Plan Review Details - Permit 19040094
Plan Review Stops For Permit 19040094
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date   Cont ID  
Sent By   Date 2021-02-02 Time 14:58 Rev Time 0.00
Received By jwitmer Date 2021-02-02 Time 14:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-08-10 Cont ID  
Sent By jwitmer Date 2020-08-10 Time 16:02 Rev Time 0.00
Received By jwitmer Date 2020-08-10 Time 15:30 Sent To  
Notes
2020-08-10 16:02:212017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19040094
 ADD: 905 9TH ST. / PCN: 74-43-43-16-01-140-0130
 CONT: SUNRISE CITY
 TEL: 561-350-5866
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. AUGUST 10TH/2020
 ACTION: DENIED
  
 1-6) SEMI- COMPLIED. THIS IS THE 3RD REVIEW WITH A SET
 OF PLANS THAT ARE ORIGINAL SIGNED AND SEALED PLANS.
 THE SHEET A-0.3 INDICATES BETWEEN THE R2 OCCUPANCIES
 THERE IS A ONE HOUR FIRE RATED WALL ALL THE WAY TO THE
 ROOF DECK. THE PLANS ARE SILENT AS TO WHAT MATERIALS
 ARE GOING TO MAKE UP THE ONE HOUR FIRE RATING. SHEET
 A-3.1 INDICATES THE TENANT SEPARATION WALLS WITH A WALL
 TYPE IDENTIFICATION TAG, (F) 1 5/8 METAL FURRING WALL.
 NOT METAL STUD WALL BUT ONLY METAL FURRING, METAL
 FURRING IS USUALLY APPLIED TO CONCRETE BLOCK
 WALLSPLEASE PROVIDE EITHER A UL WALL LISTING AND SHOW
 THE WALL COMPONENTS OR GYPSUM ASSOCIATION WALL LISTING
 AND THEIR COMPONENTS AND HOURLY FIRE RATING. PLEASE
 SHOW COMPLIANCE WITH THE 2017 FBC-B SECTION 420.2
 SEPARATION WALLS/ FIRE PARTITIONS. THE COMMON WALL
 BETWEEN THE R-2 UNITS NEEDS TO SHOW COMPLIANCE WITH THE
 2017 FBC-B SECTION 708, FIRE PARTITIONS. PLEASE SHOW
 COMPLIANCE WITH 2017 FBC-B SECTION:
 708.3 FIRE-RESISTANCE RATING. FIRE PARTITIONS SHALL
 HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR.
 708.4 CONTINUITY. FIRE PARTITIONS SHALL EXTEND FROM THE
 TOP OF THE FOUNDATION OR FLOOR/CEILING ASSEMBLY BELOW
 TO THE UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB
 OR DECK ABOVE OR TO THE FIRE-RESISTANCE-RATED
 FLOOR/CEILING OR ROOF/CEILING ASSEMBLY ABOVE, AND SHALL
 BE SECURELY ATTACHED THERETO.
  
 6) 3RD REQUEST. THERE SEEMS TO BE A DISCREPANCY WITHIN
 THE SET OF PLANS. SHEET A-0.4 THE DEMO PLAN STATES ALL
 EXTERIOR WINDOWS AND DOORS TO REMAIN. IDENTIFIED THE
 COMMENT WITH RED CIRCLEE. WHEREAS SHEET A-3.1 NOTE # 2
 IN THE LOWER LEFT HAND CORNER OF THE SHEET INDICATES
 THE EXISTING WINDOWS AND DOORS ARE TO BE REPLACED
 IDENTIFIED WITH RED CIRCLE. . 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED, DISCREPANCY.
  
 6A) 3RD REQUEST. THE WIND DESIGN CRITERIA HAS BEEN
 PROVIDED AND ASSOCIATED VULT PRESSURES. PLEASE PROVIDE
 THE ASSOCIATED PRESSURES IN VASD SINCE THE PRODUCT
 APPROVALS HAVE ALL BEEN TESTED IN VASD AND RECORDED
 RESULT ARE IN VASD. 1609.3.1 WIND SPEED CONVERSION VULT
 TO VASD.
  
