| 1C) 2ND REQUEST. UNDER THE BUILDING DATA THERE IS NO |
| LISTING FOR THE REQUIRED AREA OF REFUGE, THIS IS A 2 |
| STORY BUILDING AND NO FIRE SPRINKLERS. THE 2017 |
| FBC-ACCESSIBILITY CODE UNDER SECTION 207 ACCESSIBLE |
| MEANS OF EGRESS. SECTION 207.1. MEANS OF EGRESS SHALL |
| COMPLY WITH SECTION 1007 OF THE INTERNATIONAL BUILDING |
| CODE (2003 EDITION). |
| PLEASE REVIEW IN THE 2003 IBC-B SECTIONS DEALING WITH: |
| 1007.3 ENCLOSED EXIT STAIRWAYS, 48 INCHES BETWEEN |
| HANDRAILS. |
| 1007.4 ELEVATORS. |
| 1007.6 AREAS OF REFUGE. |
| 1007.6.1. SIZE. |
| 1007.6.2. SEPARATION. |
| 1007.6.3. TWO-WAY COMMUNICATION. |
| 1007.6.4. INSTRUCTIONS. |
| 1007.6.5. IDENTIFICATION. |
| 1007.7.7. SIGNAGE. |
| |
| 1D) 2ND REQUEST. SEPARATED MIXED OCCUPANCY SHOWS THE |
| FORMULA FOR AREA CALCULATIONS BUT HAS LEFT THE |
| CALCULATION BLANK. PLEASE PROVIDE THE ACTUAL AND |
| ALLOWABLE SQUARE FEET FOR EACH OF THE OCCUPANCIES AND |
| THE END CALCULATION. 2017 FBC-B 508.3.3. |
| |
| 1E) COMPLIED. PLEASE NOTE THE PLANS DOES NOT STATE THE |
| ACTUAL OCCUPANT LOAD FOR EACH OF THE OCCUPANCIES. THE |
| EXIT WIDTH DOES PROVIDE THE AREA FOR EACH OCCUPANCY AND |
| AREA PER OCCUPANT (TABLE 1004.1.2) BUT DOES NOT GIVE |
| THE ACTUAL OCCUPANT LOAD PER STORY AND THE TOTAL |
| OCCUPANT LOAD. 2017 FBC-B 1004.1 & TABLE 1004.1.2. |
| |
| 1F)SEMI-COMPLIED. KEY NOTES ON SHEET 041-A-101 INDICATE |
| THE DESIGNER OF RECORD REQUIRING A 2 HOUR WALL BETWEEN |
| THE B & S1 OCCUPANCY AND DECLARING THE BLOCK TO COMPLY |
| WITH (U905). THIS DESIGN REQUIRES A D-2 A 8 INCH BLOCK, |
| AND 2 HOUR FIRE RATED CONCRETE BLOCK. PLEASE NOTE WE |
| WILL REQUIRE DOCUMENTATION FROM THE BLOCK MANUFACTURER |
| THAT THEIR 2 HOUR RATING OF BLOCK COMPLIES WITH TABLE |
| 722.3.2. (2017 FBC-B) MINIMUM EQUIVALENT THICKNESS OF |
| BEARING OR NONBEARING CONCRETE MASONRY WALLS. PROVIDE |
| THE TYPE OF AGGREGATE AND EQUIVALENT THICKNESS FOR THE |
| 2 HOUR FIRE RATING. THE SAME FOR 12 INCH WIDE BLOCK, |
| PROVIDE A LETTER FROM THE BLOCK MANUFACTURER. |
| THE OTHER ISSUE WITH NOTES 10 AND 11 GO BACK TO THE |
| WORD OR, 8 INCH OR 12 INCH BLOCK. THE REQUIREMENT HAS |
| TO BE SPECIFIC. 2017 WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1 ADMINISTRATIVE CODE |
| SECTION 107.2.1.3. DRAWINGS & SPECIFICATIONS SHALL |
| CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| INFORMATION SHALL BE SPECIFIC TO THE TECHNICAL CODES |
| "SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR THE TERM |
| "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR |
| SPECIFIC INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| 1ST ROUND COMMENT. THE LIFE SAFETY SHEET 002-G-101 |
| UNDER THE HEADING OF ALLOWABLE AREA, MIXED OCCUPANCY |
| INDICATES YES, AND SEPARATION 2 HRS. THE FIRST FLOOR |
| PARTS ROOM HAS A NOTE 2 HRS. IT WOULD APPEAR THAT THIS |
| NOTE REFERS TO THE BLOCK WALL BETWEEN THE BUSINESS |
| OCCUPANCY AND S1 REPAIR GARAGE. THE FIRST FLOOR PLAN |
| SHEET 041-A-101 HAS THIS SAME WALL WITH A WALL |
| IDENTIFICATION TAG IDENTIFIED AS WALL TYPE 10. SHEET |
| 042-A-102 THE SECOND FLOOR HAS THE SAME WALL TYPE |
| IDENTIFIED WITH A WALL IDENTIFICATION TAG AS WALL TYPE |
| 6. WHEN YOU OPEN UP SHEET 050-A-501 WALL TYPES NONE OF |
| THE WALL TYPES SHOWN HAVE THE SAME NAMING CONVENTION. |
| |
| 1G) 2ND REQUEST. SHEET A-501 WALL TYPES A3-A6 ALL SHOW |
| BLOCK WALLS WITH EITHER 8 INCH OR 12 INCH CMU. EACH |
| DETAIL SHOULD BE SPECIFIC TO BLOCK TYPE AND WALL TYPE. |
| AGAIN THESE DETAILS DO NOT MATCH THE WALL |
| IDENTIFICATION TAGS LOCATED IN SHEETS 041-A-101 AND |
| 042-A-102. INFORMATION ON THE PLANS HAS TO BE SPECIFIC |
