Plan Review Details - Permit 19031191
Plan Review Stops For Permit 19031191
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-04-10 Cont ID  
Sent By dbattles Date 2019-04-10 Time 13:19 Rev Time 0.00
Received By dbattles Date 2019-04-09 Time 10:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-04-17 Cont ID  
Sent By jpearson Date 2019-04-17 Time 15:47 Rev Time 0.00
Received By jpearson Date 2019-04-17 Time 15:47 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-10 Cont ID  
Sent By jpearson Date 2019-04-10 Time 08:00 Rev Time 0.00
Received By jpearson Date 2019-04-10 Time 07:59 Sent To  
Notes
2019-04-10 07:59:55CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO REVISIONS SHOWN ON PLAN. CLOUD REVISIONS AND
 PROVIDE DESCRIPTION. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-04-11 Cont ID  
Sent By pleduc Date 2019-04-11 Time   Rev Time 0.00
Received By pleduc Date 2019-04-11 Time 15:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2019-03-28 Cont ID  
Sent By pleduc Date 2019-03-28 Time   Rev Time 0.00
Received By pleduc Date 2019-03-28 Time 13:23 Sent To  
Notes
2019-03-28 13:35:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A 1.2 - THERE IS AN INDICATION OF A "NEW
 SHAFT".
  
 WHAT IS THE PURPOSE OF THIS NEW SHAFT?
  
 HOW MANY FLOORS DOES IT CONNECT?
  
 PLEASE PROVIDE DETAILS
  
  
  
 3) SHEET A 2.2 - THE DOOR TO THE SHAFT IS INDICATED HAS
 HAVING A B RATING. THERE IS NO DEFINITION OF WHAT B IS.
  
 PLEASE PROVIDE DETAILS/DEFINITION.
  
  
  
  
 4) SHEET A 2.2 - THERE IS NO INDICATION OF THE WIDTH
 DIMENSION BETWEEN THE CORNER OF THE NEW SHAFT WALL AND
 THE EXISTING WALL.
  
 THIS DIMENSION IS REQUIREDTO MEET OR EXCEED THE
 REQUIREMENT FOR EXITING PER NFPA 101, CH 7, MEANS OF
 EGRESS.
  
 PLEASE PROVIDE THE DIMENSION AND CORRECT IR APPLICABLE.
  
  
  
  
 5) SHEET FP - FIRE SPRINKLER PLANS ARE INDICATED. THESE
 PLANS ARE NOLY REVIEWED FOR INFORMATIONAL PURPOSES.
  
 REVISED FIRE SPRINKLED SHOP DRAWING ARE REQUIRED UNDER
 SEPARATE REVISED PERMIT.
  
 PROVIDE A NOTE OF ACKNOWLEDGEMENT.
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-04-18 Cont ID  
Sent By gjohnson Date 2019-04-18 Time 08:01 Rev Time 0.00
Received By gjohnson Date 2019-04-18 Time 08:01 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-04-10 Cont ID  
Sent By gjohnson Date 2019-04-10 Time 10:10 Rev Time 0.00
Received By gjohnson Date 2019-04-10 Time 10:10 Sent To  
Notes
2019-04-10 10:10:321ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS:
  
 1. PROVIDE DETAIL OF HOW THE END OF THE PIPING WILL BE
 SECURED SO THAT GAS WILL NOT BE RELEASED INTO SPACE IF
 SOME ONE ENERGIZES THE 2" LINE A LOCKING VALVE AND CAP
 IS REQUIRED. PER WPB AMEND TO FBC 107.2.1 AND FBC FG
 404.15
 2. PLACE NOTE ON PLAN . CITY OF WEST PALM BEACH PIPING
 AFFIDAVIT OR MANOMETER TEST DOCUMENT REQUIRED AT
 JOBSITE FOR FINAL INSPECTION. PER WPB AMEND TO FBC
 107.2.1
 3. PLACE NOTE ON THE PLAN THAT PIPING IS FOR FUTURE USE
 NO APPLIANCES TO BE CONNECTED WITH OUT SEPARATE
 PERMIT.. PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-18 Cont ID  
Sent By gjohnson Date 2019-04-18 Time 08:01 Rev Time 0.00
Received By gjohnson Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2019-04-12 Time   Rev Time 0.00
Received By lmarchan Date 2019-03-26 Time 16:10 Sent To  
Notes
2019-03-27 16:11:07C08

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2019-04-12 Cont ID  
Sent By ccole Date 2019-04-12 Time 07:56 Rev Time 0.00
Received By ccole Date 2019-04-11 Time 17:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-04-18 Cont ID  
Sent By gjohnson Date 2019-04-18 Time 08:01 Rev Time 0.00
Received By gjohnson Date 2019-04-18 Time 08:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-10 Cont ID  
Sent By gjohnson Date 2019-04-10 Time 09:52 Rev Time 0.00
Received By gjohnson Date 2019-04-10 Time 09:12 Sent To  
Notes
2019-04-10 10:09:431ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS:
  
 1. PROVIDE DETAIL OF HOW THE END OF THE PIPING WILL BE
 SECURED SO THAT GAS WILL NOT BE RELEASED INTO SPACE IF
 SOME ONE ENERGIZES THE 2" LINE A LOCKING VALVE AND CAP
 IS REQUIRED. PER WPB AMEND TO FBC 107.2.1 AND FBC FG
 404.15
 2. PLACE NOTE ON PLAN . CITY OF WEST PALM BEACH PIPING
 AFFIDAVIT OR MANOMETER TEST DOCUMENT REQUIRED AT
 JOBSITE FOR FINAL INSPECTION. PER WPB AMEND TO FBC
 107.2.1
 3. PLACE NOTE ON THE PLAN THAT PIPING IS FOR FUTURE USE
 NO APPLIANCES TO BE CONNECTED WITH OUT SEPARATE
 PERMIT.. PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2019-04-09 Cont ID  
Sent By eschneid Date 2019-04-09 Time 14:17 Rev Time 0.50
Received By eschneid Date 2019-04-09 Time 13:09 Sent To  
Notes
***NONE***