 6B) 3RD REQUEST. IF WINDOWS AND DOORS ARE TO BE
 REPLACED PLEASE SHOW COMPLIANCE WITH: 2017 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (E) SHUTTERS
  
 6C) 3RD REQUEST. IDENTIFY GLAZING/ MULLIONS. THE
 SUBMITTED PRODUCT APPROVALS THE ELEMENTS LISTED BELOW
 ARE NOT IDENTIFIED. PLEASE IDENTIFY ON THE PRODUCT
 APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH
 IF UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2017 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 6D)3RD REQUEST. W. P. B. 107.3.4. PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA
 ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-12-17 Cont ID  
Sent By jwitmer Date 2019-12-17 Time 14:54 Rev Time 0.00
Received By jwitmer Date 2019-12-17 Time 13:33 Sent To  
Notes
2019-12-17 14:54:212017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19040094
 ADD: 905 9TH ST. / PCN: 74-43-43-16-01-140-0130
 CONT: SUNRISE CITY
 TEL: 561-350-5866
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. DEC. 17/2019
 ACTION: DENIED
  
 1-6) SEMI- COMPLIED. THIS IS THE 1ST REVIEW WITH A SET
 OF PLANS THAT ARE ORIGINAL SIGNED AND SEALED PLANS.
 THE SHEET A-0.3 INDICATES BETWEEN THE R2 OCCUPANCIES
 THERE IS A ONE HOUR FIRE RATED WALL ALL THE WAY TO THE
 ROOF DECK. THE PLANS ARE SILENT AS TO WHAT MATERIALS
 ARE GOING TO MAKE UP THE ONE HOUR FIRE RATING. SHEET
 A-3.1 INDICATES THE TENANT SEPARATION WALLS WITH A WALL
 TYPE IDENTIFICATION TAG, (F) 1 5/8 METAL FURRING.
 PLEASE PROVIDE EITHER A UL WALL LISTING AND SHOW THE
 WALL COMPONENTS OR GYPSUM ASSOCIATION WALL LISTING AND
 THEIR COMPONENTS AND HOURLY FIRE RATING. PLEASE SHOW
 COMPLIANCE WITH THE 2017 FBC-B SECTION 420.2 SEPARATION
 WALLS/ FIRE PARTITIONS. THE COMMON WALL BETWEEN THE R-2
 UNITS NEEDS TO SHOW COMPLIANCE WITH THE 2017 FBC-B
 SECTION 708, FIRE PARTITIONS. PLEASE SHOW COMPLIANCE
 WITH 2017 FBC-B SECTION:
 708.3 FIRE-RESISTANCE RATING. FIRE PARTITIONS SHALL
 HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR.
 708.4 CONTINUITY. FIRE PARTITIONS SHALL EXTEND FROM THE
 TOP OF THE FOUNDATION OR FLOOR/CEILING ASSEMBLY BELOW
 TO THE UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB
 OR DECK ABOVE OR TO THE FIRE-RESISTANCE-RATED
 FLOOR/CEILING OR ROOF/CEILING ASSEMBLY ABOVE, AND SHALL
 BE SECURELY ATTACHED THERETO.
  
 6) THERE SEEMS TO BE A DISCREPANCY WITHIN THE SET OF
 PLANS. SHEET A-0.4 THE DEMO PLAN STATES ALL EXTERIOR
 WINDOWS AND DOORS TO REMAIN. WHEREAS SHEET A-3.2 NOTE #
 2 IN THE LOWER LEFT HAND CORNER OF THE SHEET INDICATES
 THE EXISTING WINDOWS AND DOORS ARE TO BE REPLACED.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED,
 DISCREPANCY.
  
 6A) THE WIND DESIGN CRITERIA HAS BEEN PROVIDED AND
 ASSOCIATED VULT PRESSURES. PLEASE PROVIDE THE
 ASSOCIATED PRESSURES IN VASD SINCE THE PRODUCT
 APPROVALS HAVE ALL BEEN TESTED IN VASD AND RECORDED
 RESULT ARE IN VASD. 1609.3.1 WIND SPEED CONVERSION VULT
 TO VASD.
  
 6B) IF WINDOWS AND DOORS ARE TO BE REPLACED PLEASE SHOW
 COMPLIANCE WITH: 2017 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (E) SHUTTERS
  
 6C) IDENTIFY GLAZING/ MULLIONS. THE SUBMITTED PRODUCT
 APPROVALS THE ELEMENTS LISTED BELOW ARE NOT IDENTIFIED.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 6D) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-30 Cont ID  
Sent By jwitmer Date 2019-04-30 Time 08:59 Rev Time 0.00
Received By jwitmer Date 2019-04-30 Time 08:33 Sent To  
Notes
2019-04-30 08:59:072017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19040094
 ADD: 905 9TH ST. / PCN: 74-43-43-16-01-140-0130
 CONT: SUNRISE CITY
 TEL: 561-350-5866
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. APRIL 30/2019
 ACTION: DENIED
  