| NO EITHER, OR. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| INFORMATION SHALL BE SPECIFIC. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| 1H) INFORMATIONAL ONLY. PLEASE NOTE THE DESIGNER OF |
| RECORD CAN DESIGN TO A MORE STRINGENT STANDARD, BUT |
| UNDER THE 2017 |
| FBC-B TABLE 508.4 THERE IS NO OCCUPANCY SEPARATION |
| REQUIRED BETWEEN A B AND S1 OCCUPANCY. IF THERE IS A |
| DIFFERENCE BETWEEN THE FIRE CODE AND BUILDING CODE THEN |
| THE MOST STRINGENT CODE PREVAILS. |
| |
| 1I) 2ND REQUEST, SEMI-COMPLIED. YOU HAVE NOT COMPLIED |
| WITH THE REQUIREMENTS OF COMMENT 1-C. THIS IS NEW |
| CONSTRUCTION, 2 STORY NOT SPRINKLERED REQUIRING AN AREA |
| OF REFUGE. |
| PLEASE REVIEW IN THE 2003 IBC-B SECTIONS DEALING WITH: |
| 1007.3 ENCLOSED EXIT STAIRWAYS, 48 INCHES BETWEEN |
| HANDRAILS. |
| 1007.4 ELEVATORS. |
| 1007.6 AREAS OF REFUGE. |
| 1007.6.1. SIZE. |
| 1007.6.2. SEPARATION. |
| 1007.6.3. TWO-WAY COMMUNICATION. |
| 1007.6.4. INSTRUCTIONS. |
| 1007.6.5. IDENTIFICATION. |
| 1007.7.7. SIGNAGE. |
| |
| |
| 1ST ROUND OF COMMENTS. THE LIFE SAFETY SHEET 002-G-101 |
| SHOWS A SECOND STORY BUSINESS AND STORAGE OCCUPANCY, |
| (ASSUMED |
| S-1). THE TRAVEL DISTANCE IS SHOWN GOING DOWN THROUGH |
| THE STAIRWAY MAKING THIS STAIRWAY EXIT ACCESS AND THE |
| TRAVEL DISTANCE ON THE STAIRS TO BE TAKEN PARALLEL TO |
| THE STAIRS. FROM THE FURTHEST POINT TAKEN ON THE SECOND |
| FLOOR TO THE FIRST FLOOR LANDING THE TRAVEL DISTANCE IS |
| BETWEEN 85 TO 90 FEET. THIS IS OVER THE ALLOWABLE |
| MAXIMUM COMMON PATH OF TRAVEL FROM TABLE 1006.3.2(2) OF |
| 75 FEET AND OCCUPANT LOAD OF 49 FOR BUSINESS OR 29 FOR |
| STORAGE OCCUPANCY. IF THE STAIRWAY WAS A RATED 1 HOUR |
| EXIT STAIRWAY WITH OPENING PROTECTIVES AND EXIT |
| PASSAGEWAY TO THE EXTERIOR, THEN THE TRAVEL DISTANCE |
| FOR THE 2ND FLOOR WOULD WORK. PLEASE REVIEW ALL OF THE |
| REQUIREMENTS FOR EXIT AND EXIT PASSAGEWAYS. EXIT |
| PASSAGEWAYS ARE FOUND UNDER FBC-B 1024. PLEASE REVIEW |
| VENTILATION REQUIREMENTS (FBC-B 1024.7) FOR EXIT |
| PASSAGEWAYS AS WELL. |
| |
| 1J) 2ND REQUEST. VERSION # 2 STILL DOES NOT SHOW |
| COMPLIANCE WITH FBC-B 1015.4 OPENING LIMITATIONS. |
| REQUIRED GUARDS SHALL NOT HAVE OPENINGS THAT ALLOW |
| PASSAGE OF A SPHERE 4 INCHES (102 MM) IN DIAMETER FROM |
| THE WALKING SURFACE TO THE REQUIRED GUARD HEIGHT. ALSO |
| THERE IS A DETAIL FOR RISE AND RUN BUT NO DIMENSION FOR |
| COMPLIANCE WITH 1015.4 FBC-B EXCEPTION 2. THE |
| TRIANGULAR OPENINGS AT THE OPEN SIDES OF A STAIR, |
| FORMED BY THE RISER, TREAD AND BOTTOM RAIL SHALL NOT |
| ALLOW PASSAGE OF A SPHERE 6 INCHES IN DIAMETER. |
| 1 ST ROUND OF COMMENTS. STAIRWAY GUARDRAIL. SHEET |
| 049-A-101. PLEASE PROVIDE A DETAIL SHOWING COMPLIANCE |
| WITH: 2017 FBC-B 1015.4 OPENING LIMITATIONS. REQUIRED |
| GUARDS SHALL NOT HAVE OPENINGS THAT ALLOW PASSAGE OF A |
| SPHERE 4 INCHES (102 MM) IN DIAMETER FROM THE WALKING |
| SURFACE TO THE REQUIRED GUARD HEIGHT. |
| |
| 2A) 2ND REQUEST. THERE MUST BE A PERMANENT MEANS OF |
| EGRESS TO REACH THE ROOF TOP HATCH. |
| 1ST ROUND OF COMMENTS. SHEET 042-A102 THE 2ND FLOOR |
| PLAN AND ROOF PLAN OF THE REPAIR GARAGE, SHOWS A ROOF |
| HATCH TO GAIN ACCESS TO THE MECHANICAL EQUIPMENT ON THE |
| ROOF. SHEET 047-A-301 SHOWS A VERTICAL DISTANCE FROM |
| THE FINISH FLOOR TO THE BOTTOM OF THE BAR JOIST OF |
| 14.66 FEET, CENTERED IN THE SERVICE BAY DOORWAY. THE |
| VERTICAL DISTANCE FROM FINISH FLOOR TO THE TOP OF THE |
| ROOF AT THE ROOF HATCH IS OVER 18.50 FEET. PLEASE SHOW |
| HOW COMPLIANCE WITH 306.5 OF THE 2017 MECHANICAL CODE |
| WILL BE MET: |
| 2017 FBC-MECHANICAL. 306.5 EQUIPMENT AND APPLIANCES ON |
| ROOFS OR ELEVATED STRUCTURES. |
| WHERE EQUIPMENT REQUIRING ACCESS OR APPLIANCES ARE |
| LOCATED ON AN ELEVATED STRUCTURE OR THE ROOF OF A |
