Plan Review Details - Permit 19040046
Plan Review Stops For Permit 19040046
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-04-08 Cont ID  
Sent By pvalenti Date 2019-04-08 Time 08:57 Rev Time 0.00
Received By pvalenti Date 2019-04-08 Time 08:57 Sent To  
Notes
2019-04-08 09:11:54PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 APPROVED WITH PROVISO:
  
 AT TIME OF INSPECTION, HAVE ON-SITE THE ENGINEER'S
 SIGNED AND SEALED DETAIL FOR CONCRETE SLAB INCLUDING
 THE WIND LOAD RESISTANCE ANCHORING SPECIFICATIONS FOR
 THE GENERATOR TO SLAB CONNECTIONS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-04-15 Cont ID  
Sent By jleahy Date 2019-04-15 Time 13:32 Rev Time 0.00
Received By jleahy Date 2019-04-15 Time 13:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-09 Cont ID  
Sent By jleahy Date 2019-04-09 Time 16:30 Rev Time 0.00
Received By jleahy Date 2019-04-09 Time 16:30 Sent To  
Notes
2019-04-09 16:32:51FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 THERE ARE TWO DIFFERENT PERMIT TYPES HER GENERATOR
 (FUTURE) POOL
  
 EACH SHOULD BE A SUB-PERMIT FOR THE MAIN PERMIT POOL
 ELECTRIC FOR POOL PERMIT.
  
 PLEASE SUBMIT SEPARATE PERMITS FOR THE WORK INVOLVED.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-09 Cont ID  
Sent By jleahy Date 2019-04-09 Time 16:32 Rev Time 0.00
Received By jleahy Date 2019-04-01 Time 09:30 Sent To  
Notes
2019-04-03 09:30:49ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2019-04-04 Cont ID  
Sent By mcruz Date 2019-04-04 Time 09:16 Rev Time 0.00
Received By mcruz Date 2019-04-04 Time 09:03 Sent To B
Notes
2019-04-04 09:16:39FYI - FUTURE GENERATOR SHALL BE AT LEAST 3.5 FEET FROM
 SIDE PROPERTY LINE.