 1) THE SUBMITTED PLANS ARE COPIES NOT ORIGINAL PLANS,
 COPYRIGHT LAWS PROHIBIT THE COPYING OF PLANS AND TAKING
 OWNERSHIP AS YOUR OWN. PLAN IS CONSTITUTED BY 1 SHEET.
 THE MECHANICAL CONTRACTOR TOKE OWNERSHIP OF 1 PLAN BY
 SIGNING PLAN AND COMPANY LICENSE NUMBER, THE OTHER THE
 ELECTRICAL CONTRACTOR TOOK OWNERSHIP OF THE SAME COPIED
 PLAN SIGNED PLAN AND COMPANY LICENSE NUMBER.
 THE BUILDING CONTRACTOR SUNRISE CITY DID NOT SUBMIT ANY
 PLANS.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.3 QUALITY OF
 BUILDING PLANS. BUILDING PLANS SHALL BE DRAWN TO A
 MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR
 OTHER ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS
 FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY
 MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH
 THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.
 2) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE SECTION 503).
  
 3) FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 FIRE BLOCKING AND DRAFT STOPPING AND CALCULATED FIRE
 RESISTANCE
  
 4) 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS / PRE-ENGINEERED SYSTEMS
  
 5) 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 CONSTRUCTION REQUIREMENTS
  
 6) 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 DESIGN LOADS
 WIND REQUIREMENTS
 BUILDING ENVELOPE
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, ROOF TOP VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-02-08 Cont ID  
Sent By jleahy Date 2021-02-08 Time 16:57 Rev Time 0.00
Received By jleahy Date 2021-02-08 Time 16:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2020-08-14 Cont ID  
Sent By jleahy Date 2020-08-14 Time 17:07 Rev Time 0.00
Received By jleahy Date 2020-08-14 Time 17:04 Sent To  
Notes
2020-08-14 17:08:27SEE REVIEW COMMENTS FROM 12/22/19 JLEAHY

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-12-22 Cont ID  
Sent By jpearson Date 2019-12-22 Time 11:22 Rev Time 0.00
Received By jpearson Date 2019-12-22 Time 11:22 Sent To  
Notes
2019-12-22 10:22:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 BE ADVISED THAT THE CURRENT PLAN IS SUBSTANTIALLY
 LACKING OF INFORMATION. THEREFORE, THERE MAY BE
 ADDITIONAL COMMENTS FOR SECOND REVIEW THAT ARE NOT
 ADDRESSED IN THIS REVIEW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED, BUT FURTHER CORRECTIONS NEEDED BASED ON
 SUBMISSION, SEE NEW COMMENTS BELOW.
 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30 (LOAD CALCULATION
 IS NOT ACCURATE AND DOES NOT INCLUDE ALL EQUIPMENT.
 FURTHERMORE, THE AMOUNT OF VA SPECIFIED FOR MANY OF THE
 ITEMS DOES NOT CORRESPOND TO KNOW VALUES. PROVIDE
 CORRECTIONS AND MANUFACTURERES SPECIFICATION FOR
 EQUIPMENT.)
 4. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING ANY
 NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR
 THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE
 APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12,
 210.19, 210.20, 215.5, 408.4 (ONLY ONE PANEL IS SHOWN
 IN RISER DIAGRAM, BUT IS IS NOT POSSIBLE TO HAVE THE
 CIRCUITS FOR ALL THREE UNITS IN THIS ONE PANEL.
 ADDITIONALLY, EACH OCCUPANT SHALL HAVE READY ACCESS TO
 ALL OVERCURRENT DEVICES PROTECTING THE CONDUCTORS
 SUPPLYING THAT OCCUPANCY. PROVIDE CORRECTION. NEC
 240.24(B))
 5. PLAN SEEMS TO INDICATE THERE WILL BE A NEW
 ELECTRICAL SERVICE. PROVIDE AVAILABLE SHORT CIRCUIT
 CALCULATION FOR SERVICE INCLUDING INFORMATION FROM THE
 POWER COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT
 CURRENT IS FOR THE SERVICE TO CONFIRM THE STATED AIC
 RATING OF THE SERVICE EQUIPMENT IS ADEQUATE. PROVIDE
 AIC RATING OF ALL ELECTRICAL SERVICE EQUIPMENT AND
 PANELS. NEC 110.3, 110.9, 110.10 (PLAN STATED NEW METER
 AND NEW PANEL. PROVIDE AS PREVIOUSLY REQUESTED.)
 6. CORRECTED.
  
 NEW COMMENTS:
  
 7. PROVIDE ACCURATE RISER DIAGRAM THAT IS CODE
 COMPLIANT, SHOWING ALL DETAILS OF SERVICE EQUIPMENT,
 UNDERGROUND OR OVERHEAD SERVICE, WIRE AND BREAKER SIZES
 FOR SERVICE AND FEED TO ANY SUB-PANEL(S). SHOW GEC SIZE
 AND SYSTEM, SHOW INTERSYSTEM BONDING TERMINATION POINT.
 THE RISER DIAGRAM SHOULD REFLECT THE REQUIRED PANEL TO
 EACH TENANT SPACE. ONLY ONE SERVICE IS PERMITTED BASED
 ON LOAD, BUT ADDITIONAL METERS FOR EACH UNIT ARE
 PERMITTED IF SO DESIRED. NEC 215.5, 230.2, 250.50,
 250.94, 408.30
 8. SHOW LOCATION OF ELECTRICAL SERVICE AND ANY
 ELECTRICAL PANELS ON PLAN. WPB FBC 107.2.1
 9. A MINIMUM OF TWO SMALL APPLIANCE BRANCH CIRCUITS ARE
 REQUIRED FOR RECEPTACLE OUTLETS THAT FEED THE KICHEN
 COUNTER SPACE IN EACH UNIT. PROVIDE CORRECTION. NEC
 210.11, 210.52
 10. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S) IN
 EACH UNIT. SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS.
 PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52
 11. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63
 12. AFCI PROTECTION AS SHOWN IN NOTE 2 IS NOT CODE
 COMPLIANT. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902;
 FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE.
 13. NOTE 6 QUOTES THE 2011 NEC FOR COMPLIANCE OF TAMPER
 RESISTANT RECEPTACLES. THE 2011 NEC IS NOT THE CURRENT
 CODE. THIS NOTE ALSO QUOTES THE WRONG CODE SECTION,
 406.10, WHICH DOES NOT APPLY. PROVIDE CORRECTIONS. FBC
 PREFACE. NEC 406.12
 14. NOTES 3, 4, AND 5 SPECIFY SMOKE ALARMS, BUT NONE
 ARE SHOWN ON PLAN. PROVIDE SMOKE/CO ALARMS IN EACH
 LOCATION REQUIRED PER CODE TO CONFIRM COMPLIANCE. FBC
 RE R314.3, R315.1; WPB FBC 107.2.1
 15. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE
 INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG
 THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE OUTLET. THE WALL SPACING REQUIREMENTS
 FOR KITCHEN COUNTER SPACE STATE THAT RECEPTACLE OUTLETS
 SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE
 IS MORE THAN 24 INCHES MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE. THE PLAN PROVIDED DOES
 NOT MEET THIS CODE IN SOME AREAS. PROVIDE CORRECTION.
 NEC 210.52(C)(1); FBC RE E3901
 16. PANEL SCHEDULE SHOWS A GARAGE DOOR CIRCUIT, AND A
 CIRCUIT FOR LIFT STATION. THESE ARE NOT SHOWN ON PLAN
 ANYWHERE. PROVIDE CLARIFICATION AND/OR CORRECTIONS AS
 NEEDED. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-23 Cont ID  
Sent By jpearson Date 2019-04-23 Time 15:52 Rev Time 0.00
Received By jpearson Date 2019-04-23 Time 15:01 Sent To  
Notes
2019-04-23 15:52:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 BE ADVISED THAT THE CURRENT PLAN IS SUBSTANTIALLY
 LACKING OF INFORMATION. THEREFORE, THERE MAY BE
 ADDITIONAL COMMENTS FOR SECOND REVIEW THAT ARE NOT
 ADDRESSED IN THIS REVIEW.
  
 1. PROVIDE COMPLETE ELECTRICAL PLAN FOR REVIEW,
 DETAILING ALL WORK AS DESCRIBED IN PROVIDED CONTRACT.
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A LICENSED
 DESIGN PROFESSIONAL OR SIGNED BY THE ELECTRICAL
 CONTRACTOR QUALIFIER. FS 471.003(2)(H); 471.025; WPB
 FBC 107.2.1, 107.3.5
 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30
 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
 4. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING ANY
 NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR
 THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE
 APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12,
 210.19, 210.20, 215.5, 408.4
 5. PLAN SEEMS TO INDICATE THERE WILL BE A NEW
 ELECTRICAL SERVICE. PROVIDE AVAILABLE SHORT CIRCUIT
 CALCULATION FOR SERVICE INCLUDING INFORMATION FROM THE
 POWER COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT
 CURRENT IS FOR THE SERVICE TO CONFIRM THE STATED AIC
 RATING OF THE SERVICE EQUIPMENT IS ADEQUATE. PROVIDE
 AIC RATING OF ALL ELECTRICAL SERVICE EQUIPMENT AND
 PANELS. NEC 110.3, 110.9, 110.10
 6. THE WEST PALM BEACH AMENDMENTS TO THE FBC 2017 6TH
 ED, CHAPTER 1, STATE THE FOLLOWING: QUALITY OF BUILDING
 PLANS. BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8
 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER
 ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS
 AND SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO
 ITS RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE
 SUCH THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY,
 OR OTHER ITEMS RELATED TO RECORDS MANAGEMENT. PROVIDE
 PLANS PER THIS REQUIREMENT. WPB FBC 107.2.1.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-08-06 Cont ID  
Sent By pleduc Date 2020-08-06 Time   Rev Time 0.00
Received By pleduc Date 2020-08-06 Time 08:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-12-09 Cont ID  
Sent By pleduc Date 2019-12-09 Time   Rev Time 0.00
Received By pleduc Date 2019-12-09 Time 13:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-04-09 Cont ID  
Sent By scaldero Date 2019-04-09 Time 12:00 Rev Time 0.00
Received By scaldero Date 2019-04-09 Time 11:53 Sent To  
Notes
2019-04-09 12:00:01PERMIT # 19040094
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAIL COMMENTS:
  
