Plan Review Details - Permit 19031011
Plan Review Stops For Permit 19031011
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-04-17 Cont ID  
Sent By fgiaquin Date 2019-04-17 Time 06:51 Rev Time 0.00
Received By fgiaquin Date 2019-04-17 Time 06:36 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-04-01 Cont ID  
Sent By fgiaquin Date 2019-04-01 Time 07:23 Rev Time 0.00
Received By fgiaquin Date 2019-04-01 Time 07:23 Sent To I
Notes
2019-04-01 07:23:45ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. AS PER LAST PLAN REVIEW COMMENTS. NO ELECTRICAL PLAN
 SUBMITTED SHOWING, CONDUIT SIZE AND TYPE FROM MCC TO
 MOTORS, WIRE SIZE FROM MCC TO MOTORS, WIRE TYPE, ETC.
 PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND SEALED
 BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 2. AS PER LAST PLAN REVIEW COMMENTS VALUE FOR LIFT
 STATION IS LOW, VALUE WILL BE RAISED BY BUILDING
 OFFICIAL. FBC 109.3 BUILDING PERMIT VALUATION. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-03-25 Cont ID  
Sent By fgiaquin Date 2019-03-25 Time 06:38 Rev Time 0.00
Received By fgiaquin Date 2019-03-25 Time 06:18 Sent To P
Notes
2019-03-25 06:38:41ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO ELECTRICAL PLAN PROVIDED. PROVIDE ELECTRICAL PLAN
 FOR REVIEW, SIGNED AND SEALED BY A LICENSED DESIGN
 PROFESSIONAL. SHOW CONDUIT SIZE, CONDUIT TYPE, WIRE
 SIZE, MOTORS, OCP, HAZARDOUS LOCATION DOCUMENTATION,
 ETC. FS 471.003(2)(H); 471.025; WPB FBC 107.2.1,
 107.3.5
  
 2, WORK HAS ALREADY BEEN COMPLETED IN THE FIELD WITH NO
 INSPECTIONS. LABELS ON EQUIPMENT AND EMAILS FROM
 CONTRACTOR STATE THAT IT IS A CLASS 1 DIVISION 1
 HAZARDOUS LOCATION. A DESIGN PROFESSIONAL MUST
 DETERMINE WHETHER IT IS A CLASS LOCATION OR NOT AND
 MUST PROVIDE SIGNED AND SEALED DOCUMENTION. NEC 500.4
 NEC 107.2.1
  
 3. VALUE FOR PROJECT LOW. RAISE VALUE OR VALUE WILL BE
 SET BY BUILDING OFFICIAL.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-04-17 Cont ID  
Sent By fgiaquin Date 2019-04-17 Time 06:51 Rev Time 0.00
Received By fgiaquin Date 2019-04-02 Time 15:13 Sent To  
Notes
2019-04-03 15:13:20RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-01 Cont ID  
Sent By fgiaquin Date 2019-04-01 Time 07:24 Rev Time 0.00
Received By fgiaquin Date 2019-03-26 Time 15:39 Sent To  
Notes
2019-03-27 15:39:24RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-25 Cont ID  
Sent By fgiaquin Date 2019-03-25 Time 06:43 Rev Time 0.00
Received By fgiaquin Date 2019-03-21 Time 10:57 Sent To  
Notes
2019-03-22 10:58:00ELEC <5K