Plan Review Details - Permit 19040400
Plan Review Stops For Permit 19040400
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-05-06 Cont ID  
Sent By shill Date 2019-05-06 Time 08:56 Rev Time 0.00
Received By shill Date 2019-05-06 Time 08:56 Sent To  
Notes
2019-05-06 09:01:16****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107, FBC R 301, PROVIDE AN ARCHITECTURAL QUALITY
 PLAN, DRAWN TO SCALE. PLAN SHOULD INCLUDE ALL
 STRUCTURAL DETAILS, WIND DESIGN CRITERIA, PRINTED NAME
 AND SIGNATURE OF INDIVIDUAL TAKING RESPONSIBILITY FOR
 THE DESIGN.
  
 2. A CONCEPTUAL PLAN WAS PROVIDED FOR THE PROPOSED NEW
 WALL BUT NO STRUCTURAL DETAILS (FASTENERS, STEEL,
 ETC.).
  
 3. "CEMENT BOARD" SPECIFIED AS AN EXTERIOR COMPONENT.
 PROVIDE SPEC SHEETS, PRODUCT APPROVAL. FASTENING
 PROPOSED AND RESISTANCE TO WIND NOT CLEAR, FBC R 301.
  
 4. HARDIE BRAND VENTED SOFFIT SPECIFED. PROVIDE PRODUCT
 APPROVALS. IF NOT INSTALLED IN ACCORDANCE WITH THE
 PRODUCT APPROVAL, PROVIDE CALCULATIONS TO SHOW THAT THE
 PROPOSED INSTALLATION MEETS THE WIND DESIGN CRITERIA
 REQUIRED.
  
 A COMPLETE REVIEW CANNOT BE DONE AT THIS TIME DUE TO
 INSUFFICIENT INFORMATION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-24 Cont ID  
Sent By jpearson Date 2019-04-24 Time 09:39 Rev Time 0.00
Received By jpearson Date 2019-04-23 Time 15:00 Sent To  
Notes
2019-04-24 09:39:03CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN (BOTH COPIES) IS REQUIRED TO BE SIGNED BY PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FS
 481.229; WPB FBC 107.1, 107.2.1, 107.3.5.1.2
 2. IS THE WIRING FOR NEW LIGHT FIXTURES EXISTING, OR
 WILL THIS BE NEW CIRCUITRY? IF NEW WIRE IS TO BE
 INSTALLED, PROVIDE WIRE SIZE AND BREAKER SIZE, SHOWING
 WHERE FED FROM. WPB FBC 107.2.1; NEC 210.19, 310.15
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-05-06 Cont ID  
Sent By shill Date 2019-05-06 Time 09:01 Rev Time 0.00
Received By shill Date 2019-04-09 Time 15:45 Sent To  
Notes
2019-04-10 15:45:38R07

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By pgreilih Date 2019-04-29 Time   Rev Time 0.00
Received By pgreilic Date 2019-04-29 Time 10:40 Sent To  
Notes
2019-04-29 10:40:57PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved