Plan Review Details - Permit 19031173
Plan Review Stops For Permit 19031173
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-06-12 Cont ID  
Sent By dbattles Date 2019-06-12 Time 10:58 Rev Time 0.00
Received By dbattles Date 2019-06-12 Time 10:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-30 Cont ID  
Sent By dbattles Date 2019-04-30 Time 07:53 Rev Time 0.00
Received By dbattles Date 2019-04-29 Time 09:37 Sent To  
Notes
2019-04-30 07:54:33****CORRECTIONS****
 W.P.B. PERMIT: 19031173
 REVIEWED: APRIL 29, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) 107.5.3 FBC[AMENDED] UPDATE CODE EDITION TO STATE
 CURRENT VERSION. 2017 FBC 6 TH EDITION.
  
 2) R314.2 FBC[R] WHERE REQUIRED. SMOKE ALARMS SHALL BE
 PROVIDED IN ACCORDANCE WITH THIS SECTION.
 R314.2.2 FBC[R] ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. EXCEPTIONS:
  
 A. IN EACH SLEEPING ROOM.
 B.OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
 C. SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 FEET
 (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF A
 BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS THIS
 WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED BY
 SECTION R314.3.
  
 R314.4 FBC[R] INTERCONNECTION. WHERE MORE THAN ONE
 SMOKE ALARM IS REQUIRED TO BE INSTALLED WITHIN AN
 INDIVIDUAL DWELLING UNIT IN ACCORDANCE WITH SECTION
 R314.3, THE ALARM DEVICES SHALL BE INTERCONNECTED IN
 SUCH A MANNER THAT THE ACTUATION OF ONE ALARM WILL
 ACTIVATE ALL OF THE ALARMS IN THE INDIVIDUAL DWELLING
 UNIT. PHYSICAL INTERCONNECTION OF SMOKE ALARMS SHALL
 NOT BE REQUIRED WHERE LISTED WIRELESS ALARMS ARE
 INSTALLED AND ALL ALARMS SOUND UPON ACTIVATION OF ONE
 ALARM. EXCEPTION: INTERCONNECTION OF SMOKE ALARMS IN
 EXISTING AREAS SHALL NOT BE REQUIRED WHERE ALTERATIONS
 OR REPAIRS DO NOT RESULT IN REMOVAL OF INTERIOR WALL OR
 CEILING FINISHES EXPOSING THE STRUCTURE, UNLESS THERE
 IS AN ATTIC, CRAWL SPACE OR BASEMENT AVAILABLE THAT
 COULD PROVIDE ACCESS FOR INTERCONNECTION WITHOUT THE
 REMOVAL OF INTERIOR FINISHES.
 -
  
 ONE-FAMILY AND TWO-FAMILY DWELLINGS AND TOWNHOMES
 UNDERGOING A REPAIR, OR A LEVEL 1 ALTERATION AS DEFINED
 IN THE FLORIDA BUILDING CODE, MAY USE SMOKE ALARMS
 POWERED BY 10-YEAR NONREMOVABLE, NONREPLACEABLE
 BATTERIES IN LIEU OF RETROFITTING SUCH DWELLING WITH
 SMOKE ALARMS POWERED BY THE DWELLING?S ELECTRICAL
 SYSTEM. A BATTERY-POWERED SMOKE ALARM THAT IS NEWLY
 INSTALLED OR REPLACES AN EXISTING BATTERY-POWERED SMOKE
 ALARM AS A RESULT OF A LEVEL 1 ALTERATION MUST BE
 POWERED BY A NONREMOVABLE, NONREPLACEABLE BATTERY THAT
 POWERS THE ALARM FOR AT LEAST 10 YEARS. THE BATTERY
 REQUIREMENTS OF THIS SECTION DO NOT APPLY TO A FIRE
 ALARM, SMOKE DETECTOR, SMOKE ALARM, OR ANCILLARY
 COMPONENT THAT IS ELECTRONICALLY CONNECTED AS A PART OF
 A CENTRALLY MONITORED OR SUPERVISED ALARM SYSTEM, THAT
 USES A LOWPOWER, RADIO FREQUENCY WIRELESS COMMUNICATION
 SIGNAL; OR THAT CONTAINS MULTIPLE SENSORS, SUCH AS A
 SMOKE ALARM COMBINED WITH A CARBON MONOXIDE ALARM OR
 OTHER MULTISENSOR DEVICES, AND IS APPROVED AND LISTED
 BY A NATIONALLY RECOGNIZED TESTING LABORATORY.
  
