Plan Review Details - Permit 19031028
Plan Review Stops For Permit 19031028
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-06-06 Cont ID  
Sent By cthroop Date 2019-06-06 Time 14:21 Rev Time 0.00
Received By cthroop Date 2019-06-06 Time 13:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-05-20 Cont ID  
Sent By jduprey Date 2019-05-20 Time 08:42 Rev Time 0.00
Received By jduprey Date 2019-05-17 Time 14:43 Sent To  
Notes
2019-05-20 09:13:55BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL APPROVAL FOR THE SUBMITTED SCOPE OF WORK
 IS PENDING DUE FOR THE REASONS LISTED BELOW.
  
 1. PER PALM BEACH COUNTY PROPERTY APPRAISAL WEBSITE
 THIS PROPERTY HAVE A TOTAL OF 2932 SQUARE FOOT. THE
 ENERGY CALCULATIONS WERE SUBMITTED WITH A TOTAL OF 1818
 SQUARE FOOT AND A TOTAL OF 4 BEDROOMS, PLEASE CLARIFY.
 ALSO THE LINE ITEM NUMER 9 IS ONLY INCLUDING ONE TYPE
 OF WALL (CONCRETE BLOCK) WITH INSULATION TYPE R4.1,
 HOWEVER THE DRAWING DETAIL 3/A2.0 SHOW AN INSULATION
 TYPE R5 FOR THIS CONCRETE WALL TYPE. THE ENERGY
 CALCULATION DOCUMENT DOES NOT SHOW INSULATION
 REQUIREMENTS FOR UPPER FLOOR WOOD WALLS AS INDICATE ON
 DETAIL 3/A2.0. PLEASE CLARIFY AND RE-SUBMIT.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-11 Cont ID  
Sent By jgomez Date 2019-04-11 Time 18:03 Rev Time 0.00
Received By jgomez Date 2019-04-10 Time 11:20 Sent To Z
Notes
2019-04-11 18:05:46RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PLANS SUBMITTED NEED TO HAVE THE SEAL AND SIGNATURE
 OF THE ARCHITECT OF RECORD SHOWN ON THE TITLE BLOCK
 (REGINALD ACOX & ASSOCIATES) AS REQUIRED BY CHAPTER 481
 F.S WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS.
  
 2- PLANS SUBMITTED SHOW NEW BEDROOMS AND NEW BATHROOM.
 ACCORDING TO CITY RECORDS AND PROPERTY APPRAISER THIS
 AREA WAS PERMITTED AS A GARAGE. THERE ARE NO CITY
 RECORDS FOR THE CONVERSION OF GARAGE TO BEDROOMS AND
 BATHROOM. REVISE SCOPE OF WORK ON THE PERMIT
 APPLICATION TO REFLECT THE CONVERSION OF GARAGE TO
 LIVABLE SPACE. THIS IS A CHANGE OF USE WITHOUT A CHANGE
 OF OCCUPANCY. SEC. 506 FBC-EXISTING BUILDING AND SEC.
 1001.2.1 FBC-EXISTING BUILDING.
  
 3- SCOPE OF WORK SHOWN ON PLANS IS NOT CLEAR. ALL THE
 WORK SHOWN ON THE EXISTENT GARAGE CONVERTED TO
 BEDROOMS/BATHROOM IS CONSIDERED TO BE NEW. CLEARLY
 DEFINE THE SCOPE OF WORK ON THE SECOND FLOOR AND ON THE
 REST OF THE HOUSE. CLEARLY IDENTIFY WHAT IS NEW, WHAT
 IS REPLACED, ETC. CLEARLY IDENTIFY ALL NEW WALLS.
 CLEARLY SPECIFY WHICH WINDOWS/DOORS ARE NEW AND WHICH
 WINDOWS/DOORS ARE REPLACED. SEC. 107.2.1 CITY
 AMENDMENTS.
 NOTE: FOR WINDOWS THAT ARE GOING TO BE REPLACED,
 CLEARLY SPECIFY THE SIZE AND TYPE OF EXISTING WINDOW
 AND SIZE AND TYPE OF PROPOSED WINDOWS, SPECIALLY THE
 BEDROOM WINDOWS TO VERIFY COMPLIANCE WITH THE EGRESS
 REQUIREMENTS SEC. 702.5 FBC-EXISTING BUILDING.
  