 1) SCOPE OF WORK INCLUDES INSTALL DRYWALL, INTERIOR
 DOORS, KITCHEN AND BATHROOM CABINETS, SINKS, TOILETS,
 WATER HEATER, FLOORING , AS WELL AS ELECTRICAL
 UPGRADES. THE PLAN PROVIDED DOES NOT ACCURATELY
 REPRESENT THE SCOPE OF WORK AND APPEARS TO ONLY
 INDENTIFY SOME OF THE ELECTRICAL WORK.
 PROVIDE PLANS THAT FULLY SHOW THE SCOPE OF WORK,
 RENOVATIONS, AND UPGRADES.
  
 2) PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
  
 3) PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 4) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 5) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM, WHERE APPLICABLE.
  
 6) WORK SHALL COMPLY WITH THE 6TH EDITION OF THE
 FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE 2015
 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2021-02-22 Time   Rev Time 0.00
Received By lmarchan Date 2021-02-18 Time 11:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-02-08 Cont ID  
Sent By jleahy Date 2021-02-08 Time 16:58 Rev Time 0.00
Received By jleahy Date 2021-01-29 Time 08:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-08-14 Cont ID  
Sent By jleahy Date 2020-08-14 Time 17:08 Rev Time 0.00
Received By jleahy Date 2020-07-29 Time 09:23 Sent To  
Notes
2020-08-05 17:42:3008/05/2020 CONVERTED TO DIGITAL. JG.
  
2020-07-28 07:54:23ROUTED TO B22

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-12-23 Cont ID  
Sent By gjohnson Date 2019-12-23 Time 16:06 Rev Time 0.00
Received By gjohnson Date 2019-12-03 Time 15:16 Sent To  
Notes
2019-12-04 15:16:27B22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2019-04-30 Time   Rev Time 0.00
Received By lmarchan Date 2019-04-02 Time 15:51 Sent To  
Notes
2019-04-03 15:51:31B26

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-04-30 Cont ID  
Sent By jwitmer Date 2019-04-30 Time 08:59 Rev Time 0.00
Received By jwitmer Date 2019-04-30 Time 08:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2021-02-02 Cont ID  
Sent By medwards Date 2021-02-02 Time 15:10 Rev Time 0.00
Received By medwards Date 2021-02-02 Time 15:10 Sent To  
Notes
2021-02-02 15:11:31MECHANICAL PASSED WITH PRIVISO:
 DRYER INSTALLATION MUST MEET FBC M 504
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2020-08-07 Cont ID  
Sent By medwards Date 2020-08-07 Time 07:56 Rev Time 0.00
Received By medwards Date 2020-08-07 Time 07:54 Sent To  
Notes
2020-08-07 07:55:58PLEASE PROVIDE THE INFORMATION THAT WAS REQUESTED IN
 THE 2ND CYCLE REVIEW.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-12-23 Cont ID  
Sent By ccole Date 2019-12-23 Time 09:30 Rev Time 0.00
Received By ccole Date 2019-12-23 Time 09:29 Sent To  
Notes
2019-12-23 09:41:102ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19040094
 12/23/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW STILL
 EXIST.
  
