Plan Review Details - Permit 19031322
Plan Review Stops For Permit 19031322
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-08-14 Cont ID  
Sent By pvalenti Date 2019-08-14 Time 16:02 Rev Time 0.00
Received By pvalenti Date 2019-08-14 Time 16:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-06-05 Cont ID  
Sent By shill Date 2019-06-05 Time 15:06 Rev Time 0.00
Received By shill Date 2019-06-05 Time 15:06 Sent To  
Notes
2019-06-05 15:07:31****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC R 301, PROVIDE A STRUCTURAL DETAIL FOR THE
 GENERATOR PAD, ANCHORING, INCLUDING WIND DESIGN
 CRITERIA. IF USING AN EXISTING PAD, PROVIDE THE PERMIT
 NUMBER AND SLAB DETAIL. ANCHORING SPECIFICATION,
 INCLUDING WIND DESIGN CRITERIA, IS STILL REQUIRED,
 ALONG WITH EVIDENCE THAT THE "EXISTING PAD" CAN SUPPORT
 THE WEIGHT OF THE GENERATOR.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-25 Cont ID  
Sent By jleahy Date 2019-04-25 Time 13:40 Rev Time 0.00
Received By jleahy Date 2019-04-25 Time 13:40 Sent To  
Notes
2019-04-25 13:41:05VALUE TO LOW

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-05-03 Cont ID  
Sent By jleahy Date 2019-05-03 Time 16:58 Rev Time 0.00
Received By jleahy Date 2019-05-03 Time 16:58 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-25 Cont ID  
Sent By jleahy Date 2019-04-25 Time 13:39 Rev Time 0.00
Received By jleahy Date 2019-04-25 Time 13:39 Sent To  
Notes
2019-04-25 13:40:24VALUE FOR TO BE SHOWN AS A COMPLETE INSTALL

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2019-08-02 Cont ID  
Sent By tklarge Date 2019-08-02 Time 13:35 Rev Time 0.00
Received By tklarge Date 2019-08-02 Time 12:57 Sent To  
Notes
2019-08-02 13:23:231) THERE ARE TWO GAS DRAWINGS IN THIS SUBMITTAL. ONE
 SHOWS A 15 KW GENERATOR AND THE OTHER SHOWS A 22 KW
 GENERATOR. WHAT ARE YOU INSTALLING? YOU SHOW RWO
 DIFFERENT GENERATORS WITH THE SAME BTU LOAD OF 281,000
 WHICH DOES NOT THE MATCH THE BTU LOAD IN THE
 MANUFACTURER'S INSTALLATION MANUAL. SUBMIT TWO COPIES
 OF A GAS DRAWING THE CORRECT SIZE GENERATOR AND BTU
 LOAD. WPB AMEND. TO FBC SEC. 107.2.1.
 2) A UNION IS REQD. WITHIN ONE FOOT UPSTREAM OR
 DOWNSTREAM OF EACH REGULATOR. SHOW THIS ON THE PLAN.
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-05-07 Cont ID  
Sent By thunt Date 2019-05-07 Time 10:49 Rev Time 0.00
Received By thunt Date 2019-05-07 Time 10:49 Sent To  
Notes
2019-05-07 10:52:06GAS 2ND REVIEW**DENIED** I WOULD RECOMMEND COMMING IN
 FOR A REVIEW BEFORE RESUBMITTING.
  
 PLAN'S SUBMITTED ARE SO DEFICIENT A THOROUGH PLAN
 REVIEW COULD NOT BE PERFORMED AT THIS TIME. THE SURVEY
 AND ELC PLAN CALLS FOR A 15KW GENERATOR. INSTALLATION
 MANUAL PROVIDE LIST 6KW, 12KW, 13KW FOR NAT GAS. BOTH
 GAS RISERS CALL OUT 22KW. EACH OF THE GAS RISERS CALL
 OUT DIFFERENT BTU'S OF THE NEW GENERATOR. NO
 INSTALLATION MANUAL FOR A 22KW WAS PROVIDED
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-04-04 Cont ID  
Sent By thunt Date 2019-04-04 Time 12:11 Rev Time 0.00
Received By thunt Date 2019-04-04 Time 12:11 Sent To  
Notes
2019-04-04 12:11:26GAS 1ST REVIEW**DENIED**
  
 1) THE EXISITING GENERATOR AND SLAB WERE NEVER
 PERMITTED. A STOP WORK ORDER WAS ISSUED ON OR ABOUT THE
 01/17/2019. THE VALUE OF THIS JOB MUST BE AS IF IT WAS
 A NEW INSTALL AND NOT THE CLAIMED VALUE YOU LISTED AS
 $1315.00. W.P.B AMEND FBC 109.3. A COMPLETE SET OF
 PLANS WILL BE REQUIRED.
  
 2) YOUR NEW BTU LOAD IS LISTED AS 220,00 BUT UNDER THE
 THE GENERATOR DETAIL ON THE SAME SHEET YOU HAQVE LIST
 THE BTU AS 281,000. PLEASE CLARIFY. FBC 107.3.5
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 561-248-2703
 [email protected]
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-08-14 Cont ID  
Sent By pvalenti Date 2019-08-14 Time 16:02 Rev Time 0.00
Received By pvalenti Date 2019-07-23 Time 13:48 Sent To  
Notes
2019-07-24 13:48:46RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-05 Cont ID  
Sent By shill Date 2019-06-05 Time 15:07 Rev Time 0.00
Received By shill Date 2019-05-01 Time 11:50 Sent To  
Notes
2019-05-02 11:50:54RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-25 Cont ID  
Sent By jleahy Date 2019-04-25 Time 13:41 Rev Time 0.00
Received By jleahy Date 2019-03-28 Time 12:37 Sent To  
Notes
2019-03-29 12:37:17ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2019-04-03 Cont ID  
Sent By mcruz Date 2019-04-03 Time 16:53 Rev Time 0.00
Received By mcruz Date 2019-04-03 Time 16:49 Sent To  
Notes
***NONE***