 3) 501.1.1 FBC[RE] ADDITIONS, ALTERATIONS, OR REPAIRS:
 GENERAL. ADDITIONS, ALTERATIONS, OR REPAIRS TO AN
 EXISTING BUILDING, BUILDING SYSTEM OR PORTION THEREOF
 SHALL COMPLY WITH SECTION R502, R503 OR R504. UNALTERED
 PORTIONS OF THE EXISTING BUILDING OR BUILDING SUPPLY
 SYSTEM SHALL NOT BE REQUIRED TO COMPLY WITH THIS CODE.
 -WHICH METHOD OF COMPLIANCE IS BEING USED?
  
 503.1.1 FBC[E] BUILDING ENVELOPE ASSEMBLIES THAT ARE
 PART OF THE ALTERATION SHALL COMPLY WITH SECTION
 R402.1.2 OR R402.1.4, SECTIONS R402.2.1 THROUGH
 R402.2.13, R402.3.1, R402.3.2, R402.4.3 AND R402.4.5.
  
 4) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 TILE ROOFING (TILE,UNDERLAYMENT AND ATTACHMENT), OR
 INDICATE THAT YOU WOULD LIKE THEM DEFERED.
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2019-09-16 Cont ID  
Sent By jpearson Date 2019-09-16 Time 13:02 Rev Time 0.00
Received By jpearson Date 2019-09-16 Time 13:02 Sent To  
Notes
2019-09-16 13:02:34ELECTRICAL SHALL BE BY SEPERATE PERMIT. PLAN SUBMISSION
 REQUIRED AT TIME OF PERMIT APPLICATION FOR ELECTRICAL.
 JP

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-06-26 Cont ID  
Sent By jpearson Date 2019-06-26 Time 14:46 Rev Time 0.00
Received By jpearson Date 2019-06-26 Time 14:46 Sent To  
Notes
2019-06-26 14:46:03CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR
 THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC
 107.1, 107.2.1, 107.3.5.1.2 (NOT CORRECTED.)
 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3 (NOT PROVIDED.)
 3. CORRECTED.
 4. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-15 Cont ID  
Sent By jpearson Date 2019-04-15 Time 13:06 Rev Time 0.00
Received By jpearson Date 2019-04-15 Time 10:03 Sent To  
Notes
2019-04-15 13:06:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR
 THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC
 107.1, 107.2.1, 107.3.5.1.2
 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 4. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9; FBC RE E3606.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-04-11 Cont ID  
Sent By fmittner Date 2019-04-11 Time 14:26 Rev Time 0.00
Received By fmittner Date 2019-04-11 Time 14:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-03 Cont ID  
Sent By cthroop Date 2019-07-03 Time 09:13 Rev Time 0.00
Received By cthroop Date 2019-06-06 Time 13:38 Sent To  
Notes
2019-06-07 13:38:11R20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-30 Cont ID  
Sent By dbattles Date 2019-04-30 Time 07:53 Rev Time 0.00
Received By dbattles Date 2019-03-26 Time 16:01 Sent To  
Notes
2019-03-27 16:02:03R13

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2019-07-03 Cont ID  
Sent By cthroop Date 2019-07-03 Time 09:12 Rev Time 0.00
Received By cthroop Date 2019-07-03 Time 08:32 Sent To  
Notes
2019-07-03 09:13:24MECH. BY SEPERATE PERMIT. CT

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-04-15 Cont ID  
Sent By hmoser Date 2019-04-15 Time 13:59 Rev Time 0.00
Received By hmoser Date 2019-04-15 Time 13:33 Sent To  
Notes
2019-04-15 14:00:45PLAN DENIED
 NO MECHANICAL PLANS PROVIED HM.

