2019-06-05 15:07:31 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. FBC R 301, PROVIDE A STRUCTURAL DETAIL FOR THE | | GENERATOR PAD, ANCHORING, INCLUDING WIND DESIGN | | CRITERIA. IF USING AN EXISTING PAD, PROVIDE THE PERMIT | | NUMBER AND SLAB DETAIL. ANCHORING SPECIFICATION, | | INCLUDING WIND DESIGN CRITERIA, IS STILL REQUIRED, | | ALONG WITH EVIDENCE THAT THE "EXISTING PAD" CAN SUPPORT | | THE WEIGHT OF THE GENERATOR. | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2019-04-25 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2019-04-25 |
Time |
13:40 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2019-04-25 |
Time |
13:40 |
Sent To |
|
|
Notes |
2019-04-25 13:41:05 | VALUE TO LOW |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2019-05-03 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2019-05-03 |
Time |
16:58 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2019-05-03 |
Time |
16:58 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2019-04-25 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2019-04-25 |
Time |
13:39 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2019-04-25 |
Time |
13:39 |
Sent To |
|
|
Notes |
2019-04-25 13:40:24 | VALUE FOR TO BE SHOWN AS A COMPLETE INSTALL |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
P |
Date |
2019-08-02 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-08-02 |
Time |
13:35 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-08-02 |
Time |
12:57 |
Sent To |
|
|
Notes |
2019-08-02 13:23:23 | 1) THERE ARE TWO GAS DRAWINGS IN THIS SUBMITTAL. ONE | | SHOWS A 15 KW GENERATOR AND THE OTHER SHOWS A 22 KW | | GENERATOR. WHAT ARE YOU INSTALLING? YOU SHOW RWO | | DIFFERENT GENERATORS WITH THE SAME BTU LOAD OF 281,000 | | WHICH DOES NOT THE MATCH THE BTU LOAD IN THE | | MANUFACTURER'S INSTALLATION MANUAL. SUBMIT TWO COPIES | | OF A GAS DRAWING THE CORRECT SIZE GENERATOR AND BTU | | LOAD. WPB AMEND. TO FBC SEC. 107.2.1. | | 2) A UNION IS REQD. WITHIN ONE FOOT UPSTREAM OR | | DOWNSTREAM OF EACH REGULATOR. SHOW THIS ON THE PLAN. | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2019-05-07 |
|
|
Cont ID |
|
Sent By |
thunt |
Date |
2019-05-07 |
Time |
10:49 |
Rev Time |
0.00 |
Received By |
thunt |
Date |
2019-05-07 |
Time |
10:49 |
Sent To |
|
|
Notes |
2019-05-07 10:52:06 | GAS 2ND REVIEW**DENIED** I WOULD RECOMMEND COMMING IN | | FOR A REVIEW BEFORE RESUBMITTING. | | | | PLAN'S SUBMITTED ARE SO DEFICIENT A THOROUGH PLAN | | REVIEW COULD NOT BE PERFORMED AT THIS TIME. THE SURVEY | | AND ELC PLAN CALLS FOR A 15KW GENERATOR. INSTALLATION | | MANUAL PROVIDE LIST 6KW, 12KW, 13KW FOR NAT GAS. BOTH | | GAS RISERS CALL OUT 22KW. EACH OF THE GAS RISERS CALL | | OUT DIFFERENT BTU'S OF THE NEW GENERATOR. NO | | INSTALLATION MANUAL FOR A 22KW WAS PROVIDED | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | | | TIM HUNT | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | BUILDING DIVISION | | CITY OF WEST PALM BEACH | | 401 CLEMATIS STREET, 1ST FLOOR | | WEST PALM BEACH, FL 33401 | | 561-248-2703 | | [email protected] | | [email protected] | | | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2019-04-04 |
|
|
Cont ID |
|
Sent By |
thunt |
Date |
2019-04-04 |
Time |
12:11 |
Rev Time |
0.00 |
Received By |
thunt |
Date |
2019-04-04 |
Time |
12:11 |
Sent To |
|
|
Notes |
2019-04-04 12:11:26 | GAS 1ST REVIEW**DENIED** | | | | 1) THE EXISITING GENERATOR AND SLAB WERE NEVER | | PERMITTED. A STOP WORK ORDER WAS ISSUED ON OR ABOUT THE | | 01/17/2019. THE VALUE OF THIS JOB MUST BE AS IF IT WAS | | A NEW INSTALL AND NOT THE CLAIMED VALUE YOU LISTED AS | | $1315.00. W.P.B AMEND FBC 109.3. A COMPLETE SET OF | | PLANS WILL BE REQUIRED. | | | | 2) YOUR NEW BTU LOAD IS LISTED AS 220,00 BUT UNDER THE | | THE GENERATOR DETAIL ON THE SAME SHEET YOU HAQVE LIST | | THE BTU AS 281,000. PLEASE CLARIFY. FBC 107.3.5 | | | | | | TIM HUNT | | PLUMBING PLANS EXAMINER | | BUILDING DIVISION | | CITY OF WEST PALM BEACH | | 401 CLEMATIS STREET, 1ST FLOOR | | WEST PALM BEACH, FL 33401 | | 561-248-2703 | | [email protected] | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2019-08-14 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-08-14 |
Time |
16:02 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2019-07-23 |
Time |
13:48 |
Sent To |
|
|
Notes |
2019-07-24 13:48:46 | RESUB ROUTED TO TKLARGE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2019-06-05 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2019-06-05 |
Time |
15:07 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2019-05-01 |
Time |
11:50 |
Sent To |
|
|
Notes |
2019-05-02 11:50:54 | RESUB ROUTED TO JLEAHY |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2019-04-25 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2019-04-25 |
Time |
13:41 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2019-03-28 |
Time |
12:37 |
Sent To |
|
|
Notes |
2019-03-29 12:37:17 | ROUTED TO ZONING INBOX |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2019-04-03 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2019-04-03 |
Time |
16:53 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2019-04-03 |
Time |
16:49 |
Sent To |
|
|
Notes |
|
|