Plan Review Details - Permit 19040110
Plan Review Stops For Permit 19040110
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-05-15 Cont ID  
Sent By jgomez Date 2019-05-15 Time 14:04 Rev Time 0.00
Received By jgomez Date 2019-05-15 Time 13:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-05-15 Cont ID  
Sent By jgomez Date 2019-05-15 Time 09:32 Rev Time 0.00
Received By jgomez Date 2019-05-15 Time 09:08 Sent To  
Notes
2019-05-15 09:26:32RESIDENTIAL (R3) RE-ROOF, THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL1654-R23
 SUBMITTED:
 A) SELECTED ASSEMBLY W-104 DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES. NEED TO PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY
 LIMITATION #5.7 ON PAGE 5 OF 6 OF PRODUCT APPROVAL
 SUBMITTED. NEED THE CALCULATIONS TO MEET THE DESIGN
 PRESSURES REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-05-06 Cont ID  
Sent By jgomez Date 2019-05-06 Time 09:03 Rev Time 0.00
Received By jgomez Date 2019-05-06 Time 08:26 Sent To  
Notes
2019-05-06 08:58:35RESIDENTIAL (R3) RE-ROOF, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL1654-R22
 SUBMITTED:
 A) SELECTED ASSEMBLY W-104 DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES. NEED TO PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY
 LIMITATION #5.7 ON PAGE 5 OF 6 OF PRODUCT APPROVAL
 SUBMITTED. NEED THE CALCULATIONS TO MEET THE DESIGN
 PRESSURES REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL.
 NOTE: CONTRACTOR MAY SELECT ANOTHER ASSEMBLY THAT MEETS
 THE DESIGN PRESSURES FOR ALL ROOF ZONES AND RAS 117
 CALCULATIONS ARE NOT REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 B) PROVIDE CURRENT FLORIDA PRODUCT APPROVAL. CURRENT
 FLORIDA PRODUCT APPROVAL IS FL1654-R23 NOT FL1654-R22.
 FAC 61G20-3.001.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 C) PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL. PRODUCT
 APPROVAL SUBMITTED IS MISSING THE FLORIDA PRODUCT
 APPROVAL COVER PAGE. THIS PAGE IS REQUIRED BECAUSE IT
 SHOWS THE CURRENT CODE VERSION AND THE PRODUCT APPROVAL
 STATUS. CHAPTER 553 F.S. AND FAC 61G20-3.001.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 2- METAL ROOFING PANELS WERE CHANGED TO SHINGLES
 BECAUSE HISTORIC DOESN'T ALLOW METAL ROOFING PANELS.
 THE FOLLOWING REQUIRED INFORMATION WAS NOT SUBMITTED AS
 REQUESTED ON PREVIOUS CHECKLIST:
  
 A) SPECIFY ROOF PITCH AND ROOF MEAN ROOF HEIGHT AS
 REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS AND
 SEC. R905.10.2 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 B) PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL. PRODUCT
 APPROVAL SUBMITTED IS MISSING THE FLORIDA PRODUCT
 APPROVAL COVER PAGE. THIS PAGE IS REQUIRED BECAUSE IT
 SHOWS THE CURRENT CODE VERSION AND THE PRODUCT APPROVAL
 STATUS. CHAPTER 553 F.S. AND FAC 61G20-3.001.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 3- ROOF UNDERLAYMENT FL21895-R2 SUBMITTED: PROVIDE
 COMPLETE FLORIDA PRODUCT APPROVAL. PRODUCT APPROVAL
 SUBMITTED IS MISSING THE FLORIDA PRODUCT APPROVAL COVER
 PAGE. THIS PAGE IS REQUIRED BECAUSE IT SHOWS THE
 CURRENT CODE VERSION AND THE PRODUCT APPROVAL STATUS.
 CHAPTER 553 F.S. AND FAC 61G20-3.001.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 4- THERE IS MORE THAN ONE STRUCTURE IN THIS PROPERTY.
 PROVIDE MAP OR SKETCH SHOWING LOCATION OF AREA OF WORK
 AND SQUARE FOOTAGE OF EACH AREA (PITCH AND FLAT) AS
 REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS AND
 SEC. 107.02.1 CITY AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WILL BE RE-EVALUATED ONCE THE
 ROOFING AREAS ARE PROVIDED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-02 Cont ID  
Sent By jgomez Date 2019-04-03 Time 18:29 Rev Time 0.00
Received By jgomez Date 2019-04-02 Time 18:16 Sent To HIST
Notes
2019-04-02 18:29:50RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL1654-R22
 SUBMITTED:
 A) SELECTED ASSEMBLY W-104 DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES. NEED TO PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY
 LIMITATION #5.7 ON PAGE 5 OF 6 OF PRODUCT APPROVAL
 SUBMITTED. NEED THE CALCULATIONS TO MEET THE DESIGN
 PRESSURES REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL.
 NOTE: CONTRACTOR MAY SELECT ANOTHER ASSEMBLY THAT MEETS
 THE DESIGN PRESSURES FOR ALL ROOF ZONES AND RAS 117
 CALCULATIONS ARE NOT REQUIRED.
  
