Plan Review Details - Permit 19030914
Plan Review Stops For Permit 19030914
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2019-05-01 Cont ID  
Sent By shill Date 2019-05-01 Time 16:24 Rev Time 0.00
Received By shill Date 2019-05-01 Time 16:24 Sent To  
Notes
2019-05-01 16:24:46SUITE W103 IS BEING RETIRED
  
 SUITE W104 IS THE CORRECT ADDRESS
  
  

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2019-05-01 Cont ID  
Sent By shill Date 2019-05-01 Time 10:54 Rev Time 0.00
Received By shill Date 2019-05-01 Time 10:54 Sent To  
Notes
2019-05-01 10:54:38FOR ADDRESSING, PLEASE CONTACT (PREFERABLY VIA EMAIL):
  
 MICHAEL ORIO
 GIS SUPPORT SPECIALIST
 [email protected]
 CITY OF WEST PALM BEACH
 INFORMATION TECHNOLOGY DEPARTMENT
 401 CLEMATIS STREET, WEST PALM BEACH, FLORIDA 33401
 P: 561.494.1080
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-06-04 Cont ID  
Sent By jgomez Date 2019-06-04 Time 09:32 Rev Time 0.00
Received By jgomez Date 2019-06-03 Time 18:52 Sent To  
Notes
2019-06-03 19:14:35BUILDING REVIEW APPROVED WITH PROVISO (PROVIDE
 INFORMATION FORE REVIEW PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS/DELAYS):
 1-PROVIDE COMPLETE SIGNED & SEALED DETAILS
 /SPECIFICATIONS FOR ALL STRUCTURAL LIGHT GAUGE STEEL
 FRAMING AS SPECIFIED ON PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-05-16 Cont ID  
Sent By jgomez Date 2019-05-16 Time 14:34 Rev Time 0.00
Received By jgomez Date 2019-05-16 Time 11:32 Sent To  
Notes
2019-05-16 11:37:38SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 SEC. 801.3 FBC-EXISTING BUILDING.
  
  
 1- THERE IS A NOTE ON THE ENLARGEMENT DETAIL 1 ON SHEET
 S200 STATING "EXISTING LIGHT GAUGE WALLS TO REMAIN. ANY
 WALL THAT REQUIRED TO INSTALL THE NEW STEEL FRAMING
 SHALL BE BUILT BACK PER THE ORIGINAL BASE BUILDING
 DRAWINGS".
 ENGINEER OF RECORD NEEDS TO PROVIDE COMPLETE DETAILS
 AND SPECIFICATIONS FOR THE FRAMING OF THE WALL THAT IS
 GOING TO BE BUILT TO RECEIVE THE NEW STOREFRONT. SEC.
 1609.1 FBC.
  
 RESPONSE:
 RESPONSE LETTER FROM MCNAMARA/SLAVIA, INC. STATES THAT
 "THE STOREFRONT SYSTEM SPANS VERTICALLY AND IS ATTACHED
 TO THE SLAB ON GRADE AT THE BASE AND A NEW HSS MEMBER
 AT THE HEAD PER SECTION 1/S320. THE LIGHT GAUGE WALLS
 ARE INFILL EXTERIOR WALLS ONLY AND THEIR DESIGN IS BY
 THE LIGHT GAUGE ENGINEER".
  
 THIS STATEMENT DOESN'T SEEM TO BE CORRECT. ACCORDING TO
 STOREFRONT PRODUCT APPROVAL AND DETAILS SUBMITTED THE
 STOREFRONT IS ATTACHED TO THE SIDE WALLS AS WELL. ALSO,
 THERE WERE NO DETAILS AND SPECIFICATIONS SUBMITTED FROM
 THE LIGHT GAUGE ENGINEER.
 PROVIDE COMPLETE INFORMATION.
 NOTE: COORDINATE WITH STOREFRONT PRODUCT APPROVAL TO
 AVOID CONFLICTS/DELAYS.
  
  
 2- WALL SECTIONS ON SHEET S320 NEED TO PROVIDE COMPLETE
 SPECIFICATIONS FOR THE CONSTRUCTION OF THE PARAPET.
 NEED TO SPECIFY THE GAUGE OF THE STEEL STUDS AND
 PROVIDE FASTENER SPECIFICATIONS. SEC. 1609.1 FBC.
  
 RESPONSE:
  
 RESPONSE LETTER FROM MCNAMARA/SLAVIA, INC. STATES THAT
 "THE FINAL DESIGN OF THE LIGHT GAUGE STUDS WILL BE A
 ""DIFFERENT SUBMITTAL"" SIGNED AND SEALED BY THE GC'S
 ENGINEER".
  
 THE DIFFERED SUBMITTAL WAS NOT SUBMITTED. PROVIDE
 COMPLETE INFORMATION.
  
 3- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR THE NEW STOREFRONT SYSTEM AND DOORS
 SPECIFIED ON PLANS.
  
 RESPONSE:
 RESPONSE LETTER FROM MCNAMARA/SLAVIA, INC. STATES THAT
 "PLEASE REFER TO ARCHITECTURAL SHEET A550 FOR TH
 STOREFRONT AND DOOR ASSEMBLIES. THEY MATCH THE
 PREVIOUSLY APPROVED NOA'S FOR THE BASE BUILDING".
  
