Plan Review Details - Permit 19031336
Plan Review Stops For Permit 19031336
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-04-30 Cont ID  
Sent By jduprey Date 2019-04-30 Time 08:47 Rev Time 0.00
Received By jduprey Date 2019-04-30 Time 08:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-04-26 Cont ID  
Sent By jleahy Date 2019-04-26 Time 07:34 Rev Time 0.00
Received By jleahy Date 2019-04-26 Time 07:34 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-05-20 Cont ID  
Sent By thunt Date 2019-05-20 Time 09:35 Rev Time 0.00
Received By thunt Date 2019-05-20 Time 09:35 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-04-04 Cont ID  
Sent By thunt Date 2019-04-04 Time 14:02 Rev Time 0.00
Received By thunt Date 2019-04-04 Time 14:02 Sent To  
Notes
2019-04-04 14:02:22GAS 1ST REVIEW**DENIED**
  
 CITY RECORDS (PERMIT # 04010702) SHOWS A EXISTING GAS
 SYSTEM @ 12" W.C
  
 1)THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.
  
 2) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
  
 3) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES.
 SEC. G 2413.4.1, G2413.4.2.
  
 4) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC.
 G2413.4.1, G2413.4.2
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-20 Cont ID  
Sent By thunt Date 2019-05-20 Time 09:35 Rev Time 0.00
Received By thunt Date 2019-05-16 Time 10:59 Sent To  
Notes
2019-05-17 10:59:56RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-30 Cont ID  
Sent By jduprey Date 2019-04-30 Time 08:47 Rev Time 0.00
Received By jduprey Date 2019-03-28 Time 11:37 Sent To  
Notes
2019-03-29 11:38:05ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2019-04-03 Cont ID  
Sent By mcruz Date 2019-04-03 Time 13:03 Rev Time 0.00
Received By mcruz Date 2019-04-03 Time 13:01 Sent To  
Notes
***NONE***