Plan Review Details - Permit 19040257
Plan Review Stops For Permit 19040257
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-07-12 Cont ID  
Sent By dbattles Date 2019-07-12 Time 12:36 Rev Time 0.00
Received By dbattles Date 2019-07-12 Time 11:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-06-13 Cont ID  
Sent By dbattles Date 2019-06-13 Time 08:20 Rev Time 0.00
Received By dbattles Date 2019-06-12 Time 16:56 Sent To  
Notes
2019-06-13 08:20:03BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19040257
 REVIEWED: JUNE 13, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
  
 1. 107.5.3 FBC[AMENDED] SHEET PD2 DOESN?T SHOW THE
 GENERATOR. PLEASE SHOW HOW GENERATOR AND PAD WORK WITH
 CIVIL PLAN AT DRAIN S-16.
  
 2. 1601.1 FBC[B] PROVIDE DETAIL TO SHOW HOW GENERATOR
 CONNECTS TO PAD.
  
 3. PROVIDE SPECIFICATIONS FOR THE GENERATOR.
  
 4. IF SCREENING IS ADDED THEN SHOW DETAILS FOR
 ATTACHMENT AND WIND DESIGN.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-07-10 Cont ID  
Sent By jpearson Date 2019-07-10 Time 07:00 Rev Time 0.00
Received By jpearson Date 2019-07-10 Time 06:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-06-04 Cont ID  
Sent By jpearson Date 2019-06-04 Time 12:26 Rev Time 0.00
Received By jpearson Date 2019-06-04 Time 12:26 Sent To  
Notes
2019-06-04 12:26:27CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB
 FBC 107.2.1, 107.3.5; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-07-05 Cont ID  
Sent By pleduc Date 2019-07-05 Time   Rev Time 0.00
Received By pleduc Date 2019-07-05 Time 15:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-05-31 Cont ID  
Sent By pleduc Date 2019-05-31 Time   Rev Time 0.00
Received By pleduc Date 2019-05-31 Time 11:12 Sent To  
Notes
2019-05-31 11:47:045/31/19
  
  
 1) THE APPLICATION INDICATES THE INSTALLATION OF A
 GENERATOR & ATS.
  
 PER NFPA 37
  
 4.6* GENERAL INSTALLATION REQUIREMENTS. ENGINES AND
 THEIR
 APPURTENANCES SHALL BE INSTALLED IN ACCORDANCE WITH THE
 FOLLOWING:
 (1) APPLICABLE NFPA CODES AND STANDARDS
 (2) INDUSTRY STANDARDS
 (3) USER REQUIREMENTS
 (4) MANUFACTURER?S INSTALLATION INSTRUCTIONS
 (5)*APPLICABLE LOCAL BUILDING CODES WITH RESPECT TO
 WIND AND
 SEISMIC DESIGN REQUIREMENTS.
  
 1A) THERE ARE NO GENERATOR DETAILS.
  
 PER NFPA 110
  
 CHAPTER 4 CLASSIFICATION OF EMERGENCY POWER SUPPLY
 SYSTEMS (EPSSS)
 4.1* GENERAL. THE EPSS SHALL PROVIDE A SOURCE OF
 ELECTRICAL
 POWER OF REQUIRED CAPACITY, RELIABILITY, AND QUALITY TO
 LOADS FOR
 A LENGTH OF TIME AS SPECIFIED IN TABLE 4.1(A) AND
 WITHIN A SPECIFIED
 TIME FOLLOWING LOSS OR FAILURE OF THE NORMAL POWER
 SUPPLY
 AS SPECIFIED IN TABLE 4.1(B).
  
  
 1B) THERE ARE NO ATS DETAILS
  
 PER NFPA 110 CHAPTER 6 TRANSFER SWITCH EQUIPMENT
 6.1 GENERAL.
 6.1.1* SWITCHES SHALL TRANSFER ELECTRIC LOADS FROM ONE
 POWER
 SOURCE TO ANOTHER.
 6.1.2* THE ELECTRICAL RATING SHALL BE SIZED FOR THE
 TOTAL LOAD THAT
 IS DESIGNED TO BE CONNECTED.
 6.1.3 EACH SWITCH SHALL BE IN A SEPARATE ENCLOSURE OR
 COMPARTMENT.
 6.1.4 THE SWITCH, INCLUDING ALL LOAD CURRENT-CARRYING
 COMPONENTS,
 SHALL BE LISTED FOR ALL LOAD TYPES TO BE SERVED.
 6.1.5 THE SWITCH, INCLUDING ALL LOAD CURRENT-CARRYING
 COMPONENTS,
 SHALL BE DESIGNED TO WITHSTAND THE EFFECTS OF AVAILABLE
 FAULT CURRENTS.
  
 PLEASE REVIEW AND CORRECT OR PROVIDE DETAILED
 JUSTIFICATIONS.
  
  
  
  
 2) THE ARE NO INDICATIONS OF COMPLIANCE WITH ANY NFPA
 CODES.
  
 NFPA 37 AND 110 ARE THE MINIMUM CODES OF COMPLAINCE.
  