 4- WINDOWS ON NEW BEDROOMS WHERE THE GARAGE USED TO BE
 DON'T COMPLY WITH THE EGRESS REQUIREMENTS OF SEC.
 R310.2.1 FBC-RESIDENTIAL. REVISE AS REQUIRED. CLEARLY
 SPECIFY THE WINDOWS SIZE (WIDTH AND HEIGHT) AND TYPE.
  
 5- PROVIDE ENERGY CALCULATIONS (2 COPIES)AS REQUIRED BY
 SEC. 1106.1 FBC-EXISTING BUILDING.
  
 6- ARCHITECT OF RECORD TO SHOW ON PLANS COMPLIANCE WITH
 THE HEATING REQUIREMENTS FOR THE NEW BEDROOMS AS
 REQUIRED BY SEC. R303.10 FBC-RESIDENTIAL.
  
 7- ARCHITECT OF RECORD TO SHOW ON PLANS THE INSULATION
 R VALUES FOR WALLS AND CEILINGS AS REQUIRED BY SEC.
 R103.2 FBC-ENERGY CONSERVATION. NOTE: COORDINATE WITH
 ENERGY CALCULATIONS TO AVOID CONFLICTS/DELAYS.
  
 8- ARCHITECT OF RECORD TO SPECIFY THE DESIGN PRESSURES
 FOR DOORS AND WINDOWS UNDER THE DESIGN CRITERIA
 PROVIDED. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 9- THERE IS A NOTE A THE BOTTOM RIGHT OF THE FLOOR PLAN
 STATING THAT "REPAIR OR REPLACE ALL EXISTING BUILDING
 COMPONENTS AS NEEDED". THIS STATEMENT IS TOO GENERAL.
 ARCHITECT TO CLERKLY IDENTIFY WHICH BUILDING COMPONENTS
 NEED TO BE REPLACED AND PROVIDE COMPLETE SPECIFICATIONS
 FOR NEW COMPONENT. SEC. 107.2.1 CITY AMENDMENTS. SEC.
 801.3 FBC-EXISTING BUILDING AND SEC. 107.2.1 CITY
 AMENDMENTS.
  
 10- ARCHITECT OF RECORD TO CLARIFY HOW ARE THE GARAGE
 DOORS OPENED TO ACCESS THE OUTSIDE STORAGE AREA SHOWN
 ON THE FLOOR PLAN.? SEC. 107.2.1 CITY AMENDMENTS.
  
 11- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR ALL NEW DOORS, WINDOWS AND DOORS
 AND WINDOWS TO BE REPLACED. AND, WINDOW MULLIONS
 (SPECIFY SIZE) AND SHUTTERS (WITH COMPLETE INSTALLATION
 SCHEDULE) IF DOORS AND WINDOWS DON'T HAVE IMPACT
 GLAZING.
  
 12- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 13- DIMENSION OF THE HALLWAY BETWEEN THE NEW BEDROOMS
 AND NEW BATHROOM IS NOT GIVEN. BASED ON THE SCALE
 PROVIDED, THE WIDTH OF THIS HALLWAY DOESN'T COMPLY WITH
 SEC. R311.6 FBC-RESIDENTIAL. PROVIDE DIMENSION ON FLOOR
 PLAN. (DIMENSION TO BE VERIFIED BY INSPECTOR).
  
 14- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW BASED ON THE SCOPE OF WORK. VALUATION TO INCLUDE
 ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT
 AND DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3
 CITY AMENDMENTS. UPDATE VALUATION AS REQUIRED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 SUBMIT OLD DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-05-17 Cont ID  
Sent By ppetty Date 2019-05-17 Time 15:17 Rev Time 0.00
Received By ppetty Date 2019-05-17 Time 15:17 Sent To  
Notes
2019-05-17 15:18:52PLEASE SEE PROVISO

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-04-09 Cont ID  
Sent By jpearson Date 2019-04-09 Time 10:59 Rev Time 0.00
Received By jpearson Date 2019-04-09 Time 10:10 Sent To  
Notes
2019-04-09 10:59:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR
 THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC
 107.1, 107.2.1, 107.3.5.1.2
 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 3. PROVIDE ELECTRICAL PLAN FOR REVIEW, INDICATING
 EXISTING, NEW, AND RELOCATED LIGHTING AND RECEPTACLE
 OUTLETS. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 210.19, 210.20,
 215.5, 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
 4. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
 5. IF ANY LOAD IS BEING ADDED TO ELECTRICAL SYSTEM,
 PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
 6. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC
 107.2.1
 7. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2019-06-04 Cont ID  
Sent By aborngra Date 2019-06-04 Time 11:12 Rev Time 0.00
Received By aborngra Date 2019-06-04 Time 11:11 Sent To PC
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2019-05-22 Cont ID  
Sent By aborngra Date 2019-05-22 Time 14:01 Rev Time 0.00
Received By aborngra Date 2019-05-22 Time 14:01 Sent To PC
Notes
2019-05-22 14:01:25THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
  