 B) PROVIDE CURRENT FLORIDA PRODUCT APPROVAL. CURRENT
 FLORIDA PRODUCT APPROVAL IS FL1654-R23 NOT FL1654-R22.
 FAC 61G20-3.001.
  
 C) PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL. PRODUCT
 APPROVAL SUBMITTED IS MISSING THE FLORIDA PRODUCT
 APPROVAL COVER PAGE. THIS PAGE IS REQUIRED BECAUSE IT
 SHOWS THE CURRENT CODE VERSION AND THE PRODUCT APPROVAL
 STATUS. CHAPTER 553 F.S. AND FAC 61G20-3.001.
  
 2- METAL ROOFING PANELS: FLORIDA PRODUCT APPROVAL
 FL27499 SUBMITTED:
 A) SPECIFY ROOF PITCH AND ROOF MEAN ROOF HEIGHT AS
 REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS AND
 SEC. R905.10.2 FBC-RESIDENTIAL.
  
 B) PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL. PRODUCT
 APPROVAL SUBMITTED IS MISSING THE FLORIDA PRODUCT
 APPROVAL COVER PAGE. THIS PAGE IS REQUIRED BECAUSE IT
 SHOWS THE CURRENT CODE VERSION AND THE PRODUCT APPROVAL
 STATUS. CHAPTER 553 F.S. AND FAC 61G20-3.001.
  
 3- ROOF UNDERLAYMENT FL21895-R2 SUBMITTED: PROVIDE
 COMPLETE FLORIDA PRODUCT APPROVAL. PRODUCT APPROVAL
 SUBMITTED IS MISSING THE FLORIDA PRODUCT APPROVAL COVER
 PAGE. THIS PAGE IS REQUIRED BECAUSE IT SHOWS THE
 CURRENT CODE VERSION AND THE PRODUCT APPROVAL STATUS.
 CHAPTER 553 F.S. AND FAC 61G20-3.001.
  
 4- THERE IS MORE THAN ONE STRUCTURE IN THIS PROPERTY.
 PROVIDE MAP OR SKETCH SHOWING LOCATION OF AREA OF WORK
 AND SQUARE FOOTAGE OF EACH AREA (PITCH AND FLAT) AS
 REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS AND
 SEC. 107.02.1 CITY AMENDMENTS.
  
 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WILL BE RE-EVALUATED ONCE THE
 ROOFING AREAS ARE PROVIDED.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2019-05-14 Cont ID  
Sent By fmittner Date 2019-05-14 Time 15:25 Rev Time 0.00
Received By fmittner Date 2019-05-14 Time 15:25 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-05-02 Cont ID  
Sent By fmittner Date 2019-05-02 Time 10:00 Rev Time 0.00
Received By fmittner Date 2019-05-02 Time 10:00 Sent To B
Notes
2019-05-02 10:00:18USING SHINGLES

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2019-04-10 Cont ID  
Sent By fmittner Date 2019-04-10 Time 16:47 Rev Time 0.00
Received By fmittner Date 2019-04-10 Time 16:47 Sent To  
Notes
2019-04-10 16:48:38PROPERTY LOCATED IN HISTORIC DISTRICT. METAL ROOFING
 DOES NOT MET DESIGN GUIDLEINES FOR THIS MASONRY
 VERNACUALR STRUCTURE.
  
 QUESTIONS, CONTATC: FRIEDERIKE MITTNER, CITY HISTORIC
 PRESERVATION PLANNER AT (561) 822-1457

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-05-15 Cont ID  
Sent By jgomez Date 2019-05-15 Time 14:04 Rev Time 0.00
Received By jgomez Date 2019-05-15 Time 13:55 Sent To I
Notes
2019-05-15 13:56:42HELLO JULIO,
  
 PLEASE FIND ATTACHED THE CORRECT SYSTEM FOR 840 KANUGA
 DRIVE.
  
 THANK YOU!
  
  
  
 --
 SAMIRA GONZALEZ
 TOTAL ROOFING SYSTEMS SPECIALIST, INC.
 3201 SE DOMINICA TER
 STUART, FL 34997
 OFFICE (772) 872-8030/ FAX (772) 872-8033
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-05-15 Cont ID  
Sent By jgomez Date 2019-05-15 Time 09:41 Rev Time 0.00
Received By jgomez Date 2019-05-09 Time 15:41 Sent To I
Notes
2019-05-09 15:42:03RESUB ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-06 Cont ID  
Sent By jgomez Date 2019-05-06 Time 09:20 Rev Time 0.00
Received By jgomez Date 2019-04-25 Time 15:45 Sent To I
Notes
2019-04-26 15:45:48RESUB ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-11 Cont ID  
Sent By cpuell Date 2019-04-11 Time 10:46 Rev Time 0.00
Received By cpuell Date 2019-04-02 Time 14:14 Sent To  
Notes
***NONE***