Plan Review Stops For Permit 19031300 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2019-05-09 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-05-09 |
Time |
09:53 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2019-05-09 |
Time |
09:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2019-05-01 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-05-01 |
Time |
07:23 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2019-05-01 |
Time |
07:10 |
Sent To |
|
|
Notes |
2019-05-01 07:36:30 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561?805?6673 | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 2ND BUILDING PLAN REVIEW DENIED: | | | | AS STATED ON LAST BUILDING REVIEW, | | | | THE PERMIT APPLIED FOR IS FOR AN INTERIOR DEMO. ONLY. | | IN ADDITION TO THE INTERIOR DEMOLITION OF AREA | | IDENTIFIED ON APPLICATION, THE PLANS INCLUDE DEMOLITION | | AND REMODELING OF STRUCTURAL ELEMENTS. THE STRUCTURAL | | WORK SHOULD NOT BE ON THIS PLAN AS APPLIED FOR. | | | | PLEASE EITHER: | | | | 1. ADJUST THE DESCRIPTION OF WORK, ADD SPECIAL | | INSPECTOR AGREEMENT/SPECIAL INSPECTION PLAN, AND ADJUST | | THE VALUATION/PROVIDE VALUATION BREAK DOWN TO INCLUDE | | STRUCTURAL WORK. | | | | OR | | | | 2. REMOVE STRUCTURAL WORK FROM PLAN AND APPLY FOR | | SEPERATE COMMERCIAL PERMIT FOR STRUCTURAL WORK. | | | | THE COMMENT RESPONSE STATES THAT OPTION #1 HAS BEEN | | SELECTED. | | | | PLEASE ADJUST THE VALUATION OF PERMIT INCLUDING THE | | STRUCTURAL BREAK DOWN, SUBMIT THE REVISED PLANS WITH | | THE THE SPECIAL INSPECTOR PLAN INCLUDED, AND SUBMIT THE | | SPECIAL INSPECTOR AGREEMENT. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2019-04-04 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-04-04 |
Time |
10:01 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2019-04-04 |
Time |
10:01 |
Sent To |
|
|
Notes |
2019-04-04 10:59:39 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | BUILDING PLAN REVIEW DENIED: | | | | THE PERMIT APPLIED FOR IS FOR AN INTERIOR DEMO. ONLY. | | IN ADDITION TO THE INTERIOR DEMOLITION OF AREA | | IDENTIFIED ON APPLICATION, THE PLANS INCLUDE DEMOLITION | | AND REMODELING OF STRUCTURAL ELEMENTS. THE STRUCTURAL | | WORK SHOULD NOT BE ON THIS PLAN AS APPLIED FOR. | | | | PLEASE EITHER: | | 1. ADJUST THE DESCRIPTION OF WORK, ADD SPECIAL | | INSPECTOR AGREEMENT/SPECIAL INSPECTION PLAN, AND ADJUST | | THE VALUATION/PROVIDE VALUATION BREAK DOWN TO INCLUDE | | STRUCTURAL WORK. | | OR | | 2. REMOVE STRUCTURAL WORK FROM PLAN AND APPLY FOR | | SEPERATE COMMERCIAL PERMIT FOR STRUCTURAL WORK. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2019-05-09 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2019-05-09 |
Time |
10:04 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2019-05-09 |
Time |
10:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2019-05-01 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2019-05-01 |
Time |
08:36 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2019-05-01 |
Time |
08:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2019-04-16 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2019-04-16 |
Time |
15:17 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2019-04-16 |
Time |
15:17 |
Sent To |
|
|
Notes |
2019-04-16 15:18:35 | NEED AN ELECTRICAL PERMIT JLEAHY |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2019-04-29 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2019-04-29 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2019-04-29 |
Time |
14:32 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2019-04-08 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2019-04-08 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2019-04-08 |
Time |
15:12 |
Sent To |
E |
|
Notes |
2019-04-08 15:26:10 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS NO INDICATION OF THE SCOPE OF WORK. | | | | IS IT THE INTENT TO RETURN THIS SPACE INTO AN OPEN | | SPACE FOR FUTURE BUILDOUT? | | | | PLEASE PROVIDE A DETAILED SCOPE OF WORK. | | | | | | | | 2) SHEET A 2 - THERE ARE INDICATION OF REMOVING WALLS | | IN AN ADJACENT SPACE WHICH ON SHEET A 2 IS SHADED/NOT | | INCLUDED IN THIS PROJECT. | | | | PLEASE REVIEW AND CLARIFY/JUSTIFY. | | | | | | | | 3) THERE IS NO INDCATION OF FIRE ALARM DEMO/WORK. | | | | THE FIRE ALARM SYSTEM SHALL BE MAINTAINED THROUGHOUT | | CONSTRUCTION. | | | | ANY WORK, DEMO/INSTALL, OF ANY FIRE ALARM | | DEVICE/EQUIPMENT SHALL BE DONE UNDER SEPARATE PERMIT | | AND SHOP DRAWINGS. | | | | PLEASE PROVIDE AN APPLICABLE NOTE. | | | | | | | | 3) THERE IS INDICATIONS OF FIRE SPRINKLER WORK UNDER | | SEPARATE SHOP DRAWINGS. | | | | THE FIRE SPRINKLER SYSTEM SHALL BE FUNCTIONAL AND | | MAINTAINED THROUGHTOUT THE DEMO AND CONSTRUCTION | | PERIODS. | | | | PLEASE PROVIDE AN APPLICABLE NOTE. | | | | | | | | 5) SHEET S 1 - THERE IS NOT A CLEAR INDICATION THAT THE | | STAIRS ARE BEING REMOVED. IT APPEARS AS THOUGH THE | | STAIRS REMAIN IN THE NEW FLOOR FRAMING LAYOUT. | | | | IS IT THE INTENT TO REMOVE THE EXISTING STAIRS? | | | | PLEASE REVIEW AND REMOVE THE STAIR STEPS/TREADS ON ANY | | NEW LAYOUTS. | | | | | | | | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | | | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2019-05-09 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2019-05-09 |
Time |
10:05 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2019-05-07 |
Time |
09:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2019-05-01 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2019-05-01 |
Time |
10:00 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2019-04-25 |
Time |
15:49 |
Sent To |
|
|
Notes |
2019-04-26 15:49:20 | RESUB ROUTED TO FIRE INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2019-04-16 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2019-04-16 |
Time |
15:19 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2019-03-28 |
Time |
12:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
Rev No |
1 |
Status |
N |
Date |
2019-04-04 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-04-04 |
Time |
10:01 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2019-04-04 |
Time |
10:01 |
Sent To |
|
|
Notes |
|
|