 1. THE GARAGE DOORS SHALL REMAIN AS LOCATED OR NEW
 GARAGE DOORS SHALL BE INSTALLED. ILLUSTRATE THE GARAGE
 DOORS ON THE ELEVATION. IF NEW DOORS ARE PROPOSED,
 PROVIDE AN ILLUSTRATION OF THEIR APPEARANCE.
 2. PROVIDE A SITE PLAN ILLUSTRATING THREE (3)
 OFF-STREET PARKING SPACES. EACH SPACE MUST HAVE A
 MINIMUM WIDTH OF 8.5 FEET AND A MINIMUM DEPTH OF 18
 FEET.
 3. PROVIDE A SITE PLAN ILLUSTRATING THAT ALL MECHANICAL
 EQUIPMENT DOES NOT PROJECT MORE THAN FOUR FEET INTO A
 SETBACK. (SEC 94-305 (B)(4)) THE REAR SETBACK FOR THIS
 PROPERTY IS 15 FEET OR 10% OF THE LOT DEPTH. A ROUGH
 CALCULATION SHOWS A 100-FOOT DEPTH LOT, REQUIRING A
 MINIMUM REAR SETBACK OF 10 FEET. THE MECHANICAL
 EQUIPMENT TO THE PROPERTY LINE SHALL REQUIRE A MINIMUM
 DISTANCE OF SIX (6) FEET. A SURVEY IS REQUIRED TO
 VERIFY THE EXACT LOCATION OF THE REAR PROPERTY LINE AND
 DISTANCE TO THE STRUCTURE.
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected]
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-04-15 Cont ID  
Sent By aborngra Date 2019-04-15 Time 10:33 Rev Time 0.00
Received By aborngra Date 2019-04-12 Time 11:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-06-06 Cont ID  
Sent By cthroop Date 2019-06-06 Time 14:22 Rev Time 0.00
Received By cthroop Date 2019-05-29 Time 15:22 Sent To  
Notes
2019-05-30 15:22:39R36

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-22 Cont ID  
Sent By lmarchan Date 2019-05-22 Time 15:34 Rev Time 0.00
Received By lmarchan Date 2019-05-07 Time 14:07 Sent To  
Notes
2019-05-08 14:07:35R36

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-15 Cont ID  
Sent By cpuell Date 2019-04-15 Time 11:08 Rev Time 0.00
Received By cpuell Date 2019-03-22 Time 14:58 Sent To  
Notes
2019-03-26 14:58:32R08

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-05-20 Cont ID  
Sent By jduprey Date 2019-05-20 Time 09:15 Rev Time 0.00
Received By jduprey Date 2019-05-17 Time 09:50 Sent To  
Notes
2019-05-20 09:16:20MU-2019-012144-0000
 $236.59 PAID

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-04-11 Cont ID  
Sent By jgomez Date 2019-04-11 Time 18:15 Rev Time 0.00
Received By jgomez Date 2019-04-11 Time 18:14 Sent To  
Notes
2019-04-11 18:16:03IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-05-22 Cont ID  
Sent By cthroop Date 2019-05-22 Time 07:38 Rev Time 0.00
Received By cthroop Date 2019-05-17 Time 09:50 Sent To  
Notes
2019-05-22 07:39:22PROVISO ON PLAN. PROVIDE MANUFACTURERES SPECIFCATIONS
 AT INSPECTION. CT

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-04-10 Cont ID  
Sent By jgomez Date 2019-04-10 Time 16:13 Rev Time 0.00
Received By jgomez Date 2019-04-10 Time 16:13 Sent To  
Notes
2019-04-10 16:27:43RESIDENTIAL (R3) ADDITION/ALTERATION MECHANICAL REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 SUBMIT ALL THE INFORMATION OR CONTRACTOR TO ADVICE IF
 PROVIDING COMPLETE INFORMATION UNDER A SEPARATE PERMIT.
  
 1- PROVIDE COMPLETE MECHANICAL PLANS SHOWING ALL THE
 DUCTWORK AND EQUIPMENT, ETC. CLEARLY SPECIFY EQUIPMENT
 MANUFACTURER, MODEL, CAPACITY, ETC. 107.3.5.3 (11) CITY
 AMENDMENTS.
  
