Plan Review Details - Permit 19040351
Plan Review Stops For Permit 19040351
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-05 Cont ID  
Sent By cthroop Date 2019-06-05 Time 08:15 Rev Time 0.00
Received By cthroop Date 2019-06-03 Time 15:01 Sent To  
Notes
2019-06-04 15:01:30RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-10 Cont ID  
Sent By cthroop Date 2019-04-10 Time 10:33 Rev Time 0.00
Received By cthroop Date 2019-04-08 Time 15:38 Sent To  
Notes
2019-04-10 11:08:36 
  
2019-04-09 15:38:34REVISION ROUTED TO CTHROOP

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-06-05 Cont ID  
Sent By cthroop Date 2019-06-05 Time 08:15 Rev Time 0.00
Received By cthroop Date 2019-06-05 Time 08:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-04-10 Cont ID  
Sent By cthroop Date 2019-04-10 Time 11:09 Rev Time 0.00
Received By cthroop Date 2019-04-10 Time 09:45 Sent To  
Notes
2019-04-10 11:10:07MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. MECHANICAL SCOPE OF WORK WAS REMOVED FROM RES-REMOD.
 PERMIT 18051483. FBC 107.3.5.3 (11).
  
 2. PROVIDE ENERGY SUBMITTAL.
 M1401.3EQUIPMENT AND APPLIANCE SIZING.
 HEATING AND COOLING EQUIPMENT AND APPLIANCES SHALL BE
 SIZED IN ACCORDANCE WITH ACCA MANUAL S OR OTHER
 APPROVED SIZING METHODOLOGIES BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
  
 RE403.7HEATING AND COOLING EQUIPMENT (MANDATORY).
  
 RE403.7.1EQUIPMENT SIZING.
 HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN
 ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR
 OTHER APPROVED HEATING AND COOLING CALCULATION
 METHODOLOGIES, BASED ON BUILDING LOADS FOR THE
 DIRECTIONAL ORIENTATION OF THE BUILDING. THE
 MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR
 UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH
 THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN
 CONDITIONS DESCRIBED IN SECTION R302.1. THIS CODE DOES
 NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR
 FUTURE EXPANSION OR OTHER FACTORS THAT AFFECT EQUIPMENT
 SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT INCLUDE
 LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL
 VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM
 EXHAUST SYSTEMS. NEW OR REPLACEMENT HEATING AND COOLING
 EQUIPMENT SHALL HAVE AN EFFICIENCY RATING EQUAL TO OR
 GREATER THAN THE MINIMUM REQUIRED BY FEDERAL LAW FOR
 THE GEOGRAPHIC LOCATION WHERE THE EQUIPMENT IS
 INSTALLED.
  
 3. RETURN AIR MISSING IN BEDROOM #2.
 M1602.2 RETURN AIR OPENINGS.
 RETURN AIR OPENINGS FOR HEATING, VENTILATION AND AIR
 CONDITIONING SYSTEMS SHALL COMPLY WITH ALL OF THE
 FOLLOWING:
 1. 1.OPENINGS SHALL NOT BE LOCATED LESS THAN 10 FEET
 (3048 MM) MEASURED IN ANY DIRECTION FROM AN OPEN
 COMBUSTION CHAMBER OR DRAFT HOOD OF ANOTHER APPLIANCE
 LOCATED IN THE SAME ROOM OR SPACE.
 2. 2.THE AMOUNT OF RETURN AIR TAKEN FROM ANY ROOM OR
 SPACE SHALL BE NOT GREATER THAN THE FLOW RATE OF SUPPLY
 AIR DELIVERED TO SUCH ROOM OR SPACE.
 3. 3.RETURN AND TRANSFER OPENINGS SHALL BE SIZED IN
 ACCORDANCE WITH THE APPLIANCE OR EQUIPMENT
 MANUFACTURERS? INSTALLATION INSTRUCTIONS, MANUAL D OR
 THE DESIGN OF THE REGISTERED DESIGN PROFESSIONAL.
 4. 4.RETURN AIR SHALL NOT BE TAKEN FROM A CLOSET,
 BATHROOM, TOILET ROOM, KITCHEN, GARAGE, MECHANICAL
 ROOM, BOILER ROOM, FURNACE ROOM OR UNCONDITIONED ATTIC.
  
 4. C/U TIE DOWN REFERENCE FBCM 301.12 IS INCORRECT. TIE
 DOWN SHALL COMPLY WITH FBCR M1307.2. FLORIDA PRODUCT
 APPROVAL FL14239 IS VALID FOR THIS PROJECT.
 M1307.2ANCHORAGE OF APPLIANCES.
 APPLIANCES DESIGNED TO BE FIXED IN POSITION SHALL BE
 FASTENED OR ANCHORED IN AN APPROVED MANNER. IN SEISMIC
 DESIGN CATEGORIES D0, D1 AND D2, AND IN TOWNHOUSES IN
 SEISMIC DESIGN CATEGORY C, WATER HEATERS AND THERMAL
 STORAGE UNITS SHALL BE ANCHORED OR STRAPPED TO RESIST
 HORIZONTAL DISPLACEMENT CAUSED BY EARTHQUAKE MOTION IN
 ACCORDANCE WITH ONE OF THE FOLLOWING:
 1.ANCHORAGE AND STRAPPING SHALL BE DESIGNED TO RESIST A
 HORIZONTAL FORCE EQUAL TO ONE-THIRD OF THE OPERATING
 WEIGHT OF THE WATER HEATER STORAGE TANK, ACTING IN ANY
 HORIZONTAL DIRECTION. STRAPPING SHALL BE AT POINTS
 WITHIN THE UPPER ONE-THIRD AND LOVER ONE-THIRD OF THE
 APPLIANCE?S VERTICAL DIMENSIONS. AT THE LOWER POINT,
 THE STRAPPING SHALL MAINTAIN A MINIMUM DISTANCE OF 4
 INCHES (102 MM) ABOVE THE CONTROLS.
 2.THE ANCHORAGE STRAPPING SHALL BE IN ACCORDANCE WITH
 THE APPLIANCE MANUFACTURER?S RECOMMENDATIONS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  