Review Stop P PLUMBING
Rev No 3 Status N Date 2019-09-16 Cont ID  
Sent By cthroop Date 2019-09-16 Time 12:56 Rev Time 0.00
Received By cthroop Date 2019-09-16 Time 12:55 Sent To  
Notes
2019-09-16 12:56:28PLUMBING SHALL BE BY SEPERATE PERMIT. CT

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-06-11 Cont ID  
Sent By jesmith Date 2019-06-11 Time 15:32 Rev Time 0.00
Received By jesmith Date 2019-06-11 Time 15:20 Sent To  
Notes
2019-06-11 15:20:55CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 30A
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 PLUMBING COMMEMTS: DENIED
  
 REGARDING THE RESPONSE LETTER (REF: PERMIT
 17020652-RESPONSE LETTER), PLUMBING COMMENT RESPONSE
 THAT THE REVISED PLUMBING RISER IS ON SHEET E-1 IS NOT
 ACCURATE. THERE IS NO REVISED PLUMBING RISER ON E-2. IF
 THERE IS TO BE A REVISED RISER DIAGRAM ON E-2, THEN THE
 DIAGRAM ON S-2 SHALL BE REMOVED.
 AS THERE IS NO REVISED DRAWING IT APPEARS NO ACTION HAS
 BEEN TAKEN IN RESPONSE TO THE COMMENTS MADE IN THE
 FIRST REVIEW. PLEASE SEE BELOW.
  
 1. SHT. S-1 AND S-2 THE SEAL AND SIGNATURE OF THE
 ENGINEER APPEARS TO BE PHOTO COPIED THEY SHALL BE
 ORIGINAL. FAC 61G15-23.003
 2. REMOVE STAMP AND SIGNATURE OF PREVIOUS PLUMBING
 EXAMINER SHT. S-2 PER WPB AMEND TO FBC 107.2.1
 3. SHT S-2 THE PLUMBING SANITARY RISER IN THE BATHROOM
 GROUP ONLY ONE FIXTURE UP STREAM OF THE WET VENT IS
 ALLOWED THE LAVATORY SHALL CONNECT BETWEEN THE TOILET
 AND TUB. PER FBC RES P3108.2.1
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19031173 3212 GREENWOOD AVE

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-12 Cont ID  
Sent By gjohnson Date 2019-04-12 Time 14:14 Rev Time 0.00
Received By gjohnson Date 2019-04-12 Time 11:02 Sent To  
Notes
2019-04-12 14:41:211ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. S-1 AND S-2 THE SEAL AND SIGNATURE OF THE
 ENGINEER APPEARS TO BE PHOTO COPIED THEY SHALL BE
 ORIGINAL. FAC 61G15-23.003
  
 2. REMOVE STAMP AND SIGNATURE OF PREVIOUS PLUMBING
 EXAMINER SHT. S-2 PER WPB AMEND TO FBC 107.2.1
  
 3. SHT S-2 THE PLUMBING SANITARY RISER IN THE BATHROOM
 GROUP ONLY ONE FIXTURE UP STREAM OF THE WET VENT IS
 ALLOWED THE LAVATORY SHALL CONNECT BETWEEN THE TOILET
 AND TUB. PER FBC RES P3108.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2019-06-12 Cont ID  
Sent By dbattles Date 2019-06-12 Time 10:58 Rev Time 0.00
Received By dbattles Date 2019-06-12 Time 10:58 Sent To  
Notes
2019-06-12 11:00:50PRODUCT APPROVALS FOR ROOFING AND ATTACHMENT DUE WITH
 SUB PERMIT.
 MATERIALS TO BE APPROVED WITH HISTORICAL REVIEW.

Review Stop Z ZONING
Rev No 1 Status P Date 2019-04-11 Cont ID  
Sent By fmittner Date 2019-04-11 Time 14:26 Rev Time 0.00
Received By fmittner Date 2019-04-11 Time 14:26 Sent To  
Notes
***NONE***