Plan Review Details - Permit 19040288
Plan Review Stops For Permit 19040288
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-08-21 Cont ID  
Sent By dharvey Date 2019-08-21 Time 12:31 Rev Time 0.00
Received By dharvey Date 2019-08-21 Time 12:27 Sent To  
Notes
2019-08-21 12:31:34ALL REVISIONS WITH THE EXCEPTION OF THE KITCHEN APPEAR
 TO HAVE BEEN CORRECTED. I MET WITH AMIN TO DISCUSS THE
 PROJECT AND HOW IT MAY MOVE FORWARD. MET WITH ROBERT
 BROWN TO DISCUSS AS JULIO WAS NOT IN THE OFFICE. IT IS
 OK TO ISSUE THIS REVISION WITH THE KITCHEN AREA GRAYED
 OUT AS NOT A PART OF THIS REVISION. THE REVISIONS TO
 THE KITCHEN WILL BE SUBMITTED AS A SEPARATE REVISION
 AND REQUIRED TO BE APPROVED AND INSPECTED TO THE NEW
 REVISIONS ONCE APPROVED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-08-20 Cont ID  
Sent By jgomez Date 2019-08-20 Time 17:41 Rev Time 0.00
Received By jgomez Date 2019-08-20 Time 15:33 Sent To  
Notes
2019-08-20 17:42:04GOOD AFTERNOON DAVID,
  
 I DISCUSSED YOUR QUESTIONS WITH ROBERT BROWN (BUILDING
 OFFICIAL) AND GEORGE JOHNSON (PLUMBING PLAN REVIEWER)
 BEFORE REPLYING TO YOUR E-MAIL.
  
 1) THE PROPOSED KITCHEN FALLS MORE INTO THE U SHAPE
 KITCHEN THAT IS ENCLOSED ON THREE CONTIGUOUS SIDES. THE
 60 INCHES TURN AROUND INSIDE THE KITCHEN WORK AREAS IS
 REQUIRED. ROBERT SUGGESTED THAT MAY BE BY PROVIDING THE
 60 INCHES IN THE ISLE BETWEEN THE TRIPLE SINK
 COMPARTMENT AND THE ISLAND COUNTER WILL PROVIDE THE
 REQUIRED TURNING SPACE.
  
 2) YOU ARE RIGHT THIS IS NOT A RESIDENTIAL DWELLING
 UNIT. THE KITCHEN WORK SURFACE IS REQUIRED FOR ALL
 KITCHENS. SEC. 804.3.1 IS NOT REFERRING TO "RESIDENTIAL
 DWELLING UNITS". SECTION 804.3 MENTIONS RESIDENTIAL
 DWELLING UNITS TO CLARIFY THAT RESIDENTIAL UNITS NEED
 TO HAVE AT LEAST 30 INCHES WIDE MINIMUM SECTION OF
 COUNTER PROVIDING THE KITCHEN WORK SURFACE COMPLYING
 WITH ALL THE REQUIREMENTS OF SEC. 804.3.
  
 3) REGARDING THE MICROWAVE, IF YOU PROVIDE THE
 COUNTERTOP TYPE MICROWAVE, THEN THE MICROWAVE ABOVE THE
 COOKTOP IS NOT EQUIVALENT. IF THE COUNTER MICROWAVE
 FAILS , THEN THE OTHER DOESN'T COMPLY. THEREFORE, THE
 ANSWER IS NO.
  
 4) REGARDING THE SINK. IT WILL NEED TO COMPLY WITH THE
 FRONT APPROACH AND REQUIRED HEIGHT. THIS SINK IS FOR
 PUBLIC USE AN ACCOMMODATION. PLEASE COORDINATE WITH
 GEORGE JOHNSON (PLUMBING PLAN EXAMINER). SEE CONTACT
 INFORMATION BELOW. BY THE WAY, PLUMBING PLANS NEED TO
 BE REVISED ALSO. PLUMBING HAVE NOT SEEN THE PROPOSED
 REVISIONS. THIS MAY AFFECT THE PLUMBING INSPECTIONS IF
 PLANS DON'T MATCH WORK IN THE FIELD.
  