 2- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS BASED
 ON BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION OF
 THE BUILDING. AND, THE MANUFACTURER'S AND MODEL NUMBER
 SHALL BE SUBMITTED ALSO, ALONG WITH THE SENSIBLE AND
 TOTAL COOLING CAPACITIES AS REQUIRED BY SEC. R403.7.1
 FBC-ENERGY CONSERVATION.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-06-06 Cont ID  
Sent By cthroop Date 2019-06-06 Time 14:22 Rev Time 0.00
Received By cthroop Date 2019-06-06 Time 13:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-05-09 Cont ID  
Sent By gjohnson Date 2019-05-09 Time 16:43 Rev Time 0.00
Received By gjohnson Date 2019-05-09 Time 15:55 Sent To  
Notes
2019-05-09 16:50:481ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENT NOT COMPLIED NO
 CONTRACT PROVIDED
  
  
 VALUE SEEMS LOW. PROVIDE A SIGN BONA FIDE CONTRACT.
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-04-05 Cont ID  
Sent By thunt Date 2019-04-05 Time 13:51 Rev Time 0.00
Received By thunt Date 2019-04-05 Time 13:51 Sent To  
Notes
2019-04-05 13:54:04PLUMBING 1ST REVIEW**DENIED**
  
 1) PROVIDE A EXISTING FLOOR PLAN AND SCOPE OF WORK TO
 INCLUDE PLUMBING ISOMETRIC DRAWING. FBC 107.3.5
  
 2) PERSON DESIGNING PLAN SHALL TAKE OWNERSHIP. F.S 471
  
 3) SUB PLUMBING PERMIT REQUIRED.
  
 4) VALUE SEEMS LOW. PROVIDE A SIGN BONA FIDE CONTRACT.
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2019-06-04 Cont ID  
Sent By aborngra Date 2019-06-04 Time 11:11 Rev Time 0.00
Received By aborngra Date 2019-06-04 Time 11:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2019-05-22 Cont ID  
Sent By aborngra Date 2019-05-22 Time 14:01 Rev Time 0.00
Received By aborngra Date 2019-05-22 Time 14:01 Sent To PC
Notes
2019-05-22 14:01:44THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
  
 1. THE GARAGE DOORS SHALL REMAIN AS LOCATED OR NEW
 GARAGE DOORS SHALL BE INSTALLED. ILLUSTRATE THE GARAGE
 DOORS ON THE ELEVATION. IF NEW DOORS ARE PROPOSED,
 PROVIDE AN ILLUSTRATION OF THEIR APPEARANCE.
 2. PROVIDE A SITE PLAN ILLUSTRATING THREE (3)
 OFF-STREET PARKING SPACES. EACH SPACE MUST HAVE A
 MINIMUM WIDTH OF 8.5 FEET AND A MINIMUM DEPTH OF 18
 FEET.
 3. PROVIDE A SITE PLAN ILLUSTRATING THAT ALL MECHANICAL
 EQUIPMENT DOES NOT PROJECT MORE THAN FOUR FEET INTO A
 SETBACK. (SEC 94-305 (B)(4)) THE REAR SETBACK FOR THIS
 PROPERTY IS 15 FEET OR 10% OF THE LOT DEPTH. A ROUGH
 CALCULATION SHOWS A 100-FOOT DEPTH LOT, REQUIRING A
 MINIMUM REAR SETBACK OF 10 FEET. THE MECHANICAL
 EQUIPMENT TO THE PROPERTY LINE SHALL REQUIRE A MINIMUM
 DISTANCE OF SIX (6) FEET. A SURVEY IS REQUIRED TO
 VERIFY THE EXACT LOCATION OF THE REAR PROPERTY LINE AND
 DISTANCE TO THE STRUCTURE.
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected]
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2019-04-15 Cont ID  
Sent By jgomez Date 2019-04-16 Time 09:23 Rev Time 0.00
Received By aborngra Date 2019-04-15 Time 10:33 Sent To PC
Notes
2019-04-15 10:39:01THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
  
 1. PROVIDE A SITE PLAN ILLUSTRATING THREE (3)
 OFF-STREET PARKING SPACES. EACH SPACE MUST HAVE A
 MINIMUM WIDTH OF 8.5 FEET AND A MINIMUM DEPTH OF 18
 FEET.
  
  
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected].
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]
  