 1) THE MECHANICAL PLANS FOR THE NEW AC SYSTEMS ARE
 INCOMPLETE- SECTION 107.2.1 WPB. PLEASE PROVIDE:
  
 A) DUCT LAYOUT PLANS FOR EACH OF THE THREE APARTMENTS-
 SECTION 603 FBC M. (INCOMPLETE AC PLANS HAVE BEEN
 SUBMITTED. PROVIDE- AC EQUIPMENT SCHEDULES ON THE
 PLANS, SHOW THE SUPPLY CFMS AT EACH DIFFUSER, AND SHOW
 RETURN AIR FROM THE BEDROOMS.
 B) AC COOLING AND HEATING CALCULATIONS FOR THE NEW
 SYSTEMS- SECTION R503.2 FBC EC. (NOT PROVIDED)
 C) ENERGY CALCULATIONS FOR THE NEW CONDITIONED SPACES-
 SECTION R403.6.1 FBC EC. (NOT PROVIDED)
 D) VENTILATION CALCULATIONS PER TABLE 403.3.1.1 FOR
 EACH APARTMENT, AND INDICATE HOW OUTDOOR AIR IS BEING
 PROVIDED AND AUTOMATICALLY CONTROLLED- SECTION
 C403.2.4.3 FBC EC. (NOT PROVIDED)
 D) EXTERIOR CONDENSER MOUNTING DETAILS- SECTION 301.15
 FBC M. (OK)
 E) CONDENSATE DISPOSAL PLANS- SECTION 307.2.1 FBC M.
 (NOT PROVIDED)
  
 2) PLEASE NOTE THAT LOUVERED AC CLOSET DOORS USED FOR
 RETURN AIR SHALL BE NON-COMBUSTIBLE PER SECTION 602 FBC
 M. (OK)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-04-19 Cont ID  
Sent By ccole Date 2019-04-19 Time 07:52 Rev Time 0.00
Received By ccole Date 2019-04-19 Time 07:12 Sent To  
Notes
2019-04-19 08:26:051ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19040094
 4/19/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MECHANICAL PLANS FOR THE NEW AC SYSTEMS ARE
 INCOMPLETE- SECTION 107.2.1 WPB. PLEASE PROVIDE:
  
 A) DUCT LAYOUT PLANS FOR EACH OF THE THREE APARTMENTS-
 SECTION 603 FBC M.
 B) AC COOLING AND HEATING CALCULATIONS FOR THE NEW
 SYSTEMS- SECTION R503.2 FBC EC
 C) ENERGY CALCULATIONS FOR THE NEW CONDITIONED SPACES-
 SECTION R403.6.1 FBC EC.
 D) VENTILATION CALCULATIONS PER TABLE 403.3.1.1 FOR
 EACH APARTMENT, AND INDICATE HOW OUTDOOR AIR IS BEING
 PROVIDED AND AUTOMATICALLY CONTROLLED- SECTION
 C403.2.4.3 FBC EC.
 D) EXTERIOR CONDENSER MOUNTING DETAILS- SECTION 301.15
 FBC M
 E) CONDENSATE DISPOSAL PLANS- SECTION 307.2.1 FBC M.
  
 2) PLEASE NOTE THAT LOUVERED AC CLOSET DOORS USED FOR
 RETURN AIR SHALL BE NON-COMBUSTIBLE PER SECTION 602 FBC
 M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2021-02-22 Cont ID  
Sent By ccole Date 2021-02-22 Time 08:03 Rev Time 0.00
Received By ccole Date 2021-02-22 Time 07:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2021-02-08 Cont ID  
Sent By ccole Date 2021-02-08 Time 11:18 Rev Time 0.00
Received By ccole Date 2021-02-08 Time 10:07 Sent To  
Notes
2021-02-08 11:19:254TH REVIEW FBC-2017 PLUMBING
 PERMIT- 19040094
 2/8/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE COD
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 3RD REVIEW LISTED BELOW ARE MARKED AS
 PASSED OR FAILED. NOTES IN CAP LETTERS HAVE BEEN ADDED
 TO FAILED COMMENTS.
  
 1) FAILED. INDICATE ON THE PLANS IF THE NEW STACKABLE
 WASHER/DRYER IS CONNECTING TO EXISTING WATER AND DRAIN
 LINES. IF NEW WATER AND DRAIN LINES ARE BEING
 INSTALLED, SUBMIT A SANITARY AND WATER RISER DIAGRAM
 THAT CLEARLY REFLECTS THE SCOPE OF THE PLUMBING WORK TO
 BE DONE. WPB AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.3.
 THE ARCHITECT'S RESPONSE TO THE COMMENT INDICATES
 SAINTARY AND WATER RISER DRAWINGS WILL BE PROVIDED ON
 SHEET P-1.1, HOWEVER THE RISERS WERE NOT PROVIDED.
  
