|
 |
 |
 |
 |
 |
Plan Review Details - Permit 19040320
Plan Review Stops For Permit 19040320 |
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2019-06-03 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2019-06-03 |
Time |
07:12 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2019-06-03 |
Time |
06:25 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2019-05-15 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2019-05-15 |
Time |
07:21 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2019-05-15 |
Time |
06:45 |
Sent To |
I |
|
Notes |
2019-05-15 06:49:19 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. CAMERAS AND 64 CHANNEL VIDEO RECORDER ARE NOT | | LISTED. PROVIDE LISTING AS PER LAST PLAN REVIEW | | COMMENTS. FBC 107.2.1 NEC 90.7,110.2,110.3B | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-657-1653 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2019-04-24 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2019-04-24 |
Time |
16:51 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2019-04-24 |
Time |
16:26 |
Sent To |
I |
|
Notes |
2019-04-24 16:50:49 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PROVIDE CUT SHEETS FOR PRODUCT APPROVAL OF CAMERAS | | AND ACCESS CONTROL DEVICES, MUST BE UL OR OTHER NRTL | | LISTED DEVICES. FBC 107.2.1 NEC 90.7,110.2,110.3B | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-657-1653 | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2019-04-09 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2019-04-24 |
Time |
16:52 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2019-04-09 |
Time |
12:11 |
Sent To |
E |
|
Notes |
2019-04-09 12:20:13 | PERMIT # 19040320 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | APPROVED PROVISO: | | | | 1) THIS PERMIT APPROVAL IS FOR THE GUARD GATE ONLY. | | ADDITIONAL SHEETS REFERENCING CCTV AND ACCESS CONTROL | | FOR OTHER AREAS BELONG TO PERMIT #19031153. | | | | 2) PEDESTRIAN GATES SHALL PROVIDE FOR FREE EGRESS AT | | ALL TIMES. | | | | 3) PROVIDE A KNOX KEY SWITCH TO ALLOW GATE ACCESS TO | | EMERGENCY RESPONDERS. KEY SWITCH CAN BE ORDERED FROM | | WWW.KNOXBOX.COM. | | KEY SWITCH SHALL BE LOCATED AT MAIN ENTRANCE AND SHALL | | OPEN BOTH GATE DOORS SIMULTANEOUSLY. | | | | | | SUE ELLEN CALDERON | | ASSISTANT FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2019-06-03 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2019-06-03 |
Time |
07:12 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2019-05-28 |
Time |
09:45 |
Sent To |
|
|
Notes |
2019-05-30 09:45:41 | RESUB ROUTED TO FGIAQUINTO |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2019-05-15 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2019-05-15 |
Time |
07:21 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2019-05-09 |
Time |
13:01 |
Sent To |
|
|
Notes |
2019-05-09 13:01:40 | RESUB ROUTED TO FGIAQUINTO |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2019-04-24 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2019-04-24 |
Time |
16:52 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2019-04-05 |
Time |
16:38 |
Sent To |
FIRE |
|
Notes |
|
|
Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
Rev No |
1 |
Status |
P |
Date |
2021-02-13 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2021-02-13 |
Time |
09:10 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2021-02-13 |
Time |
09:10 |
Sent To |
|
|
Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |