Plan Review Details - Permit 19031212
Plan Review Stops For Permit 19031212
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-06-04 Cont ID  
Sent By pvalenti Date 2019-06-04 Time 10:35 Rev Time 0.00
Received By pvalenti Date 2019-06-04 Time 10:35 Sent To  
Notes
2019-06-04 10:37:04PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 APPROVED WITH PROVISO:
  
 AWS D1.1 CLAUSE 3.1: AT TIME OF INSPECTION PLEASE
 PROVIDE A WELD PROCEDURE SPECIFICATION; THE W.P.S.
 SPECIFIES THE REQUIRED ESSENTIAL VARIABLES INCLUDING:
 BASE MATERIALS, JOINTS, PROCESS, AND FILLER METALS TO
 BE USED.
 AWS D1.1 CLAUSE 4.15: AT TIME OF INSPECTION PLEASE
 PROVIDE A WELDER PERFORMANCE QUALIFICATION RECORD; THE
 W.P.Q.R. PROVIDES INFORMATION WHICH CAN BE USED TO
 VERIFY THE WELDER?S QUALIFICATION AND CERTIFICATION AS
 IT RELATES TO THE WELDING REQUIREMENTS OF THE PROJECT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-04-07 Cont ID  
Sent By pvalenti Date 2019-04-07 Time 12:34 Rev Time 0.00
Received By pvalenti Date 2019-04-07 Time 12:34 Sent To  
Notes
2019-04-07 12:38:25PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 APPROVED WITH PROVISO:
  
 PROVIDE WELD PROCEDURE SPECIFICATIONS AND QUALIFICATION
 OF WELDING PERSONNEL AT TIME OF INSPECTION.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-07-17 Cont ID  
Sent By jleahy Date 2019-07-17 Time 14:12 Rev Time 0.00
Received By jleahy Date 2019-07-17 Time 14:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-07-15 Cont ID  
Sent By jleahy Date 2019-07-15 Time 12:44 Rev Time 0.00
Received By jleahy Date 2019-07-15 Time 12:44 Sent To  
Notes
2019-07-15 12:51:37FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 COMMENTS #3 AND 4 NOT ADDRESSED FROM SECOND REVIEW.
  
 ADDITIONAL COMMENT
  
 $25,000 CONTRACT VALUE IS FOR PURCHASE OF SIGNS AND NOT
 THE INSTALLATION OF ALL THESE SIGNS, PLEASE INCLUDE
 YOUR LABOR TO INSTALL.
  
 SUBMIT A CONTRACT FOR THE INSTALLATION AND PURCHASE OF
 SIGNS.
  
 PLEASE INDICATE WHICH SIGN THE VALUES ARE SHOWN FOR.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS. FINAL
 BUILDING PERMIT VALUATION SHALL BE SET BY THE BUILDING
 OFFICIAL.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-06-04 Cont ID  
Sent By fgiaquin Date 2019-06-04 Time 06:36 Rev Time 0.00
Received By fgiaquin Date 2019-06-04 Time 05:52 Sent To B
Notes
2019-06-04 06:36:03ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NOTE ON MONUMENT SIGN PLAN QUOTING "600.6A1 EX #2"
 THERE IS NO EXCEPTION #2 TO 600.6A1 AND EXCEPTION #1
 DOESN'T APPLY TO THIS APPLICATION.
  
 2. DISCONNECT FOR MONUMENT SIGN SHOWN ON PLAN DOES NOT
 MEET THE REQUIREMENTS OF 600.6A1. DISCONNECT MUST
 DISCONNECT ALL BRANCH CIRCUITS CONDUCTORS AT THE POINT
 THEY ENTER THE SIGN. WHEN DISCONNECT IS OPEN ALL 120V
 CONDUCTORS IN SIGN MUST BE DISCONNECTED. PLEASE COMPLY.
 NEC 600.6A1
  
 3. DISCONNECT ON SHEET #3 OF PLAN DOES NOT COMPLY WITH
 600.6A1. PLEASE PROVIDE CORRECTION.
  
 4. DISCONNECT ON SHEET #15 OF PLAN DOES NOT COMPLY WITH
 600.6A1. PLEASE PROVIDE CORRECTION.
  
 5. DISCONNECT ON SHEET # 17 OF PLAN DOES NOT COMPLY
 WITH 600.6A1. PLEASE PROVIDE CORRECTION.
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-19 Cont ID  
Sent By fgiaquin Date 2019-04-19 Time 06:39 Rev Time 0.00
Received By fgiaquin Date 2019-04-19 Time 06:04 Sent To I
Notes
2019-04-19 06:39:12ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. EXTERNAL 120V DISCONNECT REQUIRED FOR ALL SIGNS
 (WALL AND MONUMENT) MUST CONFORM WITH THE REQUIREMENTS
 OF 600.6A1 NEC. DISCONNECT MUST BE WITHIN SIGHT OF SIGN
 AND SHUT DOWN BRANCH CIRCUIT CONDUCTORS FEEDING SIGN.
 PROVIDE CORRECTIONS
  
 2. PROVIDE NOTE ON PLAN FOR STATING ALL EXTERNAL SIGNS
 WILL BE CONTROLLED BY AN ASTRONOMICAL TIME CLOCK/W
 BATTERY BACKUP OR BUILDING MANAGMENT SYSTEM TO CONFORM
 WITH ENERGY CONSERVATION EXTERNAL LIGHTING REQUIREMENTS
 OF FBC EC 405.2.4
  
 3. NO WIRING DIAGRAM PROVIDED FOR MONUMENT SIGN.
 PROVIDE ELECTRICAL PLAN FOR MONUMENT SIGN. SHOW
 EXTERNAL DISCONNECT REQUIRED BY 600.6A1 AS DESCRIBED IN
 PLAN REVIEW COMMENT #1.
  
 4. NO WIRING DIAGRAM PROVIDED FOR "ATM" SIGNS. PROVIDE
 ELECTRICAL PLAN FOR "ATM" SIGNS. SHOW EXTERNAL
 DISCONNECT REQUIRED BY 600.6A1 AS DESCRIBED IN PLAN
 REVIEW COMMENT #1.
  
 5. VALUE SEEMS LOW FOR AMOUNT OF WORK SHOWN. PROVIDE
 CONTRACT INCLUDING ALL MATIERALS AND LABOR. SIGNED BY
 BOTH CONTRACTOR AND OWNER.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-04 Cont ID  
Sent By pvalenti Date 2019-06-04 Time 10:37 Rev Time 0.00
Received By pvalenti Date 2019-05-21 Time 13:11 Sent To  
Notes
2019-05-22 13:12:05RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-19 Cont ID  
Sent By fgiaquin Date 2019-04-19 Time 06:39 Rev Time 0.00
Received By fgiaquin Date 2019-03-26 Time 15:25 Sent To  
Notes
2019-03-27 15:25:46ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2019-05-31 Time   Rev Time 0.00
Received By pgreilic Date 2019-05-31 Time 14:11 Sent To E
Notes
2019-05-31 14:12:06PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2019-04-05 Time   Rev Time 0.00
Received By pgreilic Date 2019-04-05 Time 15:53 Sent To B
Notes
2019-04-05 15:54:31LABEL SETBACKS FOR ALL PROPOSED MONUMENT, DIRECTIONAL
 SIGNAGE
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]