 2) FAILED IF A NEW DRAIN LINE IS BEING INSTALLED FOR
 THE WASHER, IT SHALL BE A MINIMUM OF 3 INCHES IN
 DIAMETER UP TO THE TRAP FOR THE WASHER STANDPIPE.
 FBC-PLUMBING SEC.406.2. SEE NOTES UNDER COMMENT #1.
  
 3) FAILED. THE WATER HEATERS SHALL BE EQUIPPED WITH
 PROVISIONS FOR THERMAL EXPANSION PER FBC-PLUMBING
 SEC.607.3. THERMAL EXPANSION TANKS SHALL BE CONNECTED
 TO THE WATER HEATER COLD WATER SUPPLY PIPE AT A POINT
 THAT IS DOWNSTREAM OF ALL CHECK VALVES, PRESSURE
 REDUCING VALVES AND BACKFLOW PREVENTERS. THE NEW WATER
 HEATER DETAIL IS SHOWING A "THERMAL EXPANSION (RELIEF
 VALVE)" ON THE HOT WATER LINE. PLEASE REFER TO SECTIONS
 504.4. 504.4.1 FOR RELIEF VALVE APPROVAL AND
 INSTALLATION LOCATION AND CORRECT THE PLAN.
  
 4) PASSED. THE WATER HEATERS SHALL BE INSTALLED WITH A
 HEATER PAN AND PAN DRAIN IN ACCORDANCE WITH
 FBC-PLUMBING SEC.504.6.
  
 5) PASSED. THE SHUTOFF VALVES FOR THE STACKABLE
 WASHER/DRYER SHALL BE PROVIDED WITH ACCESS PER
 FBC-PLUMBING SEC.606.3.
  
 6) PASSED. PLANS SHALL BEAR THE SIGNATURE AND SEAL OF
 THE DESIGN PROFESSIONAL. FL. ADMIN. CODE RULE
 61G1-16.001.
  
 NEW COMMENTS BASED ON RESUBMITTED PLANS.
  
 1) P-1.1: THE PLAN AND THE ENERGY COMPLIANCE FORM
 INDICATE 30-GALLON WATER HEATERS TO BE INSTALLED,
 HOWEVER THE DETAIL INDICATES A 40-GALLON UNIT. PLEASE
 PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN LISTING THE
 MAKE, MODEL, GALLON SIZE AND EFFICIENCY RATING OF THE
 WATER HEATERS- TABLE C404.2 FBC EC.
  
 2) P-1.1: PLEASE PROVIDE A SHOWER PAN DETAIL- SECTION
 417.5.2 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2020-08-11 Cont ID  
Sent By tklarge Date 2020-08-11 Time 08:56 Rev Time 0.00
Received By tklarge Date 2020-08-11 Time 06:18 Sent To  
Notes
2020-08-11 07:03:431) INDICATE ON THE PLANS IF THE NEW STACKABLE
 WASHER/DRYER IS CONNECTING TO EXISTING WATER AND DRAIN
 LINES. IF NEW WATER AND DRAIN LINES ARE BEING
 INSTALLED, SUBMIT A SANITARY AND WATER RISER DIAGRAM
 THAT CLEARLY REFLECTS THE SCOPE OF THE PLUMBING WORK TO
 BE DONE.WPB AMEND. TO FBC SEC. 107.2.1, 107.3..5.1.3.
 2) IF A NEW DRAIN LINE IS BEING INSTALLED FOR THE
 WASHER, IT SHALL BE A MINIMUM OF 3 INCHES IN DIAMETER
 UP TO THE TRAP FOR THE WASHER STANDPIPE.FBC-PLUMBING
 SEC.406..2.
 3) THE WATER HEATERS SHALL BE EQUIPPED WITH PROVISIONS
 FOR THERMAL EXPANSION PER FBC-PLUMBING SEC.607.3.
 4) THE WATER HEATERS SHALL BE INSTALLED WITH A HEATER
 PAN AND PAN DRAIN IN ACCORDANCE WITH FBC-PLUMBING
 SEC.504.6.
 5) THE SSHUTOFF VALVES FOR THE STACKABLE WASHER/DRYER
 SHALL BE PROVIDED WITH ACCESS PER FBC-PLUMBING
 SEC.606.3.
 6) PLANS SHALL BEAR THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL. FL. ADMIN. CODE RULE 61G1-16.001.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-12-23 Cont ID  
Sent By gjohnson Date 2019-12-23 Time 15:52 Rev Time 0.00
Received By gjohnson Date 2019-12-23 Time 13:16 Sent To  
Notes
2019-12-23 16:06:321ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE SANITARY RISER FOR THE NEW STACKABLE WASHER
 IT SHALL CONNECT TO BUILDING DRAIN DOWN STREAM OF THE
 BATHROOM GROUP. PER WPB AMEND TO FBC 107.2.1 AND FBC PL
 912.1
  
