Plan Review Details - Permit 19031125
Plan Review Stops For Permit 19031125
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-04-12 Cont ID  
Sent By jleahy Date 2019-04-12 Time 09:22 Rev Time 0.00
Received By jleahy Date 2019-04-12 Time 09:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-02 Cont ID  
Sent By jleahy Date 2019-04-02 Time 16:32 Rev Time 0.00
Received By jleahy Date 2019-04-02 Time 16:32 Sent To  
Notes
2019-04-02 16:34:03FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-02 Cont ID  
Sent By jleahy Date 2019-04-02 Time 16:32 Rev Time 0.00
Received By jleahy Date 2019-03-25 Time 14:00 Sent To  
Notes
2019-03-26 14:00:28ELEC <5K