Plan Review Details - Permit 19031153
Plan Review Stops For Permit 19031153
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2019-06-19 07:02:29DEMO PURPOSES
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-06-18 Cont ID  
Sent By jleahy Date 2019-06-18 Time 10:27 Rev Time 0.00
Received By jleahy Date 2019-06-18 Time 10:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-06-17 Cont ID  
Sent By fgiaquin Date 2019-06-17 Time 06:38 Rev Time 0.00
Received By fgiaquin Date 2019-06-17 Time 06:04 Sent To I
Notes
2019-06-17 06:38:45ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO UL OR OTHER NRTL LISTING SHOWN FOR CAMERAS OR 64
 CHANNEL, A GENERIC LIST THAT SAYS "UL PRODUCT CATEGORY"
 WAS PROVIDED. THAT IS NOT A LISTING. PLEASE PROVIDE
 LISTINGS. FBC 107.2.1 NEC 90.7, 110.2, 110.3B
  
 2. NO PRODUCT SPECS PROVIDED FOR CARD READERS? PLEASE
 PROVIDE SPECS AND LISTING. FBC 107.2.1 NEC 90.7, 110.2,
 110.3B
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-05-14 Cont ID  
Sent By fgiaquin Date 2019-05-14 Time 06:18 Rev Time 0.00
Received By fgiaquin Date 2019-05-14 Time 06:03 Sent To I
Notes
2019-05-14 06:18:30ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SAME VIOLAATIONS AS LAST PLAN REVIEW.
  
 ONLY POWER SUPPLY AND DOOR STRIKE IS LISTED PER SPEC
 SHEETS PROVIDED. PROVIDED LISTINGS CLEARLY MARKED WITH
 HI-LIGHTER OR OTHER DIFFERENTIATING MEANS FOR CONTROL
 PANEL AND ALL OTHER DEVICES.. NEC 90.7, 110.2, 110.3B
  
 2. PLANS ARE NOT MARKED CORRECTLY. SEVERAL PAGES OF THE
 PLAN THE HEADING AT THE BOTTOM WHICH LABELS EACH PAGE
 "1ST FLOOR 2ND FLOOR" ETC IS NOT CLEARLY VISIBLE.
 SUBMIT NEW PLANS THAT ARE CLEARLY MARKED.
  
 FBC 107.2.1.3 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC
 MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS
 OF FLORIDA STATUTES.
  
 3. VALUE FOR PROJECT IS LOW. PROVIDE COPY OF CONTRACT
 (SIGNED BY BOTH OWNER AND CONTRACTOR) TO INCLUDE ALL
 MATERIALS AND LABOR. FBC 109.3 BUILDING PERMIT
 VALUATION. FOR PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE
 CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET
 BY THE BUILDING OFFICIAL.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-18 Cont ID  
Sent By fgiaquin Date 2019-04-18 Time 06:49 Rev Time 0.00
Received By fgiaquin Date 2019-04-18 Time 06:40 Sent To I
Notes
2019-04-18 06:49:55ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLEASE SUBMIT CUT SHEETS FOR PRODUCT APPROVAL OF ALL
 MATERIALS/DEVICES. NOTHING WAS PROVIDED. FBC 107.2.1,
 NEC 90.7, 110.2, 110.3B
  
 2. VALUE FOR PROJECT SEEMS LOW. PLEASE PROVIDE COPY OF
 SIGNED CONTRACT WITH SCOPE AND VALUE OF WORK, TO
 INCLUDE ALL MATERIALS AND LABOR. FBC 109.3
  
 3. SEVERAL PAGES OF THE SUBMITTED PLAN HAVE SOME SORT
 OF PRINTING ISSUE. THE TITLE AT THE BOTTOM OF THE PAGE
 THAT DESCRIBES WHAT PAGE IT IS. "FIRST FLOOR, SITE
 PLAN, ETC" IS NOT LEGIBLE AND MISSING LETTERS. PLEASE
 PROVIDE PLANS THAT ARE ACCURATE AND CLEARLY LEGIBLE AND
 DESCRIBE CLEARLY WHAT PAGE IS WHAT.
  
 107.2.1.3 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC
 MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS
 OF FLORIDA STATUTES.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-05-30 Cont ID  
Sent By pleduc Date 2019-05-30 Time   Rev Time 0.00
Received By pleduc Date 2019-05-30 Time 13:41 Sent To E
Notes
2019-05-30 13:49:47THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) PROVIDE A KNOW KEY SWITCH AT THE ENTRY FOR FIRE
 DEPARTMENT ACCESS.
  
  
  
 2) PROVIDE A KNOX KEY SWITCH AT THE FD SOUTH EXIT GATE
 FOR FIRE DEPARTMENT EGRESS.
  
  
 3) THERE ARE INDICATION OF ACCESS CONTROL
  
 ALL INSTALLED EQUIPMENT SHALL FUNCTION AS PER THE
 REQUIREMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS AS
 APPLICABLE BELOW PER EACH DOOR/ENTRY/EXIT.
  
  
 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR
 ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS
 SHALL BE PERMITTED TO BE ELECTRICALLY LOCKED IF
 EQUIPPED WITH APPROVED, LISTED HARDWARE, PROVIDED THAT
 ALL OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS
 AFFIXED TO THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED IN THE DIRECTION OF EGRESS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN THE DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER
 SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE
 DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE
 DIRECTION OF EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH ANSI/UL 294, STANDARD FOR ACCESS
 CONTROL SYSTEM UNITS.
  
  
 7.2.1.6.2* ACCESS-CONTROLLED EGRESS DOOR ASSEMBLIES.
 WHERE PERMITTED IN CHAPTERS 11 THROUGH 43, DOOR
 ASSEMBLIES IN THE MEANS OF EGRESS SHALL BE PERMITTED TO
 BE EQUIPPED WITH ELECTRICAL LOCK HARDWARE THAT PREVENTS
 EGRESS, PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE
 MET:
 (1) A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO UNLOCK THE DOOR LEAF IN THE DIRECTION OF
 EGRESS UPON DETECTION OF AN APPROACHING OCCUPANT.
 (2) DOOR LEAVES SHALL AUTOMATICALLY UNLOCK IN THE
 DIRECTION OF EGRESS UPON LOSS OF POWER TO THE SENSOR OR
 TO THE PART OF THE ACCESS CONTROL SYSTEM THAT LOCKS THE
 DOOR LEAVES.
 (3) DOOR LOCKS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 COMPLYING WITH ALL OF THE FOLLOWING CRITERIA:
 (A) THE MANUAL RELEASE DEVICE SHALL BE LOCATED ON THE
 EGRESS SIDE, 40 IN. TO 48 IN. (1015 MM TO 1220 MM )
 VERTICALLY ABOVE THE FLOOR, AND WITHIN 60 IN. (1525 MM)
 OF THE SECURED DOOR OPENINGS.
 (B) THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS
 AS FOLLOWS: PUSH TO EXIT.
 (C) WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK
 INDEPENDENT OF THE LOCKING SYSTEM ELECTRONICS .AND THE
 LOCK SHALL REMAIN UNLOCKED FOR NOT LESS THAN 30
 SECONDS.
 (4) ACTIVATION OF THE BUILDING FIRE-PROTECTIVE
 SIGNALING SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY
 UNLOCK THE DOOR LEAVES IN THE DIRECTION OF EGRESS, AND
 THE DOOR LEAVES SHALL REMAIN UNLOCKED UNTIL THE
 FIRE-PROTECTIVE SIGNALING SYSTEM HAS BEEN MANUALLY
 RESET.
 (5) THE ACTIVATION OF MANUAL FIRE ALARM BOXES THAT
 ACTIVATE THE BUILDING FIRE-PROTECTIVE SIGNALING SYSTEM
 SPECIFIED IN 7.2.1.6.2 (4) SHALL NOT BE REQUIRED TO
 UNLOCK THE DOOR LEAVES.
 (6) ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER OR
 FIRE DETECTION SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY
 UNLOCK THE DOOR LEAVES IN THE DIRECTION OF EGRESS, AND
 THE DOOR LEAVES SHALL REMAIN UNLOCKED UNTIL THE
 FIRE-PROTECTIVE SIGNALING SYSTEM HAS BEEN MANUALLY
 RESET.
 (7) THE EGRESS SIDE OF ACCESS-CONTROLLED EGRESS DOORS,
 OTHER THAN EXISTING ACCESS-CONTROLLED EGRESS DOORS,
 SHALL BE PROVIDED WITH EMERGENCY LIGHTING IN ACCORDANCE
 WITH SECTION 7.9.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-04-01 Cont ID  
Sent By scaldero Date 2019-04-01 Time 12:51 Rev Time 0.00
Received By scaldero Date 2019-04-01 Time 12:38 Sent To E
Notes
2019-04-01 12:51:07PERMIT # 19031153
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED PROVISO:
  
 1) PROVIDE A KNOX KEY SWITCH TO ALLOW GATE ACCESS TO
 EMERGENCY RESPONDERS. KEY SWITCH CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 2) PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 3) PER SECTION 7.2.1.6.2, ACCESS-CONTROLLED EGRESS
 DOORS ARE PERMITTED PROVIDED THAT ALL SEVEN OF THE
 FOLLOWING CRITERIA ARE MET:
 1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO DETECT AN OCCUPANT APPROACHING DOORS THAT
 ARE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS UPON
 DETECTION OF AN APPROACHING OCCUPANT OR LOSS OF POWER
 TO THE SENSOR.
 2. LOSS OF POWER TO THE PART OF THE ACCESS CONTROL
 SYSTEM THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK
 THE DOORS IN THE DIRECTION OF EGRESS.
 3. THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 LOCATED VERTICALLY 40 TO 48 INCHES ABOVE THE FLOOR AND
 WITHIN 60 INCHES HORIZONTALLY OF THE SECURED DOORS.
 4. THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS
 PUSH TO EXIT.
 5. WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK,
 INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS,
 AND THE DOORS SHALL REMAIN UNLOCKED FOR NOT LESS THAN
 30 SECONDS.
 6. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
 7. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER
 SYSTEM OR AUTOMATIC DETECTION SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
  
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-06-17 Cont ID  
Sent By fgiaquin Date 2019-06-17 Time 06:38 Rev Time 0.00
Received By fgiaquin Date 2019-05-28 Time 09:51 Sent To  
Notes
2019-05-30 09:51:20RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-14 Cont ID  
Sent By fgiaquin Date 2019-05-14 Time 06:18 Rev Time 0.00
Received By fgiaquin Date 2019-05-09 Time 12:56 Sent To  
Notes
2019-05-09 12:56:56RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-18 Cont ID  
Sent By fgiaquin Date 2019-04-18 Time 06:50 Rev Time 0.00
Received By fgiaquin Date 2019-03-25 Time 14:13 Sent To  
Notes
2019-03-26 14:14:05ROUTED TO FIRE INBOX

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2021-02-13 Cont ID  
Sent By shill Date 2021-02-13 Time 10:20 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
***NONE***