 2. THE SHUT OFF VALVE FOR THE STACKABLE WASHERS SHALL
 BE ACCESSIBLE WITHOUT MOVING THE APPLIANCES. PER FBC PL
 606.3
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-18 Cont ID  
Sent By jesmith Date 2019-04-18 Time 10:39 Rev Time 0.00
Received By jesmith Date 2019-04-18 Time 09:47 Sent To  
Notes
2019-04-18 10:39:48CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 WPB CCC = WEST PALM BEACH CROSS CONNECTION CONTROL
 MANUAL
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 1. PLUMBING REVIEW CONDUCTED IN ACCORDANCE WITH WPB FBC
 107.3.5.1.3
 2. PER WPB FBC 107.2.1, PROVIDE THE BUILDING
 CLASSIFICATION/OCCUPANCY AS PRESCRIBED IN FBC CHAPTER 3
 AND OCCUPANT LOAD CALCULATIONS IN ACCORDANCE WITH FBC
 1004 AND 1005.
 3. CONTINGENT UPON THE DETERMINATION OF THE BUILDING
 CLASSIFICATION/OCCUPANCY, CLOTHES WASHER FACILITIES
 WILL BE REQUIRED IN ACCORDANCE WITH FBC PL TABLE 403.1.
 4. PER WPB FBC 107.2.1, PROVIDE DEDICATED PLUMBING
 FLOOR PLAN NOTING A COMPLETE SCOPE OF WORK; INDICATE ON
 THE PLAN PLUMBING FIXTURES, WATER HEATERS AND
 APPLIANCES TO BE REPLACED. ADDITIONALLY, INDICATE ON
 THE PLANS TUB/SHOWER VALVE REPLACEMENT. PROVIDE NOTE ON
 THE PLAN CONFIRMING THAT ROUGH/TOP OUT WORK WILL BE
 LIMITED TO IN WALL REPLACEMENT OF TUB SHOWER VALVES AND
 PROVISION FOR WATER HAMMER ARRESTORS FOR CLOTHES
 WASHERS (SEE NOTE 2); IF THERE IS TO BE MORE EXTENSIVE
 ROUGH/TOP OUT WORK, THEN IT SHALL BE INDICATED ON THE
 PLANS. THE PLAN SHALL BE CLEAR AND LEGIBLE AND COMPLY
 WITH WPB FBC 107.2.1.3.
 5. THE PLAN SHALL BE STAMPED/SEALED AND SIGNED BY
 DESIGNER OF RECORD IN ACCORDANCE WITH FS 471 AND FAC
 61G15.
 6. PER WPB FBC 107.2.1, PROVIDE THE NOTE ?INDIVIDUAL
 SHOWER AND TUB-SHOWER COMBINATION VALVES SHALL BE
 BALANCED-PRESSURE, THERMOSTATIC OR COMBINATION
 BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO
 THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA
 B125.16 OR ASME A112.18.1/CSA B125.1 AND SHALL BE
 INSTALLED AT THE POINT OF USE PER FBC PL 424.3.?
 7. PROVIDE WATER HEATER SPEC WITH CAPACITY AND
 ELECTRICAL CHARACTERISTICS. ELECTRICAL CHARACTERISTICS
 SHALL MATCH ELECTRICAL PLANS.
 8. PER WPB FBC 107.2.1, PROVIDE THE NOTE ?WATER HEATER
 INSTALLATION SHALL COMPLY WITH FBC PL CHAPTER 5 AND FBC
 PL 607.3.?
 9. PER WPB FBC 107.2.1, PROVIDE THE NOTE ?A
 WATER-HAMMER ARRESTOR SHALL BE INSTALLED WHERE
 QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER
 ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S INSTRUCTIONS. WATER-HAMMER ARRESTORS
 SHALL CONFORM TO ASSE 1010 PER BY FBC PL 604.9.?
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-02-22 Cont ID  
Sent By ccole Date 2021-02-22 Time 08:03 Rev Time 0.00
Received By ccole Date 2021-02-22 Time 07:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-02-02 Cont ID  
Sent By jwitmer Date 2021-02-02 Time 14:39 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-08-05 Cont ID  
Sent By jgomez Date 2020-08-05 Time 17:45 Rev Time 0.00
Received By jgomez Date 2020-08-05 Time 17:43 Sent To  
Notes
2020-08-05 17:46:23CONVERTED TO DIGITAL.
 ARCHITECT'S DRAWINGS WITH ORIGINAL SEAL AND SIGNATURE
 SENT TO TEMP. STORAGE (PENDING LAST REVIEW). JG.
  