 PLEASE REVIEW AND ENSURE COMPLAINCE AND PROVIDE AN
 APPLICABLE NOTE.
  
  
  
 3) THERE ARE NO INDICATIONS OF WHERE THE EXHAUST IS
 LOCATED, AT WHAT HEIGHT IT ENDS AT, ANY DIMENSION TO
 OPENINGS THAT MAY BE APPLICABLE TO THE ABOVE NOTED
 CODES.
  
  
  
 PER NFPA 110
  
 7.10 EXHAUST SYSTEM.
 7.10.1 THE EXHAUST SYSTEM EQUIPMENT AND INSTALLATION,
 INCLUDING
 PIPING, MUFFLER, AND RELATED ACCESSORIES, SHALL BE IN
 ACCORDANCE WITH NFPA37, STANDARD FOR THE INSTALLATION
 AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES, AND
 OTHER APPLICABLE
 STANDARDS.
  
 NFPA 37
  
  
  
 PLEASE REVIEW AND PROVIDE DETAILS.
  
  
  
 4) THERE ARE NO MANUFACTURES SPEC SHEETS PROVIDED.
  
 PLEASE PROVIDE SPEC SHEETS FOR VERIFICATION PURPOSES.
  
  
  
 5) THERE ARE NO INDICATIONS OF HOW THE GENERATOR WILL
 BE SECURED TO THE SLAB.
  
 7.4 MOUNTING.
 7.4.1 ROTATING ENERGY CONVERTERS SHALL BE INSTALLED ON
 SOLID
 FOUNDATIONS TO PROHIBIT SAGGING OF FUEL, EXHAUST, OR
 LUBRICATINGOIL
 PIPING AND DAMAGE TO PARTS RESULTING IN LEAKAGE AT
 JOINTS.
  
 7.5* VIBRATION. VIBRATION ISOLATORS, AS RECOMMENDED BY
 THE
 MANUFACTURER OF THE EPS, SHALL BE INSTALLED EITHER
 BETWEEN THE
 ROTATING EQUIPMENT AND ITS SKID BASE OR BETWEEN THE
 SKID BASE
 AND THE FOUNDATION OR INERTIA BASE.
  
 PLEASE PROVIDE DETAILS OR JUSTIFY.
  
  
  
 6) THERE ARE NO INDICATIONS OF ELECTRICAL PROTECTIONS
  
 PER NFPA 37
  
 4.5.4 BATTERIES, WIRING, AND ELECTRICAL DEVICES SHALL
 BE PROTECTED
 AGAINST ARCING AND ACCIDENTAL SHORTING.
  
  
 PER NFPA 110
  
 6.5 PROTECTION.
 6.5.1* GENERAL. THE OVERCURRENT PROTECTIVE DEVICES IN
 THE EPSS
 SHALL BE COORDINATED TO OPTIMIZE SELECTIVE TRIPPING OF
 THE CIRCUIT
 OVERCURRENT PROTECTIVE DEVICES WHEN A SHORT CIRCUIT
 OCCURS.
  
 PLEASE PROVIDE DETAILS
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2019-07-17 Cont ID  
Sent By gjohnson Date 2019-07-17 Time 16:54 Rev Time 0.00
Received By gjohnson Date 2019-07-17 Time 16:54 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-06-12 Cont ID  
Sent By thunt Date 2019-06-12 Time 13:25 Rev Time 0.00
Received By thunt Date 2019-06-12 Time 13:00 Sent To  
Notes
2019-06-12 13:30:56GAS 2ND REVIEW**DENIED**
  
  
 1) ANSWERED**
  
 2) ANSWERED**
  
 3) ANSWERED**
  
 4) ANSWERED**
  
 5) PLEASE PROVIDE MEASUREMENTS AND ALL PIPING USED FOR
 EACH SECTION OF PIPING .SUBMIT AN ISOMETRIC DRAWING
 THAT CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF
 PIPE PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 6) PARTIAL SEE COMMENT #5.SHOW THE TYPE OF PIPE
 MATERIAL BEING INSTALLED, ALL PIPE SIZES, AND THE
 CORRESPONDING EHD NUMBER OF THE CORRUGATED STAINLESS
 STEEL TUBING (IF APPLICABLE) FOR EACH PIPE SIZE. WPB
 AMENDMENTS TO FBC SEC.107.2.1.
  
 7) NOT ADDRESSED. THIS IS THE SUBMITTAL PHASE PLEASE
 SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR THE GAS GENERATOR TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3
  
 NEW COMMENT'S
  
 8) SYSTEM IS CALLED OUT AS .5LB BUT YOU SHOW A PRESSURE
 REGULATOR ON THE CONNECTION DETAIL. PLEASE CLARIFY. FBC
 107.2.1
  
 9) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1,
  
 10) PRESSURE REGULATORS SHALL BE INSTALLED PER FBC-GAS
 410.2
  
 (A) A TEE FITTING WITH ONE OPENING CAPPED OR PLUGGED
 SHALL BE INSTALLED BETWEEN THE MP REGULATOR AND ITS
 UPSTREAM SHUTOFF VALVE.
  