| BUILDING SUCH THAT PERSONNEL WILL HAVE TO CLIMB HIGHER |
| THAN 16 FEET (4877 MM) ABOVE GRADE TO ACCESS SUCH |
| EQUIPMENT OR APPLIANCES, AN INTERIOR OR EXTERIOR MEANS |
| OF ACCESS SHALL BE PROVIDED. SUCH ACCESS SHALL NOT |
| REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30 |
| INCHES (762 MM) IN HEIGHT. |
| |
| 2B) 2ND REQUEST. 2017 FBC-B 1015.6 MECHANICAL |
| EQUIPMENT. GUARDS SHALL BE PROVIDED WHERE APPLIANCES, |
| EQUIPMENT, FANS, ROOF HATCH OPENINGS OR OTHER |
| COMPONENTS THAT REQUIRE SERVICE ARE LOCATED WITHIN 10 |
| FEET (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING |
| SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN |
| 30 INCHES ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE |
| GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE |
| OF A SPHERE 21 INCHES IN DIAMETER. THE GUARD SHALL |
| EXTEND NOT LESS THAN 30 INCHES BEYOND EACH END OF SUCH |
| APPLIANCE, EQUIPMENT, FAN OR COMPONENT. |
| |
| 2C)2ND REQUEST. PLEASE ALSO PROVIDE CODE COMPLIANCE |
| WITH: 2017 FBC-B ROOF HATCH EXCEPTION: IN BUILDINGS |
| WITHOUT AN OCCUPIED ROOF, ACCESS TO THE ROOF SHALL BE |
| PERMITTED TO BE A ROOF HATCH OR TRAP DOOR NOT LESS THAN |
| 16 SQUARE FEET IN AREA AND HAVING A MINIMUM DIMENSION |
| OF 2 FEET. |
| |
| 3) 2ND REQUEST. SHEET 028-S-1.0. EARTHWORK GENERAL |
| NOTES: NOTE # 1 INDICATES ALL EARTHWORK SHALL BE DONE |
| IN ACCORDANCE WITH THE REQUIREMENTS OUTLINED IN THE |
| GEOTECHNICAL REPORT BY UNIVERSAL ENGINEERING SCIENCES. |
| REPORT # 16357, DATED APRIL 22, 2019. SUBMIT REPORT. |
| PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B 1803.5.2 |
| QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, STRENGTH |
| OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A |
| LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE |
| PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION |
| BE CONDUCTED. |
| IF THE SOILS REPORT DOES NOT HAVE AN ELECTRONIC |
| SIGNATURE, THEN SUBMIT ONE PAPER ORIGINAL WITH |
| SIGNATURE AND SEAL. 61G15-23.002 ENGINEER SEAL |
| SIGNATURE. |
| 1ST ROUND OF COMMENTS. SHEET 028-S-1.0. EARTHWORK |
| GENERAL NOTES: NOTE # 1 INDICATES ALL EARTHWORK SHALL |
| BE DONE IN ACCORDANCE WITH THE REQUIREMENTS OUTLINED IN |
| THE GEOTECHNICAL REPORT BY XXXXXXX/ DATE: XXXXX, |
| MINIMUM BEARING PRESSURE XXXXXXX. PLEASE SHOW |
| COMPLIANCE WITH THE 2017 FBC-B 1803.5.2 QUESTIONABLE |
| SOIL. WHERE THE CLASSIFICATION, STRENGTH OR |
| COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A |
| LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE |
| PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION |
| BE CONDUCTED. |
| |
| 4) COMPLIED. PRESSURES ARE IN VASD AND PRESSURE ZONES |
| 1-5 ARE GOOD. |
| |
| 5) PROVISO: THIS BUILDING HAS WELDED AND BOLTED STEEL |
| CONNECTIONS, PLEASE PROVIDE COMPLIANCE WITH, THE |
| CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| STANDARDS AT TIME OF INSPECTION. |
| 2014 FBC-B 2204.1 WELDING |
| 2014 FBC-B 2204.2 BOLTING. |
| |
| 6) 2ND REQUEST. THE SUBMITTED NOA: 14-0827.18TAMKO |
| MODIFIED BITUMEN ROOF SYSTEM OVER STEEL DECK HAS |
| VARIOUS SUB-SYSTEMS LISTED WITHIN THE REPORT BUT NONE |
| OF THE SUB-SYSTEMS WERE IDENTIFIED AS THE ONE BEING |
| INSTALLED. : FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED |
| (LIMITATION #7 ALLOWS ENHANCED FASTENING, LIMITATION # |
| 9 DOES NOT ALLOW ENHANCED FASTENING) FOR ROOF ZONES 2 & |
| 3. FASTENER DENSITIES SHALL BE INCREASED FOR BOTH |
| INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE |
| WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION |
| PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED |
| PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT. |