  
  GEORGE PRIEST JOHNSON
  PLUMBING PLANS EXAMINER II
  DEVELOPMENT SERVICES
  BUILDING INSPECTIONS
  
  PHONE: 805-6700 EXT: 6711
  FAX: 805-6676
  E-MAIL: [email protected]
  
  
 PLEASE FEEL FREE TO CALL ME IF YOU HAVE ANY QUESTIONS,
 THANK YOU
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
 -----ORIGINAL MESSAGE-----
 FROM: DAVID
 SENT: TUESDAY, AUGUST 20, 2019 9:29 AM
 TO: JULIO GOMEZ ; [email protected]
 SUBJECT: 1803 AUSTRALIAN
  
 GOOD MORNING JULIO,
  
 RE: 19040288
  
 THANK YOU FOR GETTING BACK TO AMMI AND I SO QUICKLY
 WITH YOUR COMMENTS. I HAVE A COUPLE OF QUESTIONS
 THOUGH:
  
 1) I THOUGHT OUR KITCHENETTE WAS A PASSTHROUGH TYPE NOT
 A "U" SHAPE. WE HAVE TWO ENTRANCES/EXITS INTO THE SPACE
 NOT A DEAD END SITUATION WHERE A TURNAROUND WOULD BE
 NECESSARY.
  
 2) SEC 804.3.1 FBCA IS REFERRING TO "RESIDENTIAL
 DWELLING UNITS" WHICH WE ARE CERTAINLY NOT. THIS IS
 MORE OF A CONTINENTAL BREAKFAST TYPE SETUP, OR A GRAB N
 GO.
  
 3) IF WE WERE TO HAVE AN ADDITIONAL COUNTERTOP TYPE
 MICROWAVE THAT MEETS REACH REQUIREMENTS CAN WE KEEP THE
 MICROWAVE ABOVE THE COOKTOP?
  
 4) I UNDERSTAND THE KITCHEN SINK HEIGHT REQUIREMENT OF
 34", HOWEVER THE THREE COMPARTMENT SINK IS FOR
 EMPLOYEES DOING SANITARY WASHING. IS THERE ANY WAY YOU
 CAN APPROVE A PARALLEL APPROACH OF 36" HIGH BECAUSE
 THIS IS A "SERVICE STYLE" COUNTER OR A "FOOD SERVICE
 LINE" COUNTER?
  
 THANK YOU FOR YOUR ATTENTION TO THIS MATTER.
  
 SINCERELY,
  
 DAVID J. GENGLER, A.I.A
 (561) 340-9320
  
  
 ****ORIGINAL COMMENTS:
  
 REVISION, SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1- ARCHITECT STATES ON SHEET A-02 THAT "THIS KITCHEN
 SHALL BE USED AS A DOMESTIC KITCHEN FOR USE BY
 INDIVIDUAL PATIENTS & GUESTS AS WELL AS FOR THE
 PURPOSES OF STORING AND HEATING FOOD PREPARED OFFSITE.
 NO FOOD SHALL BE PREPARED FOR PUBLIC CONSUMPTION IN
 THIS KITCHEN".
  
 A)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 KITCHEN COMPLIANCE WITH SEC. 804 FBC-ACCESSIBILITY AS
 REQUIRED BY SEC. 212 FBC-ACCESSIBILITY.
  
 RESPONSE:
 (1) SEC. 804.2.2 FBC-ACCESSIBILITY FOR U-SHAPED
 KITCHENS REQUIRES 60" CLEARANCE BETWEEN ALL OPPOSING
 BASE CABINETS, COUNTER TOPS, APPLIANCES OR WALL WITHIN
 KITCHEN WORK AREAS. PLEASE REVISE PLANS AS REQUIRED.
  
 (2) PLEASE SHOW THE KITCHEN WORK SURFACE POSITIONED FOR
 A FORWARD APPROACH AS REQUIRED BY SEC. 804.3.1
 FBC-ACCESSIBILITY. ALSO, SHOW KNEE AND TOE CLEARANCE
 COMPLYING WITH SEC. 306 FBC-ACCESSIBILITY. AND SPECIFY
 THE HEIGHT OF THE KITCHEN WORK SURFACE AS REQUIRED BY
 SEC. 804.3.2 FBC-ACCESSIBILITY
  
 (3) THE LOCATION OF THE MICROWAVE ABOVE THE COOKTOP
 DOESN'T SEEM TO COMPLY WITH SEC. 308.3.2
 FBC-ACCESSIBILITY FOR SIDE REACH WITH AN OBSTRUCTION.
 PLEASE, REVISE AS REQUIRED.
  
 (4) PROVIDE INFORMATION SHOWING THE HEIGHT OF THE SINK
 AS REQUIRED BY SEC. 804.4 AND SEC. 606.3
 FBC-ACCESSIBILITY
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-08-19 Cont ID  
Sent By jgomez Date 2019-08-19 Time 18:46 Rev Time 0.00
Received By jgomez Date 2019-08-19 Time 15:43 Sent To I
Notes
2019-08-19 18:09:46REVISION, SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1- ARCHITECT STATES ON SHEET A-02 THAT "THIS KITCHEN
 SHALL BE USED AS A DOMESTIC KITCHEN FOR USE BY
 INDIVIDUAL PATIENTS & GUESTS AS WELL AS FOR THE
 PURPOSES OF STORING AND HEATING FOOD PREPARED OFFSITE.
 NO FOOD SHALL BE PREPARED FOR PUBLIC CONSUMPTION IN
 THIS KITCHEN".
  
 A)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 KITCHEN COMPLIANCE WITH SEC. 804 FBC-ACCESSIBILITY AS
 REQUIRED BY SEC. 212 FBC-ACCESSIBILITY.
  
 RESPONSE:
 (1) SEC. 804.2.2 FBC-ACCESSIBILITY FOR U-SHAPED
 KITCHENS REQUIRES 60" CLEARANCE BETWEEN ALL OPPOSING
 BASE CABINETS, COUNTER TOPS, APPLIANCES OR WALL WITHIN
 KITCHEN WORK AREAS. PLEASE REVISE PLANS AS REQUIRED.
  
 (2) PLEASE SHOW THE KITCHEN WORK SURFACE POSITIONED FOR
 A FORWARD APPROACH AS REQUIRED BY SEC. 804.3.1
 FBC-ACCESSIBILITY. ALSO, SHOW KNEE AND TOE CLEARANCE
 COMPLYING WITH SEC. 306 FBC-ACCESSIBILITY. AND SPECIFY
 THE HEIGHT OF THE KITCHEN WORK SURFACE AS REQUIRED BY
 SEC. 804.3.2 FBC-ACCESSIBILITY
  
 (3) THE LOCATION OF THE MICROWAVE ABOVE THE COOKTOP
 DOESN'T SEEM TO COMPLY WITH SEC. 308.3.2
 FBC-ACCESSIBILITY FOR SIDE REACH WITH AN OBSTRUCTION.
 PLEASE, REVISE AS REQUIRED.
  
 (4) PROVIDE INFORMATION SHOWING THE HEIGHT OF THE SINK
 AS REQUIRED BY SEC. 804.4 AND SEC. 606.3
 FBC-ACCESSIBILITY
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-14 Cont ID  
Sent By jwitmer Date 2019-06-14 Time 08:40 Rev Time 0.00
Received By jgomez Date 2019-06-13 Time 19:01 Sent To  
Notes
2019-06-14 08:41:42REVISION, BUILDING REVIEW COMMENTS
 CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS.
  
 1- ARCHITECT STATES ON SHEET A-02 THAT "THIS KITCHEN
 SHALL BE USED AS A DOMESTIC KITCHEN FOR USE BY
 INDIVIDUAL PATIENTS & GUESTS AS WELL AS FOR THE
 PURPOSES OF STORING AND HEATING FOOD PREPARED OFFSITE.
 NO FOOD SHALL BE PREPARED FOR PUBLIC CONSUMPTION IN
 THIS KITCHEN".
  
 A)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 KITCHEN COMPLIANCE WITH SEC. 804 FBC-ACCESSIBILITY AS
 REQUIRED BY SEC. 212 FBC-ACCESSIBILITY.
  
 B) SHOW ON PLANS HOW COMPLYING WITH ALL THE
 REQUIREMENTS OF SEC. 407.2.6 FBC-BUILDING.
  
 SEC. 407.2.6 NURSING HOME COOKING FACILITIES.
 IN GROUP I-2, CONDITION 1, OCCUPANCIES, ROOMS OR SPACES
 THAT CONTAIN A COOKING FACILITY WITH DOMESTIC COOKING
 APPLIANCES SHALL BE PERMITTED TO BE OPEN TO THE
 CORRIDOR WHERE ALL OF THE FOLLOWING CRITERIA ARE MET:
  
 1.THE NUMBER OF CARE RECIPIENTS HOUSED IN THE SMOKE
 COMPARTMENT IS NOT GREATER THAN 30.
  
 2.THE NUMBER OF CARE RECIPIENTS SERVED BY THE COOKING
 FACILITY IS NOT GREATER THAN 30.
  
 3.ONLY ONE COOKING FACILITY AREA IS PERMITTED IN A
 SMOKE COMPARTMENT.
  
 4.THE TYPES OF DOMESTIC COOKING APPLIANCES PERMITTED
 ARE LIMITED TO OVENS, COOKTOPS, RANGES, WARMERS AND
 MICROWAVES.
  
 5.THE CORRIDOR IS A CLEARLY IDENTIFIED SPACE DELINEATED
 BY CONSTRUCTION OR FLOOR PATTERN, MATERIAL OR COLOR.
  
 6.THE SPACE CONTAINING THE DOMESTIC COOKING FACILITY
 SHALL BE ARRANGED SO AS NOT TO OBSTRUCT ACCESS TO THE
 REQUIRED EXIT.
  
 7.A DOMESTIC COOKING HOOD INSTALLED AND CONSTRUCTED IN
 ACCORDANCE WITH SECTION 505 OF THE FLORIDA BUILDING
 CODE, MECHANICAL IS PROVIDED OVER THE COOKTOP OR RANGE.
  
 8.THE DOMESTIC COOKING HOOD PROVIDED OVER THE COOKTOP
 OR RANGE SHALL BE EQUIPPED WITH AN AUTOMATIC
 FIRE-EXTINGUISHING SYSTEM OF A TYPE RECOGNIZED FOR
 PROTECTION OF DOMESTIC COOKING EQUIPMENT. PREENGINEERED
 AUTOMATIC EXTINGUISHING SYSTEMS SHALL BE TESTED IN
 ACCORDANCE WITH UL 300A AND LISTED AND LABELED FOR THE
 INTENDED APPLICATION. THE SYSTEM SHALL BE INSTALLED IN
 ACCORDANCE WITH THIS CODE, ITS LISTING AND THE
 MANUFACTURER'S INSTRUCTIONS.
  
 9.A MANUAL ACTUATION DEVICE FOR THE HOOD SUPPRESSION
 SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH SECTIONS
 904.12.1 AND 904.12.2.
  
 10.AN INTERLOCK DEVICE SHALL BE PROVIDED SUCH THAT UPON
 ACTIVATION OF THE HOOD SUPPRESSION SYSTEM, THE POWER OR
 FUEL SUPPLY TO THE COOKTOP OR RANGE WILL BE TURNED OFF.
  
 11.A SHUT-OFF FOR THE FUEL AND ELECTRICAL POWER SUPPLY
 TO THE COOKING EQUIPMENT SHALL BE PROVIDED IN A
 LOCATION THAT IS ACCESSIBLE ONLY TO STAFF.
  
 12.A TIMER SHALL BE PROVIDED THAT AUTOMATICALLY
 DEACTIVATES THE COOKING APPLIANCES WITHIN A PERIOD OF
 NOT MORE THAN 120 MINUTES.
  
 13.A PORTABLE FIRE EXTINGUISHER SHALL BE INSTALLED IN
 ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-06-22 Cont ID  
Sent By jpearson Date 2019-06-22 Time 18:54 Rev Time 0.00
Received By jpearson Date 2019-06-22 Time 18:54 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-08-19 Cont ID  
Sent By pleduc Date 2019-08-19 Time   Rev Time 0.00
Received By pleduc Date 2019-08-19 Time 10:31 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-05-24 Cont ID  
Sent By pleduc Date 2019-05-24 Time   Rev Time 0.00
Received By pleduc Date 2019-05-24 Time 15:16 Sent To  
Notes
2019-05-24 15:32:465/24/19
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A 04 - THERE IS AN INDICATION OF A KITCHEN
 WITH AN OVERHEAD MICROWAVE VENT AND A 36 " COOKTOP.
  
 THOUGH THERE IS A NOTE FOR A HOOD AND FIRE SUPPRESSION
 SYSTEM, THERE IS NOT INDICATION OF ANY PERMITTED SHOP
 DRAWING FOR EITHER.
  
 THIS OCCUPANCY IN THE FFC IS NEW RESIDENTIAL BOARD AND
 CARE OCCUPANCIES
  
 6.1.9.1* DEFINITION ? RESIDENTIAL BOARD AND CARE
 OCCUPANCY. AN
 OCCUPANCY USED FOR LODGING AND BOARDING OF FOUR OR MORE
 RESIDENTS, NOT
 RELATED BY BLOOD OR MARRIAGE TO THE OWNERS OR
 OPERATORS, FOR THE PURPOSE
 OF PROVIDING PERSONAL CARE SERVICES
  
 PER NFPA 101 - CH 32 NEW RESIDENTIAL BOARD AND CARE
 OCCUPANCIES
  
 32.3.3.8 COOKING FACILITIES.
  
 32.3.3.8.1 COOKING FACILITIES SHALL BE PROTECTED IN
 ACCORDANCE WITH
 9.2.3, UNLESS OTHERWISE PERMITTED BY 32.3.3.8.2,
 32.3.3.8.3, OR
 32.3.3.8.4.
  
 THERE ARE NUMEROUS CONDITIONS TO MEET TO NOT PROVIDE A
 FIRE SUPPRESSIONS SYSTEM.
  
 PLEASE REVIEW AND PROVIDE DETAILS OF COMPLIANCE OR
 PROVIDE A SUPPRESSION SYSTEM.
  
  
  
  
 2) SHEET M 02 - A DOMESTIC MICROWAVE IS INDICATED.
 THERE ARE NO DETAILS THAT IT COMPLIES WITH THE ABOVE
 NOTED CODES.
  
 PER NFPA 101 - CH 32 NEW RESIDENTIAL BOARD AND CARE
 OCCUPANCIES
  
 32.3.3.8 COOKING FACILITIES.
  
 32.3.3.8.1 COOKING FACILITIES SHALL BE PROTECTED IN
 ACCORDANCE WITH
 9.2.3, UNLESS OTHERWISE PERMITTED BY 32.3.3.8.2,
 32.3.3.8.3, OR
 32.3.3.8.4.
  
 THERE ARE NUMEROUS CONDITIONS TO MEET TO NOT PROVIDE A
 NFPA 96 HOOD SYSTEM.
  
 PLEASE REVIEW AND PROVIDE DETAILS OF COMPLIANCE OR
 PROVIDE A SUPPRESSION SYSTEM.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-08-20 Cont ID  
Sent By jgomez Date 2019-08-20 Time 17:43 Rev Time 0.00
Received By jgomez Date 2019-08-20 Time 15:33 Sent To  
Notes
2019-08-20 15:33:28E-MAIL FROM ARCHITECT.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-08-19 Cont ID  
Sent By jgomez Date 2019-08-19 Time 18:48 Rev Time 0.00
Received By jgomez Date 2019-08-15 Time 14:34 Sent To I
Notes
2019-08-19 14:30:38TO JG DESK
2019-08-16 14:35:09RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-06-22 Time   Rev Time 0.00
Received By lmarchan Date 2019-05-21 Time 14:32 Sent To  
Notes
2019-05-22 14:33:08C10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-04-10 Time   Rev Time 0.00
Received By cpuell Date 2019-04-05 Time 16:11 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-06-11 Cont ID  
Sent By ccole Date 2019-06-11 Time 09:08 Rev Time 0.00
Received By ccole Date 2019-06-10 Time 17:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-04-10 Cont ID  
Sent By ccole Date 2019-04-10 Time 11:15 Rev Time 0.00
Received By ccole Date 2019-04-10 Time 11:15 Sent To I
Notes
2019-04-10 11:48:491ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19040288
 4/10/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: AS-BUILT MECHANICAL DRAWINGS
 DENIED.
  
 1) SHEETS M01, M02, M03, M04: THE AS-BUILT DRAWINGS
 HAVE COFLICTING DETAILS AND NOTES REGARDING THE SMOKE
 DAMPERS. THERE IS A NOTE ON M-01 STATING THEY ARE NOT
 REQUIRED, HOWEVER ON THAT SAME SHEET AND ON THE OTHERS,
 THEY ARE CALLED OUT TO BE INSTALLED AT DUCT
 PENETRATIONS AT COMMON CORRIDOR/ROOM WALLS. PLEASE
 CORRECT THESE CONFLICTS.
  
 2) M01, M02, M03, & M04: THE AS-BUILT DRAWINGS SHOW THE
 DUCTED RETURNS FROM THE ROOMS AND THE MAIN DUCT TRUNK
 IN THE CORRIDOR HAVE BEEN REMOVED AND REPLACED WITH A
 SYSTEM OF RETUN AIR THAT USES TRANSFER DUCTS FROM THE
 ROOMS AND THE CORRIDOR AS A MEANS OF RETURNING AIR TO
 THE AIR HANDLERS. PLEASE NOTE THAT CORRIDORS SHALL NOT
 BE USED AS RETURN AIR DUCTS PER SECTION 601.2 FBC M.
  
 3) PLEASE PROVIDE AS-BUILT ARCHITECTURAL PLANS SHOWING
 THE CHANGES MADE TO THE CORRIDOR AND ROOM SEPARATION
 WALLS. APPARENTLY THESE SMOKE PARTITION WALLS THAT WERE
 DESIGNED AND APPROVED TO EXTEND FROM FLOOR TO UNDERSIDE
 OF SLAB HAVE BEEN CHANGED TO EXTEND ONLY TO CEILING
 LEVEL- SEE SECTION 710.4 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2019-05-24 Cont ID  
Sent By llouie Date 2019-05-24 Time   Rev Time 0.00
Received By llouie Date 2019-05-24 Time   Sent To  
Notes
2019-05-24 10:26:17ZONING APPROVED WITH THE FOLLOWING PROVISO:
  
 1.) SEPARATE PERMITS REQUIRED FOR THE FOLLOWING:
 FENCE/WALL, SIGNAGE, PARKING AREA, LANDSCAPE AND
 IRRIGATION.