 (B) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE
 INSTALLED WITHIN 1 FOOT (304 MM) OF EITHER SIDE OF THE
 MP REGULATOR.
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-04-10 Cont ID  
Sent By thunt Date 2019-04-10 Time 14:32 Rev Time 0.00
Received By thunt Date 2019-04-10 Time 06:56 Sent To  
Notes
2019-04-10 14:32:32GAS 1ST REVIEW**DENIED**
  
 1) GENERATORS ARE REQUIRED TO HAVE THERE OWN PERMIT AND
 NOT BE A SUB OFF OF MASTER PERMIT. NOTE MASTER PLAN
 DOES NOT SHOW GENERATOR
  
 2) VALUE SEEMS LOW AND MUST INCLUDE THE COST OF THE
 GENERATOR. WPB AMEND TO THE FBC 109.3
  
 3) STEEL PIPING IS NOT PERMITTED UNDERGROUND. FBC-G
 404.11.1
  
 4) PRIVATE PROVIDER PAPERWORK HAS NOT BEEN INCLUDE IN
 THIS SUBMITTAL. FBC 107.3.5
  
 5) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2.
  
 6) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 7) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-07-17 Cont ID  
Sent By gjohnson Date 2019-07-17 Time 16:54 Rev Time 0.00
Received By gjohnson Date 2019-07-03 Time 15:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-13 Cont ID  
Sent By dbattles Date 2019-06-13 Time 08:22 Rev Time 0.00
Received By dbattles Date 2019-05-30 Time 12:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-10 Cont ID  
Sent By thunt Date 2019-04-10 Time 14:32 Rev Time 0.00
Received By thunt Date 2019-04-08 Time 11:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-07-12 Cont ID  
Sent By dbattles Date 2019-07-12 Time 12:37 Rev Time 0.00
Received By dbattles Date 2019-07-12 Time 12:37 Sent To  
Notes
2019-07-17 16:53:56PLUMBINGL SHEET: PER THE WPB AMENDMENTS TO THE FBC,
 EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL
 PLAN REQUIRES A DIGITAL SIGNATURE WITH THE PROPER THIRD
 PARTY VERIFICATION. SELF-CERTIFICATION IS NOT
 ACCEPTABLE FOR ENGINEERS. ADDITIONALLY, THE DIGITAL
 SIGNATURE MUST INCLUDE THE STATEMENT "SIGNED AND
 SEALED" AS PER FAC 61G15-23.004. PROVIDE CORRECTION.
 WPB FBC 107.1; FS 471/481
2019-07-10 06:53:26ELECTRICAL SHEETS: PER THE WPB AMENDMENTS TO THE FBC,
 EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL
 PLAN REQUIRES A DIGITAL SIGNATURE WITH THE PROPER THIRD
 PARTY VERIFICATION. SELF-CERTIFICATION IS NOT
 ACCEPTABLE FOR ENGINEERS. ADDITIONALLY, THE DIGITAL
 SIGNATURE MUST INCLUDE THE STATEMENT "SIGNED AND
 SEALED" AS PER FAC 61G15-23.004. PROVIDE CORRECTION.
 WPB FBC 107.1; FS 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-06-13 Cont ID  
Sent By dbattles Date 2019-06-13 Time 08:20 Rev Time 0.00
Received By dbattles Date 2019-06-13 Time 08:20 Sent To  
Notes
2019-06-13 08:22:35ANY NEW SHEETS PROVIDED TO BE DIGITALLY SIGNED

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-04-10 Cont ID  
Sent By thunt Date 2019-04-10 Time 14:32 Rev Time 0.00
Received By thunt Date 2019-04-10 Time 14:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2019-07-16 Cont ID  
Sent By eschneid Date 2019-07-16 Time 14:00 Rev Time 0.25
Received By eschneid Date 2019-07-16 Time 14:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-05-31 Cont ID  
Sent By eschneid Date 2019-05-31 Time 09:22 Rev Time 0.25
Received By eschneid Date 2019-05-31 Time 09:22 Sent To  
Notes
2019-05-31 09:40:58FAILED
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) PROVIDE THE INFORMATION ON THE GENERATOR, TO INCLUDE
 LENGTH, WIDTH AND HEIGHT DIMENSIONS (HEIGHT DIMENSION
 TO HIGHEST FEATURE OF GENERATOR).
  
 2) PROVIDE INFORMATION ON HOW THE GENERATOR WILL BE
 SCREENED IN ACCORDANCE WITH THE CITYPLACE DRI WHICH
 REQUIRES THAT ALLL MECHANICAL EQUIPMENT BE SCREENED
 FROM PUBLIC VIEW THROUGH ANY COMBINATION OF
 LANDSCAPING, WALLS AND EQUIPMENT LOCATION. PLEASE
 PROVIDE DRAWINGS VERIFYING THAT THE PROPOSED GENERATOR
 AND ATS WILL BE SCREENED FROM PUBLIC VIEW.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]