 (A)PRODUCT APPROVALS SUBMITTED AND PRODUCT APPROVALS
 LISTED ON SHEET A550 DON'T MATCH. REVISE AS REQUIRED TO
 MATCH.
  
 (B) STOREFRONT ENGINEERED DRAWINGS SUBMITTED WITH THE
 DOORS AND STOREFRONT PRODUCT APPROVALS NEED TO HAVE THE
 ENGINEER'S (THOMAS J. TWOMEY) SEAL AND SIGNATURE AS
 REQUIRED BY CHAPTER 471 F.S. WHEN SUBMITTING DOCUMENTS
 FOR PUBLIC RECORDS. ENGINEER DRAWINGS SUBMITTED
 NOTE: THIS IS A DIGITAL SUBMITTAL. NEED DIGITAL
 SIGNATURE ON DIGITAL SUBMITTALS.
  
 4- OK.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-04-25 Cont ID  
Sent By jgomez Date 2019-04-25 Time 13:31 Rev Time 0.00
Received By jgomez Date 2019-04-24 Time 17:10 Sent To  
Notes
2019-04-25 13:32:52BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 SEC. 801.3 FBC-EXISTING BUILDING.
  
  
 1- THERE IS A NOTE ON THE ENLARGEMENT DETAIL 1 ON SHEET
 S200 STATING "EXISTING LIGHT GAUGE WALLS TO REMAIN. ANY
 WALL THAT REQUIRED TO INSTALL THE NEW STEEL FRAMING
 SHALL BE BUILT BACK PER THE ORIGINAL BASE BUILDING
 DRAWINGS".
 ENGINEER OF RECORD NEEDS TO PROVIDE COMPLETE DETAILS
 AND SPECIFICATIONS FOR THE FRAMING OF THE WALL THAT IS
 GOING TO BE BUILT TO RECEIVE THE NEW STOREFRONT. SEC.
 1609.1 FBC.
  
 2- WALL SECTIONS ON SHEET S320 NEED TO PROVIDE COMPLETE
 SPECIFICATIONS FOR THE CONSTRUCTION OF THE PARAPET.
 NEED TO SPECIFY THE GAUGE OF THE STEEL STUDS AND
 PROVIDE FASTENER SPECIFICATIONS. SEC. 1609.1 FBC.
  
 3- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR THE NEW STOREFRONT SYSTEM AND DOORS
 SPECIFIED ON PLANS..
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
 NEW ADDRESS WILL BE W104. SEE E-MAIL BELOW DATED
 05/01/19
  
 MICHAEL,
  
 AS WE DISCUSSED, WE WILL MOVE FORWARD USING THE W104
 ADDRESS FOR THE PROJECT AND FUTURE ADDRESS. WE WILL
 RETIRE THE W 103 ADDRESS..
  
 BILL DUFFY
 772-532-6523
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2019-04-20 Cont ID  
Sent By fgiaquin Date 2019-04-20 Time 08:41 Rev Time 0.00
Received By fgiaquin Date 2019-04-20 Time 08:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-04-04 Cont ID  
Sent By scaldero Date 2019-04-04 Time 09:00 Rev Time 0.00
Received By scaldero Date 2019-04-04 Time 08:54 Sent To  
Notes
2019-04-04 09:00:55PERMIT # 19030914
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING
 (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE
 FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 2) PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN
 STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE
 MAINTAINED AT ALL TIMES.
  
 3) SEPARATE PERMITS REQUIRED FOR ALL WORK DONE RELATED
 TO THE FIRE ALARM AND SPRINKLER SYSTEM.
  
 4) WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
  
 SUE ELLEN CALDERON
 ASST. FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-06-04 Cont ID  
Sent By jgomez Date 2019-06-04 Time 09:33 Rev Time 0.00
Received By jgomez Date 2019-05-29 Time 14:07 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-16 Cont ID  
Sent By jgomez Date 2019-05-16 Time 14:35 Rev Time 0.00
Received By jgomez Date 2019-05-03 Time 09:57 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-04-25 Cont ID  
Sent By jgomez Date 2019-04-25 Time 13:35 Rev Time 0.00
Received By jgomez Date 2019-03-29 Time 09:44 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-04-25 Cont ID  
Sent By jgomez Date 2019-04-25 Time 13:33 Rev Time 0.00
Received By jgomez Date 2019-04-25 Time 13:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-05-16 Cont ID  
Sent By shill Date 2019-05-16 Time 10:06 Rev Time 0.00
Received By shill Date 2019-05-16 Time 10:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-04-25 Cont ID  
Sent By jgomez Date 2019-04-25 Time 13:34 Rev Time 0.00
Received By jgomez Date 2019-04-25 Time 13:33 Sent To  
Notes
2019-04-25 13:35:22SIGNATURES SEEM TO BE OK. THEY WILL BE REVIEWED AGAIN
 AFTER RE-SUBMITTAL. JG.

Review Stop Z ZONING
Rev No 2 Status P Date 2019-06-03 Cont ID  
Sent By eschneid Date 2019-06-03 Time 15:14 Rev Time 0.25
Received By eschneid Date 2019-06-03 Time 15:14 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2019-04-03 Cont ID  
Sent By eschneid Date 2019-04-03 Time 10:50 Rev Time 0.50
Received By eschneid Date 2019-04-03 Time 10:50 Sent To  
Notes
***NONE***