| 1609.6.4.4.1 COMPONENTS & CLADDING. |
| |
| 7) 2ND REQUEST. THE SUBMITTAL NOA: 16-0219.01 TC-5 |
| SERIES STEEL ROOF CURB FOR TRANE ROOF TOP UNITS. PLEASE |
| REVIEW SHEET 4 AND 5 OF THE PRODUCT APPROVAL FOR |
| TECHNICAL NOTES. RESTRAINT BRACKET QUANTITY IS |
| DETERMINED BY PROJECT SPECIFIC CALCULATIONS, PERFORMED |
| BY A FLORIDA LICENSED PE OR FLORIDA REGISTERED |
| ARCHITECT THAT CONSIDER THE UNIQUE COMBINATION OF THE |
| UNIT SIZE AND APPLICABLE LATERAL AND UPLIFT PRESSURES |
| FOR EACH JOB. PLEASE PROVIDE CALCULATION FOR HOW MANY |
| BRACKETS WILL BE NEEDED FOR EACH TYPE OF UNIT. |
| 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED. 2017 |
| FBC-M- 301.15 WIND RESISTANCE. MECHANICAL EQUIPMENT, |
| APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL |
| BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES |
| DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING |
| CODE, BUILDING. |
| |
| 8) 2ND REQUEST. THE SUBMITTAL NOA: 17-1017.14 TRULITE |
| SERIES 3100 REGISTER ALUMINUM STOREFRONT/ WINDOW WALL |
| SYSTEM- L. M. I. SHEETS 2-5 DO NOT OPEN FOR REVIEW. |
| PLEASE NOTE ON PAGE 6 ONLY THE BOTTOM SERIES OF GLASS |
| IS HIGHLIGHTED FOR PRESSURES. THE UPPER WINDOW GLASS IS |
| NOT MENTIONED. THE UPPER GLAZING UNITS WHICH HAVE BOTH |
| VERTICAL AND HORIZONTAL FRAMING MEMBERS ARE NOT |
| IDENTIFIED ON SHEETS 8 AND 9 OF THE REPORT NOR IS THE |
| CHART HIGHLIGHTED OR CIRCLED TO IF THE JAMBS ARE |
| REQUIRED TO BE STEEL RE-ENFORCED. SHEET 10 OF 17 THE |
| DOOR MULLION INDICATES TRULITE DOORS ARE UNDER A |
| SEPARATE NOA. SHEET 13 OF 17 THE ANCHOR LOAD CHART IS |
| NOT IDENTIFIED AS TO THE TYPE OF ANCHOR FOR THE FRAME |
| WIDTH AND HEIGHT. |
| IDENTIFY GLAZING/ MULLIONS. |
| PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE |
| SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION |
| TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH |
| GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED |
| OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B |
| 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| |
| 9) 2ND REQUEST. GENSTEEL SERIES GENSTORM OUTSWING DOOR |
| NOA: 17-0803.01 PLEASE PROVIDE THE TYPE OF LOCK OPTION |
| THAT WILL BE USED WITH THIS DOOR. SEE SHEET 9 OF 11. |
| |
| 10) 2ND REQUEST. THE SUBMITTAL NOA: 17-1218.02 MIAMI |
| TECH ALUMINUM A/C STAND. THE ROOF TOP A/C STAND PRODUCT |
| APPROVAL A MIAMI-DADE NOA # 17-1218.02 WAS SUBMITTED, |
| REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE |
| FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW) |
| OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND, |
| THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS, |
| WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES, |
| ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE |
| STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL |
| IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED |
| BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. |
| |
| 11) THE PERMIT APPLICATION INDICATES THAT THE SQUARE |
| FOOTAGE OF THE AUTO DEALERSHIP BEING 15,805 SQ. FT. |
| THAT WOULD APPEAR TO BE THE 1ST FLOOR ONLY. THE TOTAL |
| SQ. FOOTAGE I CALCULATED WAS 18,534.00 SQ. FT. |
| DISCREPANCY IN SQ. FT. |
| |
| 108.3* BUILDING PERMIT VALUATION. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE |
| MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. |
| WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING |
| PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE |
| QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| EACH PERMIT. |
| |
| ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK |
| STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE |
| AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & |
| FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, |
| LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR |
| FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE |
| REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE |
| ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE |
| STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE |
| REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE |
| BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE |
| BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR |
| THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE |
| PRIME OR MASTER PERMIT. |
| |
| 12) 2ND REQUEST. INFORMATION REQUIRED, SINCE THIS |
| PROJECT IS A NEW AUTOMOBILE DEALERSHIP WILL THEY BE |
| FILLING THE CARS WITH GASOLINE? I DIDN'T SEE TANKS ON |
| ANY PLAN, ARE THEY TO BE ABOVE GROUND OR BENEATH THE |
| GROUND? NOTE PETROLEUM TANKS ARE TO BE REVIEWED UNDER |
| SEPARATE PERMIT, FEES AND REVIEWS. |
| 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 13) INFORMATIONAL: ART IN PUBLIC PLACES |
| THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES |
| ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR |
| NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT |
| APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL |
| PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN |
| $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE. |
| PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND |
| CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, |
| ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION |
| 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL |
| PROJECT CONSTRUCTION COST. |
| PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| PROJECTS. |
| SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE |
| DEVELOPMENT. |
| (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND |
| THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL |
| PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW |
| CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN |
| EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE |
| EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS |
| WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED |
| CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES |
| REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED |
| SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF |
| THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW |
| CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS. |
| FOR CONTACT INFORMATION PLEASE CONTACT: |
| MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR |
| 822-1515 E-MAIL: [email protected] |
| |
| 14) 2ND REQUEST. IMPACT FEES - DIGITAL SUBMITTALS: |
| PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE |
| DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS |
| OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST |
| FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE |
| OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL |
| IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME |
| THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM |
| CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS |
| TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON |
| APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO |
| YOUR PROJECT OR EMAIL IT TO [email protected] . |
| PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300 |
| N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL. |
| |
| 15) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |